background image

SDC-650 Multiple door controller 

Step 3: Connecting the RS-485 reader network 

 

 

Copyright© 2015 

– Saflec Systems (Pty) Ltd. 

http://www.saflecsystems.co.za 

 

Step 3: Connect the RS-485 controller network

 

All controllers in a specific network will be connected together via an isolated multi-drop RS-485 
network. This network will be connected as detailed in the figure below. 

 

 

 

 

 

Figure 5 

Wiring configuration for multiple controllers on the RS-485 controller network 

 

NOTE: 

The RS-485 network requires termination on the first and last controller on the line by 

shorting J6. Controllers in the middle of the line must not have the termination jumper inserted as 
this can cause network problems. 
 
In the diagram above you will see that the controller on the left is terminated while the controller 
on the right isn’t. This is because the cables go off to another controller; hence the controller is in 
the middle of the line and must not be terminated. 

 

Step 4: Connecting the RS-485 device network

 

All readers or IO expansion boards are connected to each other via an RS-485 multi-drop network 
which is connected to the controller as detailed in the figure below. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 6 

Wiring configuration for an SSR reader on the RS-485 device network 

 

Summary of Contents for SDC-650

Page 1: ...nputs Up to 16 SDC controllers can be linked using a protected RS 485 network The PC can connect to it using either RS 232 or the built in Ethernet connector or through the RS 485 network from another...

Page 2: ...SDC 650 Multiple door controller 2 Introduction Copyright 2015 Saflec Systems Pty Ltd http www saflecsystems co za Figure 2 Possible position for an SDC 650 in a SACS access control system...

Page 3: ...wer the panel will be active If the screen is blank it will be in screen saving mode Tapping any button will awaken the screen and allow you to configure the device Figure 3 The configuration and diag...

Page 4: ...ations network Each controller on this network requires a unique address for communications and identification Duplicate addresses will cause communication problems The address of the controller can b...

Page 5: ...and last controller on the line by shorting J6 Controllers in the middle of the line must not have the termination jumper inserted as this can cause network problems In the diagram above you will see...

Page 6: ...mmunicate with the host system This can be done through either the Ethernet connection or the RS 232 connection The Ethernet cable is a non power over Ethernet cable to an RJ 45 plug The typical wirin...

Page 7: ...at the controller board with the power connector on the top right of the board the inputs are arranged in ascending order from left to right with a shared common between each input pair See the diagra...

Page 8: ...for the output relays Figure 12 Example wiring for an externally powered magnetic lock Normally closed Output mode 2 Internally powered outputs To set the output to internally powered mode place two j...

Page 9: ...loads such as strike locks care should be taken to prevent a back EMF voltage spike In order to do this a freewheeling diode also known as flyback diode should be connected across the load as seen in...

Page 10: ...Figure 16 The Web interface front page It shows basic diagnostics information on the main page but the links at the bottom will require a username and password for authentication The default username...

Page 11: ...contact Maximum voltage AC 250Vac Maximum voltage DC 220Vdc Internally powered Outputs Maximum combined current 3 7A Recommended maximums per relay 750mA at 12Vdc Externally powered Outputs Recommende...

Page 12: ...SDC 650 Multiple door controller 12 Copyright 2015 Saflec Systems Pty Ltd http www saflecsystems co za Notes...

Reviews: