WFDTNRN Vane-type Waterflow Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

IMPORTANT

Please Read Carefully And Save
This instruction manual contains important information about the installation and 

operation of waterflow detectors. Purchasers who install waterflow detectors for use 

by others must leave this manual or a copy of it with the user. Read all instructions 

carefully before beginning.

CAUTION

The model WFDTNRN is a vane-type waterflow detector for use in wet-pipe fire 

sprinkler systems only. Vane-type waterflow detectors shall not be used as the sole ini-

tiating device in both deluge and preaction systems; waterflow detectors used in these 

types of systems may result in an unintended discharge caused by a surge, trapped air 

or a short retard time.

WARNING

Installation must be performed by qualified personnel and in accordance with all na-

tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death 

could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could 

result.

PRINCIPLES OF OPERATION

Vane-type waterflow detectors mount to water filled pipes in fire sprinkler systems. 

Waterflow in the pipe deflects a vane. Deflection of the vane produces a switched out-

put. All detectors will activate on a sustained flow of water greater than 10 gallons per 

minute (gpm) but will not activate if the flow rate is less than 4 gpm.

COMPATIBLE PIPE TEES/RISERS

Model WFDTNRN is supplied with 12 paddles. One paddle is provided for each size 

of the threaded, sweat or plastic tee. See Figure 1 and approximate tee depth chart. 

Each paddle has an indication that shows the pipe size and type of tee to be used with.

FIGURE 1. MOUNTING DIMENSIONS

3-1/2"

2-5/8"

4"

TEE DEPTH

DESIGNED TO FIT WITHIN 2 X 4 STUD WALL CONSTRUCTION

PLASTIC VANE

TEE FITTING

INSTALLATION GAUGE

END OF PADDLE TREE MUST

FIT BETWEEN TOP OF TEE

AND BOTTOM OF FLANGE

TEE

ADAPTER

INSTALLATION GUIDELINES

Before installing any waterflow alarm device, be thoroughly familiar with:
NFPA 72:   Installation, Maintenance and Use of Local Protective Signalling Sys-

tems

NFPA 13:  Installation of Sprinkler Systems, specifically Section 3.17

NFPA 25:   Inspection, Testing and Maintenance of Sprinkler Systems, specifically 

Chapters 4 and 5, and Section 5.3.3.2

NFPA 13D:  Standard for Residential Dwellings

NFPA 13R:  Standard for Multifamily Dwellings

FIGURE 2. ASSEMBLY DIAGRAM

COVER

FLOW

COVER TAMPER

SWITCH (OPTIONAL P/N CTS)

TIMER

ASSEMBLY

(P/N FS-RT)

GASKET

ACTUATOR

LEVER

WATERFLOW

GROUND SCREW

MOUNTING

PLATE

PADDLE

1" NPT

THREAD

TAMPER PROOF

WRENCH (P/N WFDW)

FILISTER HEAD

SCREW

SPECIFICATIONS

Contact Ratings: 

10 A @ 125/250 VAC 

2.5 A @ 24 VDC 

Triggering Threshold Bandwidth (Flow Rate): 

4 to 10 GPM

Static Pressure Rating: 

250 PSI (Max.)

Dimensions (Installed): 

4in H x 3½ in W x 6¾ in D

Operating Temperature Range: 

32°F to 150°F (0°C to 66°C)

Shipping Weight: 

2 lbs

Enclosure Rating: 

NEMA 4

U. S. Patent Number: 

5,213,205

I56-4044-E

W0388-01

W0390-00

APPROXIMATE TEE DEPTH REQUIREMENTS (SEE FIGURE 1)

Tee Depth

Threaded

Sweat

CPVC NIBCO/

SPEARS 

(no insert)

CPVC 

SPEARS 

(with insert)

CPVC/Tyco

1 × 1 × 1"

2

1

/

8

"

1

3

/

4

"

2

1

/

8

"

2

15

/

32

"

2

13

/

16

"

1

1

/

4

 × 1

1

/

4

 × 1"

2

1

/

2

"

2

1

/

8

"

N/A

N/A

N/A

1

1

/

2

 × 1

1

/

2

 × 1"

2

3

/

4

2

1

/

4

"

3"

3"

N/A

2 × 2 × 1"

3

1

/

4

"

2

3

/

4

"

N/A

N/A

N/A

  

I56-4044-E 

 

 4/21

Summary of Contents for WFDTNRN

Page 1: ...vided for each size of the threaded sweat or plastic tee See Figure 1 and approximate tee depth chart Each paddle has an indication that shows the pipe size and type of tee to be used with FIGURE 1 MOUNTING DIMENSIONS 3 1 2 2 5 8 4 TEE DEPTH DESIGNEDTO FITWITHIN 2 X 4 STUDWALL CONSTRUCTION PLASTICVANE TEE FITTING INSTALLATION GAUGE END OF PADDLETREE MUST FIT BETWEENTOP OFTEE AND BOTTOM OF FLANGE T...

Page 2: ...h provided Move the ac tuator lever back and forth to check for binding If the vane binds remove the detector and correct the problem before proceeding CAUTION Be sure the direction of flow arrow and directional cover points in the correct direc tion otherwise a waterflow condition will go unreported See Figure 3 FIGURE 3 DIRECTIONAL COVER OPERATIONAL TESTING Always notify a central station monito...

Page 3: ...ty having jurisdiction for leaks and replace if leaks occur Test detectors at least quarterly as described in Operational Testing to insure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the switch enclosure becomes faulty request Part No FS RT and ensu...

Page 4: ...sprinkler water supply should be sealed or locked in the normally open position The normally open position should be monitored by a sprinkler supervisory switch THREE YEAR LIMITED WARRANTY SAFE SIGNAL warrants that the equipment herein shall conform to said descriptions as to all af firmation of fact and shall be free from defects of manufacture labeling and packaging for a pe riod of three 3 year...