S+S Regeltechnik HYGRASGARD ESFF-I Operating Instructions, Mounting & Installation Download Page 8

G  

General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor  element. 
–  On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure.  

In case of pollution  ⁄  contamination, this filter should be cleaned on a regular basis.

– Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 
–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.
– In case of pollution, we recommend cleaning and recalibration in the factory.
– In any case, the sensor must not get in contact with chemicals or other cleaning agents.
– The relative humidity of 0 ...100 % is indicated by an output signal of 0 -10 V or 4 ... 20 mA. 

The device operating range covers 10.0 ... 99.9 % r. H. Outside of that range, mismeasurements or increased deviations may occur.

– When several sensors (0  -10 V) are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating 

 voltage source may be short-circuited. 

– The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.
– If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
 Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In additionIn addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV 

and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils 
of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed by authorised specialists only.
– The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

 Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve- 
ment of our products.

– In case of any modifications made by the user, all warranty claims are forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation by 

similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, or as an 

EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

,  the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Summary of Contents for HYGRASGARD ESFF-I

Page 1: ...rierfähig mit aktivem Ausgang G Operating Instructions Mounting Installation Screw in humidity and temperature sensors for pressure systems calibrateable with active output F Notice d instruction Sonde d humidité et de température à visser pour systèmes de pression étalonnable avec sortie active r Руководство по монтажу и обслуживанию Датчик влажности и температуры ввинчиваемый для систем повышенн...

Page 2: ...HYGRASGARD ESFF HYGRASGARD ESFTF D G F r Maßzeichnung ESFF Dimensional drawing ESFTF Plan coté Габаритный чертеж 64 72 107 14 8 37 8 M16x1 5 156 118 ø10 ø20 ...

Page 3: ...ussbild 0 14 1 5 mm über Schraubklemmen auf Platine Gehäuse Kunststoff Polyamid 30 glaskugelverstärkt mit Schnellverschlussschrauben Schlitz Kreuzschlitz Kombination Farbe reinweiß ähnlich RAL 9010 Abmaße Gehäuse 72 x 64 x 37 8 mm Thor III Kabelverschraubung M 16 x 1 5 mit Zugentlastung auswechselbar max Innendurchmesser 10 4 mm Schutzrohr aus Metall Messing vernickelt Ø 20 mm Prozessanschluss G N...

Page 4: ... Offset Feuchte 5 r H Offset r H Versorgungsspannung 15 36V DC 4 20mA für 0 100 r H R L 500 Ohm 1 2 4 6 Offset Temperatur 3 K Offset Feuchte 5 r H Offset C r H UB GND UB 24V AC DC Ausgang Feuchte 0 10V in r H Ausgang Temperatur 0 10V in C 1 2 3 Offset Temperatur 3 K Offset Feuchte 5 r H Offset C r H Versorgungsspannung 15 36V DC 4 20mA für 0 100 r H R L 500 Ohm 4 20mA für 0 50C R L 500 Ohm ...

Page 5: ... von der Gewährleistung und Haftung ausgeschlossen Die Installation der Geräte darf nur durch Fachpersonal erfolgen Es gelten ausschließlich die technischen Daten und Anschlussbedingungen der zum Gerät gelieferten Montage und Bedienungs anleitung Abweichungen zur Katalogdarstellung sind nicht zusätzlich aufgeführt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Prod...

Page 6: ...onnection see connecting diagram 0 14 1 5 mm via terminal screws on circuit board Enclosure plastic material polyamide 30 glass globe reinforced with quick locking screws slotted Phillips head combination colour pure white similar RAL 9010 Enclosure dimensions 72 x 64 x 37 8 mm Thor III Cable gland M16 x 1 5 including strain relief exchangeable max inner diameter 10 4 mm Protective tube metal bras...

Page 7: ...0 10 V in r H 1 2 Offset humidity 5 r H Offset r H Supply voltage 15 36V DC 4 20mA for 0 100 r H R L 500 Ohm 1 2 4 6 Offset temperature 3 K Offset humidity 5 r H Offset C r H UB GND UB 24V AC DC Output humidity 0 10 V in r H Output temperature 0 10 V in C 1 2 3 Offset temperature 3 K Offset humidity 5 r H Offset C r H Supply voltage 15 36V DC 4 20mA for 0 100 r H R L 500 Ohm 4 20mA for 0 50C R L 5...

Page 8: ...om warranty or liability These devices must be installed by authorised specialists only The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve ment of our products I...

Page 9: ...5 55 C Raccordement électrique 2 ou 3 fils voir schéma de raccordement 0 14 1 5 mm par bornes à vis sur carte Boîtier matière plastique polyamide renforcé à 30 de billes de verre avec vis de fermeture rapide association fente fente en croix couleur blanc pur similaire à RAL 9010 Dimensions du boîtier 72 x 64 x 37 8 mm Thor III Presse étoupe M 16 x 1 5 avec décharge de traction remplaçable diamètre...

Page 10: ...humidity 0 10 V in r H 1 2 Offset humidity 5 r H Offset r H Supply voltage 15 36V DC 4 20mA for 0 100 r H R L 500 Ohm 1 2 4 6 Offset temperature 3 K Offset humidity 5 r H Offset C r H UB GND UB 24V AC DC Output humidity 0 10 V in r H Output temperature 0 10 V in C 1 2 3 Offset temperature 3 K Offset humidity 5 r H Offset C r H Supply voltage 15 36V DC 4 20mA for 0 100 r H R L 500 Ohm 4 20mA for 0 ...

Page 11: ...linons toute responsabilité ou garantie au titre de tout dommage consécutif provoqué par des erreurs commises sur cet appareil L installation des appareils doit être effectuée uniquement par un spécialiste qualifié Seules les données techniques et les conditions de raccordement indiquées sur la notice d instruction accompagnant l appareil sont applicables des différences par rapport à la présentat...

Page 12: ... окружающей среды при хранении 25 60 C при эксплуатации 5 55 C Эл подключение двух или трехпроводное см схему соединения 0 14 1 5 мм по винтовым зажимам на плате Корпус пластик полиамид 30 усиление стеклянными шариками с быстрозаворачиваемыми винтами комбинация шлиц крестовой шлиц цвет чистый белый аналогичен RAL 9010 Размеры корпуса 72 x 64 x 37 8 мм Thor III Присоединение кабеля M 16 x 1 5 с раз...

Page 13: ...10 V in r H 1 2 Offset humidity 5 r H Offset r H Supply voltage 15 36V DC 4 20mA for 0 100 r H R L 500 Ohm 1 2 4 6 Offset temperature 3 K Offset humidity 5 r H Offset C r H UB GND UB 24V AC DC Output humidity 0 10 V in r H Output temperature 0 10 V in C 1 2 3 Offset temperature 3 K Offset humidity 5 r H Offset C r H Supply voltage 15 36V DC 4 20mA for 0 100 r H R L 500 Ohm 4 20mA for 0 50C R L 500...

Page 14: ...жит устранению по гарантии Установка приборов должна осуществляться только квалифицированным персоналом Действительны исключительно технические данные и условия подключения приведенные в поставляемых с приборами руководствах по монтажу и эксплуатации Отклонения от представленных в каталоге характеристик дополнительно не указываются несмотря на их возможность в силу технического прогресса и постоян...

Page 15: ...я Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S Regeltechnik GmbH La reproduction des textes même partielle est uniquement autorisée après accord de la société S S Regeltechnik GmbH Перепечатка в том числе в сокращенном виде разрешается лишь с согласия S...

Page 16: ...HYGRASGARD ESFF HYGRASGARD ESFTF D G F r ...

Reviews: