Figure 3-2 Design life and temperature curve
Charge
Floating charge
Charge method: 2.27V / cell with limited current of 0.3 C
10
(A).
Charge voltage must be adjusted according to ambient temperature, temperature
compensation coefficient is -3mV / cell /
℃
.
Floating charge voltage at different ambient temperature, as below table
Temperature
(
℃
)
0
10
20
25
30
35
Floating charge
voltage
(
V/cell
)
2.33
~
2.36 2.30
~
2.33 2.27
~
2.30 2.25
~
2.28 2.24
~
2.27 2.22
~
2.25
Cycle application
Charge method: 2.40V / cell with limited current of 0.25 C
10
(A).
Charge voltage must be adjusted according to ambient temperature, temperature
compensation coefficient is -4mV / cell /
℃
.
When charged capacity is about 105-110% of discharged capacity or in constant voltage case,
the charge current must be kept unchanged for 3 hours in the final stage of charge., charge is
ended.
O
pe
ra
tio
n
an
d
m
ai
nt
en
an
ce
17