Discharge 

09

 

 

 

End voltage with different discharge rate must be less than the specified value. Charge the battery 
as soon as possible after discharge.

 

In order to extend the service life, the depth of discharge should be less than 60% of the rated

 

capacity. The discharge over 60% DOD is deep discharge and would shorten the service life.

 

Under the temperature of -25

,discharge over 60% DOD is prohibited, except protective measure 

is adopted such as raising temperature.

 

 

 

 
 

Temperature

 

 

 

The operation temperature range is -20

--55

. All the performance data is measured at ambient

 

temperature of 25

.The optimal temperature is 25

±5

, over high temperature would shorten the 

service life and over low temperature would lower the capacity available. The highest acceptable 
temperature is 55

.

 

 

 

 

 

Floating Charge and Equalizing charge

 

 

 

Floating charge

 

 

Floating operation is the best operation condition for battery. In floating operation, the battery 
keep fully charged state,under this condition,battery could reach the longest service life.Under

 

the temperature of 25

, recommended floating charge voltage setting value is 2.23V/ cell,

 

In such method,it take about 24~36h for battery fully charged.   For achieving better 
performance, the floating charge voltage should be suitable adjusted according to ambient 
temperature, temperature compensation coefficient is -3.5mV/

/cell, for details please refer to 

Table 4-1.

 

Summary of Contents for 6FMJ-100

Page 1: ......

Page 2: ...t Series 04 2 Battery and Terminal Layout 05 Chapter Three Technical Characteristics 1 Performance Curve 06 Chapter Four Operation 1 Discharge 09 2 Temperature 09 3 Floating Charge and Equalizing char...

Page 3: ...hall be replaced by manufacturer s service center If there is need to replace and maintain please contact after sale service center Used battery is recyclable and improper disposal of battery may be g...

Page 4: ...pen and close acid filter in valve preventing acid fog escape and preventing out flame in when depression Long service life The grid is made of lead calcium tin alloy with corrosion proof character an...

Page 5: ...ensures it can work in high temperature or over discharge condition preventing dry up of the battery Thick ABS container and cover with high impact proof vibration prood prevents leakage and container...

Page 6: ...nch mm inch mm inch kg lbs 6FMJ 65 12 65 310 12 20 174 6 85 209 8 23 236 9 29 27 59 4 1540 7 25 GFM 24 6FMJ 85 12 85 414 16 30 174 6 85 218 8 58 228 8 98 34 74 8 2060 5 19 GFM 24 6FMJ 100 12 100 513 2...

Page 7: ...Type and Dimensions Battery and Terminal Layout Battery Layout 6FMJ 65 05 6FMJ 85 Terminal Layout 6FMJ 100 120 150 200 Terminal GFM 24...

Page 8: ...tics Performance Curve 06 Cycle performance curve 25 Voltage curve of simulation wind energy system cycle application Large cycle discharge voltage curve Shallow cycling at not fully charged state Sha...

Page 9: ...aracteristics 07 Discharge capacity and temperature curve Temperature Figure 3 3 Discharge capacity curve under different temperature Service life and temperature curve Figure 3 4 Floating service lif...

Page 10: ...ic curve under different depth of discharge 25 08 120 1 2 2 5 100 80 60 40 20 1 0 0 8 0 6 0 4 0 2 2 4 2 3 2 2 1 2 1 2 3 4 2 0 1 2 3 4 1 25 D O D 2 50 D O D 3 75 D O D 0 0 0 1 2 3 4 4 100 D O D 0 2 4 6...

Page 11: ...ure of 25 The optimal temperature is 25 5 over high temperature would shorten the service life and over low temperature would lower the capacity available The highest acceptable temperature is 55 Floa...

Page 12: ...be supplementary charged The battery is out of work beyond 6 months Running in full floating operation for a long term but not discharge under more than 40 C10 capacity the batteries need an equalizin...

Page 13: ...harge Recharge the battery immediately after discharge according to the below method Charge the battery with constant current of no more than 0 2C10 A until the battery voltage rises to 2 33 2 37V cel...

Page 14: ...0 1C10 8 7 2 33 18 0 15C10 6 8 2 33 16 Operation Table 4 3 Required charge time in different depth of discharge 12 Storage The battery should be stored in clean and dry environment Storage time batter...

Page 15: ...tery with 2 35V cell for 8 to 12 hours It is necessary to limit the current and the optimum limiting value is within 0 2C10 A Testing of the open circuit with the storage battery can decide whether it...

Page 16: ...rminals to chargers During the installation and transit of the battery use insulted tools gloves aprons and safety glasses avoiding battery is impacted do not twist connecting terminals and safety val...

Page 17: ...Maintenance Repeat every item of monthly inspection Measure and record the floating voltage of each on line battery Annually Maintenance Repeat every item of quarterly maintenance and inspection Check...

Page 18: ...ny metal objects to be put on top of the battery shall be strictly prohibited Please do not use any organic solvent to clean batteries Please do not take down safety valve or add any substance into ba...

Page 19: ...No 1 Shengyang Road Qufu City Shandong Province 273100 P R China Tel 0086 537 4438666 6028 Fax 0086 537 4411936 E mail sales sacredsun cn...

Reviews: