1.   Waterflow detectors may not work or operate properly if sprinkler piping being monitored 

is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should 

be checked regularly for such blocking material, following the instructions in Chapter 5 of 

NFPA Standard 13A.

2.   Alarms generated by the activation of waterflow detectors may not be received by a central 

station if telephone or other communication lines to the detector are out of service, disabled, 

or open.

3.   Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water systems, 

however, may substantially reduce waterflow detector service life.

WARNING

THE LIMITATIONS OF WATERFLOW ALARM DEVICES

4.   Waterflow detectors are not a substitute for insurance. Building owners should always insure 

property and lives being protected by sprinkler systems.

5.   If valves controlling the water supply to a sprinkler system are closed, vane-type waterflow 

detectors will not work. All valves controlling a sprinkler water supply should be sealed or 

locked in the normally open position. The normally open position should be monitored by 

a sprinkler supervisory switch.

FIGURE 6. FIELD WIRING

UL-LISTED
COMPATIBLE
CONTROL PANEL

POWER
24VDC OR
120 VAC

SUGGESTED EOL
RESISTOR

SSM24-X
SSV120-X

NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFECTED, 
I.E.,WHEN WATER IS FLOWING. 
DUAL SWITCHES PERMIT 
APPLICATIONS TO BE COMBINED 
ON A SINGLE DETECTOR.

CONTACT RATINGS

SCHEMATIC OF
INDIVIDUAL
SWITCH IN
“NO WATERFLOW”
CONDITION

A-NC

COM

B-NO

BREAK WIRE AS
SHOWN FOR 
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.

125 / 250 VAC

24 VDC

10 AMPS

2.5 AMPS

INITIATING

LOOP

W0393-02

UL LISTING LIMITATIONS

In accordance with the UL certification, the model WFDNFT has additional critical installa-

tion limitations when installed in sprinkler systems constructed of metallic pipe and fittings. 

The model WFDNFT must be installed in accordance with the limitations for BlazeMaster

®

 

CPVC pipe and fittings, which limits the installation of the product to systems in Light Hazard 

occupancies as defined in ANSI/NFPA 13, Residential occupancies as defined in ANSI/NFPA 

13R, and Residential occupancies as defined in ANSI/NFPA 13D. All Listing limitations of  

BlazeMaster

®

 CPVC pipe and fittings as outlined in BlazeMaster

®

 installation and design manuals 

must be followed for model WFDNFT to be used in accordance with its Listing. These consider-

ations include, but are not limited to: (1) Acceptable installation limitations (concealed, exposed, 

system risers); (2) Chemical compatibility; 3) Handling and storage; (4) Freeze protection and 

proximity to heat sources.

THREE-YEAR LIMITED WARRANTY

SAFE SIGNAL warrants that the equipment herein shall conform to said descriptions as to all af-

firmation of fact and shall be free from defects of manufacture, labeling, and packaging for a pe-

riod of three (3) years from the invoice date to the original purchaser, provided that representative 

samples are returned to SAFE SIGNAL for inspection. Upon a determination by SAFE SIGNAL 

that a product is not as warranted, SAFE SIGNAL shall, at its exclusive option, replace or repair 

said defective product or parts thereof at its own expense except that Purchaser shall pay all   

shipping, insurance, and similar charges incurred in connection with the replacement of the 

defective product or parts thereof. This Warranty is void in the case of abuse, misuse, abnormal 

usage, faulty installation, or repair by unauthorized persons, or if for any other reason SAFE 

SIGNAL determines that said product is not operating properly as a result of causes other than 

defective manufacture, labeling, or packaging.

  

I56-4263-B 

 

 

  4/21

Summary of Contents for WFDNFT

Page 1: ...elays do NOT accumulate they reset if the flow of water stops or drops below minimum triggering flow rate before the entire delay has elapsed All detectors will activate on a sustained flow of water of 10 gallons per minute gpm or greater down stream of the device COMPATIBLE PIPE TEES RISERS The WFDNFT is supplied with 12 paddles One paddle is provided for each size of tee See Figure 1 and approxi...

Page 2: ...r and correct the problem before proceed ing CAUTION Avoidusingapipewrenchtotightenthelockingcollar Over torquingthelockingcollar may cause damage to the detector If additional tightening past hand tight is required on the collar use of a band wrench is recommended to protect collar surface not to exceed hand tight plus 1 notch on collar Be sure the direction of flow arrow and directional cover po...

Page 3: ... applicable NFPA codes and standards and or the authority having jurisdiction for leaks and replace if leaks occur Test detectors at least quarterly as described under Operational Testing to insure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the dela...

Page 4: ...e with the UL certification the model WFDNFT has additional critical installa tion limitations when installed in sprinkler systems constructed of metallic pipe and fittings The model WFDNFT must be installed in accordance with the limitations for BlazeMaster CPVC pipe and fittings which limits the installation of the product to systems in Light Hazard occupancies as defined in ANSI NFPA 13 Residen...

Reviews: