automatically re-energize after the unsafe levels of CO clears.  
Select a wall location at least 

4” off the floor. 

60-542-R 

Cut a 5 5/8” 

(143mm) W x 3 1/8” (79mm) H hole.

 60-541-R drill 

1/4” (6mm) hole

 

for the wires. 

2.

 

 Do not connect to  a previously  installed solenoid.

 

SEE: 

SPECIAL WIRING NOTICE. 

 

3.

 

Connect Supply (+) to the Red wire lead.  Install a 5 amp fuse in the         
positive (+) circuit. Connect the Black wire to the 12 volt Ground (-). 

4.

 

Reconnect the power supply. Warm up 10 minutes then test the alarm. 

 

 

 

 

MODEL  65-541-MS / 65-542-MS

 

1.

 

Model 65-541/65-542-MS Multi-station interconnect

(Maximum 10 

units and 2000 feet of wire)

. Allows multiple 65-541/542MS alarms to 

be connected together.  When one of the alarms detects unsafe levels of 
CO or gas it will activate.  It will also activate the audible alarm of all 
the interconnected units.  Only the alarm that detected CO or gas will 
have its Red LED light lit up so that you can determine the cause of the 

alarm.   Select a wall location no between 4” and 20” off the floor. 

60-

542-MS Cut a 5 5/8

” (143mm) W x 3 1/8” (79mm) H hole.

 60-541-MS 

drill 

1/4” (6mm) hole

 for the wires.   

2.

 

 Connect the Red wire to the 12 volt supply (+). Install a 1 amp fuse in 
the positive circuit (+). 

Note you must use a separate 1 amp fuse for 

each alarm.  

Connect the Black wire to the 12 volt Ground (-). 

3.

 

Interconnect Wiring 

 Connect Blue wires from each alarm and Yellow 

wires for each alarm. Continue connecting in series (Daisy Chain). 

4.

 

Reconnect the power supply. Warm up 10 minutes then test the alarm. 

 

 

 

MODEL 65-541-R-MS / 65-542-R-MS   

1.

 

Model 65-541-R/65-542-R-MS - With Normally Closed relay.

 This 

unit supplies a relay with contacts rated12 VDC, 3 amp (max). The 
relay is energized whenever the alarm is operational. It may be used to 
shut down a generator or to open an (optional) gas solenoid valve. The 
relay may also be used to interface to alarm systems, using either the 
normally closed or normally open contact, depending on the 
requirements of the alarm system. In the event of an alarm the relay 
will shut off.  It will automatically re-energize after the unsafe levels of 
CO  clears.  
 Select a wall location at least  

4”  off the floor. 

65-541-R-MS Cut a 5 

5/8” (143mm) W x 3 1/8” (79mm) H hole.

65-542-R-MS drill 

1/4” 

(6mm) hole

 for the wires.  

2.

 

 

Do not connect to an existing installed solenoid.

 

SEE: 

SPECIAL WIRING NOTICE. 

 

3.

 

Connect Supply (+) to the Red wire lead.  Install a 5 amp fuse in the         
positive (+) circuit. Connect the Black wire to the 12 volt Ground (-). 

4.

 

Interconnect Wiring - Connect Blue wires from each alarm and Yellow 
wires from each alarm. Continue connecting in series (Daisy Chain).

 

5.

 

Reconnect the power supply. Warm up 10 minutes then test the alarm.

 

 

Model 65-541-R-MS / 65-542-R-MS Wiring

 - 

 

 

 

Only use UL or recognized permanent wire connectors to 
replace any unit installed with spade connectors or wire nuts.

 

  

TEST PROCEDURE

 

!

 WARNING 

TO  REDUCE  THE  RISK  OF  CARBON  MONOXIDE  POISONING, 

TEST  THIS  ALARM’S  OPERATION  AFTER  THE  RV  HAS  BEEN 

IN  STORAGE,  BEFORE  EACH  TRIP  AND  AT  LEAST  ONCE  PER 
WEEK DURING USE BY PRESSING THE TEST/RESET BUTTON

!

 

WARNING 

WARNING:  THE  TEST  BUTTON  ONLY  TESTS  THE 
ALARM  CIRCUIT  NOT  THE  SENSORS.  TO  TEST  THE  CO 
SENSOR USE A CAN OF SAFE-T-ALERT CO TEST GAS TO 
TEST THE 400 PPM CALABRATION POINT. DO NOT TRY 
TO GENERATE CO TO TEST THE ALARM.

  The TEST/RESET 

button tests all ELECTRICAL functions of the alarm. It does not check the 
sensor operation. 

The alarm may be tested at any time. The TEST/Mute switch is located on 
the  front  of  the  alarm.  Press  and  hold  the  test  button  for  1  second 

IMPORTANT

 - 

 If this alarm does not test properly return it immediately 

for repair or replacement. If the alarm is over five years old replace it. 

 

SPECIAL WIRING NOTICE. 

 

 

 

 

 

OPERATION

 

 When the unit is first powered up, the CO sensor requires a ten (10) minute 
initial warm-up period to clean the sensor element and achieve stabilization. 
The  GREEN  LED  indicator  will  flash  on  and  off  during  the  10  minute 
warm-up  period.  This  unit  cannot  go  into  a  alarm  during  the  warm-up 
period.  See Test Procedure in this manual.  After the warm-up period, the 
GREEN power ON indicator should glow continuously

 

If the ON indicator 

light  does  not  light,  see  the  section, 

Trouble-Shooting  Guide

,  in  this 

manual for further information.  

Do not attempt to fix it yourself. 

!

 DANAGER - FIRE RISK -  DO NOT CONNECT A 

SAFE-T-ALERT alarm to non Safe-T-Alert supplied 
solenoid. You must use a new solenoid with the correct 
electrical rating. 

 