13
5.4 Alarm setting
E.g. To set No. 1 relay output as over voltage alarm, set pulse width as 10.0s, set alarm value as 120.0%, set
hysteresis value as 5.0%, set alarm delay as 1.0s, the operation process is as follows,
Enter programming interface,
select signal input setting menu
Menu
Menu
>3s
Menu
Set relay working mode as alarm mode Alr
Set relay pulse width as 10.0s
Set alarm item as over voltage alarm
Set alarm value as 120.0% of rated value
Set hysteresis value as 5.0% of rated value
Set alarm delay time as 1.0s
Save modified data
and exit programming mode