Filling pistol
G
Select the appropriate spacer
tube for cell type that is to be
topped-up. Refer to the spacer
tube list in the tables (see page 4)
for correct spacer tube
identification. The spacer tubes
are individually marked with an
identity letter.
G
Attach spacer tube to the front
end of the probe by orienting the
spacer tube so that the stepped
inside diameter is placed on the
probe first.
G
Push the spacer tube completely
against the probe top so that
there is NO visible space between
the spacer tube and the probe
top (refer to the pictures below).
G
Open vent cap of cell and insert
probe into cell until spacer tube
sits on open vent hole.
G
Press and hold handle until the
pistol automatically stops
dispensing water and release
handle.
G
Remove the probe from the cell.
G
Repeat topping-up other cells.
Note:
•
There will be some water that
drips out of the probe after the
handle is released. Let this
drain into the cell or to another
desirable location.
Caution:
•
Use correct spacer tube to
prevent overfilling or underfilling.
•
Only use distilled or de-ionized
water. NEVER use tap water.
•
Topping-up equipment should be
dedicated to Ni-Cd batteries.
Correct installation for specified spacer tubes (see page 4)
Spacer tubes
“
A
”
to
“
F
”
and
“
H
”
Spacer tube
“
G
”
Total filling pistol length (mm)
625
Packaging dimensions (mm)
810 x 200 x 50 (L x W x H)
Kit of 8 spacer tubes supplied
(marked
“
A
”
to
“
H
”
)
To function correctly, the filling pistol requires
1 to 1.7 bar
Filling pistol
Operation procedure