Operating manual - ChillPAC and LP ChillPAC Mk 3
010823 en 2021.06
43/68
5.3.3
Valve positions during operation, ChillPAC
(water-cooled condenser)
Pos. no. Designation
Position during operation
400
Compressor unit valves
Please see the compressor manual
401
Compressor suction stop valve
Open
402
Compressor discharge stop valve
Open
45
Stop valve for oil recovery / oil return
Open
421
Purging valve
Closed
425
Float valve - expansion
Opens automatically
426
Stop valve - expansion
Open
428
Liquid drain valve (R717)
Closed
431
Stop valve for oil drainage
Open
432
Charge valve (R717)
Closed
433
Stop valve for oil recovery
Open
436
Stop valve for oil recovery
Open
437
Stop valve for oil return
Open
442
Double stop valve
One outlet open / one outlet closed
443
Safety relief valve
(Closed) Fixed set point
444
Safety relief valve
(Closed) Fixed set point
445
Double stop valve
One outlet open / one outlet closed
446
Safety relief valve
(Closed) Fixed set point
447
Safety relief valve
(Closed) Fixed set point
Table 1: Valve positions during operation, ChillPAC