background image

F  

Montage et installation

Sortie de commutation 

KH - 30 

W1

A1 B1

W1

A1 B1

Hysteresis

3% r.H.

Switching output 1

Relative humidity

Gone 

switchpoint

threshold

Preset

switchpoint

threshold

exeeded

Switching back when humidity 

falls below preset limit value

with 3% r.H. hysteresis

Behaviour when preset

limit value is exeeded

below preset

W2

A2 B2

W2

A2 B2

Hysteresis

3% r.H.

Switching output 2

Relative humidity

Gone 

switchpoint

threshold

Preset

switchpoint

threshold

exeeded

Behaviour when preset

limit value is exeeded

Switching back when humidity 

falls below preset limit value

with 3% r.H. hysteresis

below preset

Schéma de raccordement  

KH - 30 

1

2

3

4

5

6

7

8

9

GND

UB 24V AC/DC

Humidifying
Relay 1

Dehumidifying

Humidifying
Relay 2

Dehumidifying

Potential-free

changeover contact 24V

Output humidity 0-10V

Schéma de raccordement  

KH - 30

1

A1 W1 B1 A2 W2 B2

2 3

7 8 9

4 5 6

R1

J1

95%

5%

95%

5%

R2

+ UB

Output

GND

Mode 1 Mode 2

Switching output

Switching

threshold

relative

humidity for

relay 1

Switching

threshold

relative

humidity for

relay 2

Operating

mode

Alimentation

ca

cc

→   1

24 V∼

15 ... 36 V  cc

→   3

0 V

GND

sortie

ca

cc

2

 

→  (r. F.)

0 ... 10 V

0 ... 10 V

4

 

(A1) →

relais 1    contact NF

5

 

(W1) →

relais 1    contact inverseur

6

 

(B1) →

relais 1    contact NO

7

 

(A2) →

relais 2    contact NF

8

 

(W2) →

relais 2    contact inverseur

9

 

(B2) →

relais 2    contact NO

Mode  1  :

  Le potentiomètre (R1 pour relais 1, R2 pour relais 2, voir schéma de raccordement) permet de déterminer pour chacun des deux relais des points 

de commutation indépendants dans une plage allant de 5 % ... 95 % h.r.. Si le point de commutation correspondant est dépassé, le relais correspondant com-
mute (contact inverseur W commute de position A en position B). Si l’humidité relative descend de nouveau de plus de 3 % h.r. (hystérésis) au-dessous du 
point de commutation préréglé, la sortie de commutation correspondante repasse dans sa position d’origine (contact inverseur W commute de position B en 
position A). 

Mode  2  :

  En mode 2, seul le potentiomètre R1 est actif (R2 sans fonction) ! Le point de commutation pour le premier relais est déterminé par le potentio-

mètre R1 (voir schéma de raccordement) dans une plage allant de 5 % ... 95 % h.r.. En mode 2, le point de commutation de la deuxième sortie relais est tou-
jours déterminé comme « point de commutation 1 + 5 % h.r. ». En mode 2 aussi, une hystérésis de 3 % h.r. est prédéfinie pour chaque sortie de commutation. 

10

Summary of Contents for HYGRASREG KH-30

Page 1: ...altenden Ausgang G Operating Instructions Mounting Installation Duct hygrostats and humidity sensors including mounting flange electronic two step with continuous switching outputs F Notice d instruct...

Page 2: ...HYGRASREG KH 30 D G F r Ma zeichnung KH 30 Dimensional drawing Plan cot...

Page 3: ...unststoff Polyamid 30 glaskugelverst rkt mit Schnell verschluss schrauben Schlitz Kreuzschlitz Kombination Farbe reinwei hnlich RAL 9010 Abma e Geh use 108 x 70 x 73 5 mm Thor II Kabelverschraubung M...

Page 4: ...s modus Versorgung AC DC 1 24 V 15 36 V DC 3 0 V GND Ausgang AC DC 2 r F 0 10 V 0 10 V 4 A1 Relais 1 ffnerkontakt 5 W1 Relais 1 Wechselkontakt 6 B1 Relais 1 Schlie erkontakt 7 A2 Relais 2 ffnerkontakt...

Page 5: ...ef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses G...

Page 6: ...rial polyamide 30 glass globe reinforced with quick locking screws slotted Phillips head combination colour pure white similar RAL 9010 Enclosure dimensions 108 x 70 x 73 5 mm Thor II Cable gland M 16...

Page 7: ...dity for relay 2 Operating mode Supply AC DC 1 24 V 15 36 V DC 3 0 V GND Output AC DC 2 r F 0 10 V 0 10 V 4 A1 Relay 1 Breaker contact 5 W1 Relay 1 Changeover contact 6 B1 Relay 1 Normally open contac...

Page 8: ...on are not explicitly mentioned and are possible in terms of technical progress and continuous improve ment of our products In case of any modifications made by the user all warranty claims are forfei...

Page 9: ...pla able Temp rature du bo tier 10 C 65 C Bo tier mati re plastique polyamide renforc 30 de billes de verre avec vis de fermeture rapide association fente fente en croix couleur blanc pur similaire RA...

Page 10: ...on ca cc 1 24 V 15 36 V cc 3 0 V GND sortie ca cc 2 r F 0 10 V 0 10 V 4 A1 relais 1 contact NF 5 W1 relais 1 contact inverseur 6 B1 relais 1 contact NO 7 A2 relais 2 contact NF 8 W2 relais 2 contact i...

Page 11: ...ces par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications...

Page 12: ...65 C 30 RAL 9010 108 x 70 x 73 5 Thor II M 16 x 1 5 8 c 20 NL 190 III EN 60 730 IP 65 EN 60 529 0 14 2 5 2 CE 2004 108 EC 36 x15 x 1 4 5 3 S1 4 5 2 7 8 3 S2 7 8 2 0 10 0 100 1 5 6 S1 5 6 2 8 9 S2 8 9...

Page 13: ...reset limit value is exeeded Switching back when humidity falls below preset limit value with 3 r H hysteresis below preset KH 30 1 2 3 4 5 6 7 8 9 GND UB 24V AC DC Humidifying Relay 1 Dehumidifying H...

Page 14: ...r ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Page 15: ...Mounting diagram Sch ma de montage Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitte...

Page 16: ...D G F r MF 20 K Ma zeichnung MF 20 K Dimensional drawing Plan cot Zubeh r Accessories Accessoires...