S+S Regeltechnik THERMASGARD RTM1-I Operating Instructions, Mounting & Installation Download Page 8

Devices are to be connected under dead-voltage condition. Devices must 
only be connected to safety extra-low voltage. Consequential  damages 
caused by a fault in this device are excluded from warranty or liability. These 
devices must be installed and commissioned by authorised specialists. The 
technical data and connecting conditions shown on the device labels and in 
the mounting and operating instructions delivered  together with the device 
are exclusively valid. Deviations from the catalogue representation are not 
explicitly mentioned and are possible in terms of technical progress and 
continuous improvement of our pro ducts. In case of any modifications made 
by the user, all warranty claims are  forfeited. Operating this device close 
to other devices that do not comply with EMC directives may influence 
functionality. This device must not be used for monitoring applications, 
which serve the purpose of protecting persons against hazards or injury, or 
as an EMERGENCY STOP switch for systems or machinery, or for any other 
similar safety-relevant purposes.
Dimensions of housing or housing accessories may show slight 

 

tolerances on the specifications provided in these instructions. 
Modifications of these records are not permitted. 
In case of a complaint, only complete devices returned in original packing 
will be accepted.

Our “General Terms and Conditions for Business“ together with the 
“General Conditions for the Supply of Products and Services of the 
Electrical and Electronics Industry“ (ZVEI conditions) including 

 

supplementary clause “Extended Retention of Title“ apply as the 

 

exclusive terms and conditions“.

Notes regarding mechanical mounting and attachment:

Mounting shall take place while observing all relevant regulations and  
standards applicable for the place of measurement (e.g. such as welding 
instructions, etc.). Particularly the following shall be regarded:
–  VDE  ⁄  VDI directive technical temperature measurements, measurement 

set - up for temperature measurements.

–  The EMC directives must be adhered to. 
–  It is imperative to avoid parallel laying of current-carrying lines.

We recommend to use shielded cables with the shielding being  attached at 
one side to the DDC  ⁄  PLC.Before mounting, make sure that the existing 
thermometer‘s technical parameters comply with the actual conditions at 
the place of  utilization, in particular in respect of:
–  Measuring range 
–  Permissible maximum pressure, flow velocity 
–  Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

CONNECTING CONDITIONS
Output:   0  - 10  V

The output voltage follows linear to the temperature signal applied at  
the input terminals and generates a proportional output signal of 0 - 10 V. The 
voltage outputs are short-circuit proof against ground wire. Applying voltage 
supply to the output terminals will destroy the device.

Output:   4 ... 20 mA

In case of the 4 ... 20 mA measuring transducer, display and evaluating 
 

elements are connected in series in the current loop. The measuring 

 

transducer thereby liWiths the flowing current in variance of the input signal. 
4 mA are for the measuring transducer‘s internal current consumption. The 
apparent ohmic resistance can either be connected in the plus or minus path 
of the measuring transducer. In case of an apparent ohmic resistance in the 
plus path, power supply and resist.

SAFETY REGULATIONS

These devices shall only be used for their intended purpose. Respective 
safety regulations issued by the VDE, the states, their control authorities, 
the TÜV and the local energy supply company must be observed. The buyer 
has to ensure adherence to the building and safety regulations and has to 
avoid all dangers of any kind. We do not assume any warranty for faults or 
damages arising or resulting from improper use of our equipment or from 
non-observance of operating instructions. These instruments must be 

 

installed by authorised specialists only!

Preferably shielded cables should be used in order to prevent damages  ⁄  
errors. It is imperative to avoid laying parallel with current-carrying lines. 
EMC directives must be adhered to.

Notes on commissioning:

This device was calibrated, adjusted and tested under standardised conditions. 
When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at 
regular intervals. 

Commissioning is mandatory and may only be performed 

by qualified personnel! 

G  

Installation and Commissioning

G  

General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical 

and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be 

observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the 

TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent 

perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve-

ment of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation 

by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read installation and commissioning and all notes provided therein are to be regarded!

Summary of Contents for THERMASGARD RTM1-I

Page 1: ...mit Mehrbereichsumschaltung und aktivem Ausgang G Operating Instructions Mounting Installation Room temperature measuring transducers calibratable with multi range switching and active output F Notice...

Page 2: ...hnung Geh use Baldur1 Dimensional drawing Housing Baldur1 Plan cot bo tier Baldur1 Baldur1 Ma zeichnung Geh use Edelstahl Dimensional drawing Housing stainless steel Plan cot bo tier acier inox T K 6...

Page 3: ...Kunststoff Werkstoff ABS Farbe Reinwei hnlich RAL 9010 optional aus Edelstahl V2A 1 4301 Abma e Geh use 85 x 85 x 27 mm Baldur 1 75 x 75 x 25 mm Edelstahl elektrischer Anschluss 0 14 1 5 mm ber Schrau...

Page 4: ...al ist mit einem Messger t abzugreifen Hierbei wird die Ausgangsspannung gegen das Nullpotenial O V der Eingangsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Be tri...

Page 5: ...nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Der Betrieb in der N he von Ger ten welche nicht den EMV Richtlinien entsprechen kann zur Beeinflussung der Funk tionswe...

Page 6: ...white similar to RAL 9010 optional stainless steel V2A 1 4301 Dimensions 85 x 85 x 27 mm Baldur 1 75 x 75 x 25 mm stainless steel Electrical connection 0 14 1 5 mm via terminal screws Installation wa...

Page 7: ...a one way rectifier or reverse polarity protection diode is integrated in this device variant This internal one way rectifier also allows operating 0 10 V devices on AC supply voltage The output signa...

Page 8: ...nergy supply company must be observed The buyer has to ensure adherence to the building and safety regulations and has to avoid all dangers of any kind We do not assume any warranty for faults or dama...

Page 9: ...re plastique mat riau ABS couleur blanc pur similaire RAL 9010 option en acier inox V2A 1 4301 Dimensions 85 x 85 x 27 mm Baldur 1 75 x 75 x 25 mm acier inox Raccordement lectrique 0 14 1 5 mm par bo...

Page 10: ...ment s en courant alternatif Le signal de sortie doit tre pr lev avec un appareil de mesure Ce faisant la tension de sortie est mesur e par rapport au potentiel z ro O V de la tension d entr e Si cet...

Page 11: ...doit viter toutes sortes de risques Les d fauts et dommages r sultant d un usage abusif de nos produits ou du non respect des instructions d utilisation ne seront pas couverts par la garantie L insta...

Page 12: ...0 EN 60 529 CE EN 61326 2014 30 EU 36 x 15 x r THERMASGARD RTM Rev 2020 V24 RTM1 xx THERMASGARD RTM 1 WG01 RTM1 U IP30 U RTM1 U Pt1000 0 10 1101 41A1 0000 200 RTM1 U DISPLAY Pt1000 0 10 1101 41A1 2000...

Page 13: ...50 200 10 15 20 25 30 35 36 40 Load resistance diagram Working resistance Ohm Operating voltage V DC Admissible range 30 70 C c 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND...

Page 14: ...r EMV ZBEI VDE VDI DDC PLC 0 5 g 0 10 0 10 4 20 mA 4 20 4 VDE r ZVEI VDE EMV...

Page 15: ...hkeiten bieten jedoch keine Gew hr f r bestimmte Produkteigenschaften Da die Ger te unter verschiedensten Bedingungen und Belastungen eingesetzt werden die sich unserer Kontrolle entziehen muss ihre s...

Page 16: ...C O N OFF OFF 0 C 150 C OFF OFF OFF 12 3 1 2 4 5 3 ON passiver Sensor passiver Sensor UB 24 V AC DC Ausgang 0 10 V in C UB GND interner Sensor passiver Sensor max min 10K Offset DIP 12 3 1 2 4 5 3 ON...

Reviews: