background image

Power terminals M6

Heat sink

Grounding point M3

Handle

Handle

Unit 1

Unit 1

bus

bus

bus

bus

Unit 2

Unit 2

Unit 3

Unit 3

Unit 

n

Unit 

n

Emergency vent ports

+

+

+

+

+

+

+

+

+

+

-

-

-

-

-

-

-

-

-

-

5. Transportation   

Use the original packaging or 
equivalent. Follow the necessary 
transportation rules for Li-ion 
batteries by consulting with your 
company’s standard practice and 
your local transportation regulations. 
Secure the Evolion

® 

2.1  kWh  to  prevent 

violent shock and other items from 
falling onto it. The Evolion

® 

2.1  kWh 

must be OFF during transportation.

6. Installation   

See Figure 4 for Evolion

® 

2.1 kWh 

features.

Pin 1

RS485+

Pin 2

RS485-

Pin 3

Ground (isolated from power terminals)

Pin 4

Wake up (ground referenced)

Pin 5

Reserved

Pin 6

Reserved

Pin 7

Dry contact alarm output

Pin 8

Dry contact alarm output

IMPORTANT:

 A reverse connection 

on the power terminals may cause 
an internal fuse fault. See Section 
10 if replacing the fuse is necessary.

Connect communication

See Table 4 for RJ45 jack pin 
assignments.

Table 4 - RJ45 pin assignments 

Both RJ45 jacks are interchangeable 
and can be used to plug either the 
communication cable (772518) or 
the RJ45 resistor cap (773455).
To access the dry contact alarm 
signal, use pins 7 and 8. Both minor 
or major alarm signals are reported 
and the default state of the pin is as 
follows:
CLOSED = ALARM/power down
OPEN    = NO ALARM
Use the communication cable 
provided. See Figures 7 and 8.

Make sure to conduct an 
Evolion

® 

2.1  kWh  Installation  and 

Commissioning (I&C) prior to 
startup. Setting a unique node 
ID (default = 1) for each parallel 
connected Evolion

®

 is necessary in 

order to communicate using the 
Saft Evolion

® 

Toolbox software during 

operation.

IMPORTANT:

 Never connect the 

power terminals in series with other 
Evolion

® 

2.1  kWh units. The Evolion

® 

2.1  kWh may be damaged and 
rendered inoperable.

IMPORTANT:

 Parallel connecting can 

be done as long as the total system 
discharge current never exceeds 
130 A (5 kW at 42 V) continuous.  
In this case paralleling any number of 
units is allowed.

Make sure to never parallel connect 
Evolions that have more than 2 V 
difference between the modules. 
Equalizing the voltage by charging or 
discharging modules separately may 
be necessary. To check the open 
circuit voltage when disconnected, 
press the ON/OFF button for at least 
2 seconds and measure the voltage 
at the terminals. Make sure to turn 
the unit OFF by pressing the ON/OFF 
button for at least 4 seconds.
The Evolion

® 

2.1  kWh  limits  its 

own current with a built in charge 
regulated circuit. However, starting 
up the Evolion

® 

to avoid the charge 

regulated mode is important to avoid 
a possible internal fuse fault.
Make sure to switch off the battery 
breaker(s) before connecting Evolion

® 

2.1  kWh power terminals to the 
power bus.
The Evolion

® 

2.1  kWh  power  terminals 

can be connected to systems with a 
positive ground, a negative ground or 
a floating ground system.
In order to prevent reverse connections, 
make sure to measure and note the 
polarity of the power bus cables.

Never block the heat sink.

Do not obstruct the emergency 
vent ports.

Install in environment with IP55 
(NEMA3 outdoor) or higher 
protection index.

95% maximum humidity  
(non-condensing)

Overall installation steps  
(details follow):
1. Connect power
2. Connect communication (optional)
3. Startup

Required tools

• 10 mm socket (for terminal)
• Multimeter (60 Vdc, ohms)
• Flat screwdriver (for cover removal)
• 7 mm socket (for fuse)
• Torque wrench (insulated)

Connect power

Always connect the Evolion

® 

2.1  kWh 

using the provided cables in order 
to balance the resistance in each 
branch. See Figures 5 and 6 for power 
connections schematics and options.

Figure 4 - Evolion

® 

2.1  kWh  features 

(oriented upright with front and back view) 

Figure 6 - Parallel connecting Evolions

OPTION 1 - For any 

number of 

parallel 

chained

 Evolions, 

take off the power 

bus connection 

at the end of the 

parallel connected 

system. This is the 

best way to balance 

the resistance of 

each.

NOTE: Can only be 

used when the total 

continuous bus 

current is less than 

or equal to 63 A.

OPTION 2 - For any 

number of 

direct 

connected 

Evolions, 

using the same 

length of cable 

for each will make 

sure to balance the 

resistance.

Figure 5 - Connecting to terminals

•  Only use the terminal bolts, washers, 

terminal protectors and cable lugs 

provided.

•  Terminal bolt torque = 6 N.m (53 in.lbs)

Summary of Contents for Evolion 2.1 kWh

Page 1: ...arge in less than 3 weeks and render the unit inoperable It is mandatory to check the SOC every 6 months while in a long storage period See Figure 3 and Table 2 If the Evolion 2 1 kWh is stored at a low SOC for too long it may eventually over discharge and render the unit inoperable To conduct a maintenance charge Connect according to Section 6 Make sure the set point voltage on the rectifier is 5...

Page 2: ...hat have more than 2 V difference between the modules Equalizing the voltage by charging or discharging modules separately may be necessary To check the open circuit voltage when disconnected press the ON OFF button for at least 2 seconds and measure the voltage at the terminals Make sure to turn the unit OFF by pressing the ON OFF button for at least 4 seconds The Evolion 2 1 kWh limits its own c...

Page 3: ...e Evolion 2 1 kWh when it is connected the power bus This may cause a fuse fault When the Evolion 2 1 kWh is ON the LED s are active indicating its operational status see Table 6 The Evolion 2 1 kWh will accept charge current only when the temperature is above 30 C and below 75 C 22 F and 167 F Discharging The Evolion 2 1 kWh will discharge above 30 C and below 75 C 22 F and 167 F The maximum allo...

Page 4: ...o maintenance but checking its state and taking necessary action during periodic site routines is recommended The SOC can be checked while in operation Refer to Figure 3 and Table 2 Check if the heat sink area is obstructed or accumulated with dirt and debris As necessary un obstruct or clean using a non metallic brush or a dry or damp cloth Do not use any cleaning solvents or soaps Do not immerse...

Reviews: