Maintenance
1. Cleaning Notes:
Battery appearance, terminal area and working environment must be kept clean and dry.
In battery cleaning process, avoid use of electrostatic cleaning tools.
Clean the battery with damp cloth. Do not use of gasoline, alcohol or other organic solvents;
also do not use cloth containing these substances.
2. Inspection and Maintenance
VRLA batteries are not maintenance-free batteries, battery operation process gradually
changes with time. In order to ensure good battery usage, operational management and
control are very important. To understand the operation status of batteries and equipment
and to prevent accidental damage, regular maintenance is required. Periodically check
and record the measurements using the following method for batteries used in UPS system
room and base station (including outdoor station) site.
2.1 Monthly Maintenance Inspection Items
Item
Content
Standard
Maintenance
1-Temperature
Detection
1-Measure and record
battery terminal and
container temperature
by using infrared
thermometer.
2-Use infrared
thermometer to measure
ambient temperature.
1-Ambient Temp:
-20
℃
~+55
℃
2-Recommended
Temperature:
25±5
℃
1-Check that the battery temperature
compensation functions are turned on and
that the battery temperature probe is
properly installed.
2-Check that the room temperature
conditioning equipment such as
air-conditioning is turned on.
2- Battery Float
Voltage
Measurement
Measure floating voltage
on positive and negative
terminal of the battery
group with multimeter.
Measurement and
control module
display operating
voltage differences
within 0.05V
If the monitoring module shows
inconsistency even after adjusting, replace
or repair it.
3-Battery
Appearance
Inspect
the
battery
container for bulging,
leakage and damage.
Normal
Appearance
Confirm the reason for any abnormal
appearance, if it affects normal use,
replace the battery.
Check for dirt stains
Clean Appearance
Clean dust and dirt with damp cloth
Inspect the connection
cables, terminals, etc.
for oxidation, rust &
other abnormalities
No oxidation, rust
If you find oxidation or rust, replace the
connecting wire, and swab terminal with
Vaseline etc.
O
pe
ra
tio
n
an
d
m
ai
nt
en
an
ce
22
Summary of Contents for sp series