
11
THE FLOW DIAGRAM BELOW ILLUSTRATES THE
PROCEDURES FOR THE FOLLOWING POSSIBLE SCENARIOS:
HEATER RUNNING BUT NO HEAT IS GENERATED
This means that only the fan is functioning and not the heating element, and is likely to be due to the
thermal limiter cutting out to stop the elements getting to excessive temperatures.
i
Remove the bolts from the top of the heating element control enclosure and pull up the lid
taking care of the attached earth cable.
ii
Reset the limiter by pushing the limiter reset button as shown in Image: No.
6
iii
Replace lid ensuring gasket is in place, hand tighten insert all bolts with washers and then
tighten to 3Nm.
HEATER DOES NOT RUN AT ALL
This can be caused by either the input fuses or the motor fuses inside the electrical control box
enclosure tripping. This could be caused by a power supply problem, or misuse of the unit such as
blocking the airflow.
i
Remove the bolts from the top of the electrical control
enclosure and pull up the lid taking care of the attached
earth cable.
ii
Check the 3 input fuses and replace if required with 32A gG
fuse part no. TRASP140032G
iii
Check the 3 motor fuses and replace if required with 4A gG
fuse part no. TRASP14004G
iv
Replace lid ensuring gasket is in place, hand tighten insert
all bolts with washers and then tighten to 3Nm.
If after these actions the heater still does not work or the
problem persists, there is likely to be a fault in the heater
and it should be returned to
SA Equip
for investigation.
Contact the SA Service Centre on
+44 (0)333 240 6111
or
for more details.
Open
element
box and
reset
Replace
fuses
Open
control
box
Does
the heater
function?
Have
any fuses
tripped
Heater not
functioning
Contact
SA Equip
If problem
persists
contact
SA Equip
NO
NO
NO
YES
YES
YES
NO
Does
the fan
run?
Only to be carried out by a
Compex qualified electrician.
Summary of Contents for FLEXIHEAT SAPH18/440
Page 14: ...14 DECLARATION OF CONFORMITY...