safgard 550 Series Manual Download Page 4

MAXIMUM PRESSURE:

250 PSI

INPUT VOLTAGE: 

120 VAC, 60 HZ

SWITCH RATINGS:

5.8 FLA, 34.8 LRA

SWITCH CONTACTS:

SPDT

ALARM CIRCUIT: 

125 VA @ 120 VAC
Pilot Duty

DIMENSIONS

SPECIFICATIONS

LIMITED MANUFACTURER’S WARRANTY

We  warrant  products  manufactured  by
Hydrolevel  Company  to  be  free  from  defects  in
material  and  workmanship  for  a  period  of  two
years  from  the  date  of  manufacture  or  one  year
from  the  date  of  installation,  whichever  occurs
first. In the event of any claim under this warran-
ty  or  otherwise  with  respect  to  our  products
which is made within such period, we will, at our
option, repair or replace such products or refund
the  purchase  price  paid  to  us  by  you  for  such
products.  In  no  event  shall  Hydrolevel  Company

be  liable  for  any  other  loss  or  damage,  whether
direct,  indirect,  incidental  or  consequential.  This
warranty is your EXCLUSIVE remedy and shall be
IN  PLACE  OF  any  other  warranty  or  guarantee,
express  or  implied,  including,  without  limitation,
any  warranty  of  MERCHANTABILITY  or  fitness
for  a  particular  purpose.  This  warranty  may  not
be assigned or transferred and any unauthorized
transfer  or  assignment  thereof  shall  be  void  and
of no force or effect.

126 Bailey Road
North Haven, CT 06473
Phone: (203) 776-0473
FAX: (203) 764-1711

www.hydrolevel.com

5

9

/

16

1

1

/

16

5

1

/

2

3

1

/

16

BACK

3

7

/

8

1

5

/

8

1

1

/

8

1

5

/

8

2

3

/

8

BOTTOM

FITTINGS

Controls equipped with the EL1214-SV Probe can be mounted in standard reducing tees (supplied by others). Safgard manifolds, listed below, can be used

with all probe models.

MODEL

PSI

SIZE

FOEM-1

160

1 1/2" x 1 1/2" x 3/4"NPT

FOEM-2

160

1" x 1" x 3/4"NPT

FOEM-3

160

1 1/4" x 1 1/4" x 3/4"NPT

1214C-2 TEE

250

1" x 1" x 3/4"NPT

FOEM MANIFOLD

1214C-2 TEE

021218

MAINTENANCE:

Remove and inspect probe annually. Clean any scale or build-up from the probe using a scouring pad or steel wool. Re-install the probe and

test the control operation in accordance with the Operating Instructions. If the probe is installed in an equalizing line of a steam boiler, the equalizing line

should be blown down weekly.

Test Pressure: 1000 PSI, All Models

PROBE DATA

2"

SQUARE

1

7

/

8

"

3

13

/

16

"

15

/

16

"

1"

3

/

4

" NPT

5

/

16

"

2"

SQUARE

1

1

/

16

"

3"

15

/

16

"

1"

3

/

4

" NPT

5

/

16

"

2"

SQUARE

1

7

/

8

"

4

9

/

16

"

1"

3

/

4

" NPT

5

/

16

"

1

11

/

16

"

EL1214 – STANDARD MODEL – 3/4" NPT

For 1/2", order Model EL1220

EL1214-SV – 3/4" NPT

For 1/2", order No. EL1220-SV

EL1214-P – 3/4" NPT

Reviews: