![S+S Regeltechnik AERASGARD RFTM-LQ-CO2-Modbus Operating Instructions, Mounting & Installation Download Page 20](http://html1.mh-extra.com/html/s-s-regeltechnik/aerasgard-rftm-lq-co2-modbus/aerasgard-rftm-lq-co2-modbus_operating-instructions-mounting-and-installation_3228865020.webp)
20
G
AERASGARD
®
RFTM - LQ - CO
2
- Modbus
|
Telegrams
TELEGRAMS
Function 04 Read Input Register
Register
Parameter
Data Type
Value
Range
3x0001
CO2
Sampling 4 s
Signed 16 bit
350...5000
350...5000 ppm
3x0002
CO2
Filtering 32 s
Signed 16 bit
350...5000
350...5000 ppm
3x0003
VOC
Sampling 4 s
Signed 16 bit
0...1000
0.0...100.0 % VOC
3x0004
VOC
Filtering 32 s
Signed 16 bit
0...1000
0.0...100.0 % VOC
3x0005
Temperature
Sampling 4 s
Signed 16 bit
0…500
0.0...+50.0 °C
3x0006
Temperature
Filtering 32 s
Signed 16 bit
0…500
0.0...+50.0 °C
3x0007
Relative humidity
Sampling 4 s
Signed 16 bit
0...1000
0.0...100.0 % r.H.
3x0008
Relative humidity
Filtering 32 s
Signed 16 bit
0...1000
0.0...100.0 % r.H.
3x0009
*
not assigned
–
–
–
–
3x0010
*
not assigned
–
–
–
–
3x0011
*
Potentiometer position
no filtering
Signed 16 Bit
0...1000
0.0...100.0 % r.H.
*
only for device version with setpoint potentiometer
Function 06 Write Single Register & Function 16 Write Multiple Register
Register
Parameter (display)
Data Type
Value
Range
4x0001
Physical parameter displayed
Index on display
Unsigned 8 bit
0…10
0…10
Standard display (cyclic):
VOC in %,
CO2 in ppm,
temperature in °C,
relative humidity in % r.H.
–
0
Default
setting
alternative display (static):
CO2 in ppm
1
1
VOC in %
2
2
Temperature in °C
3
3
Relative humidity in % r.H.
4
4
Freely configurable display
–
10
4x0002
7-Segment Value
Signed 16 Bit
-999…9999
-999…9999
4x0003
14-Segment Pattern 1
See Graphic
Unsigned 16 Bit
See Binary Pattern
4x0004
14-Segment Pattern 2
See Graphic
Unsigned 16 Bit
See Binary Pattern
4x0005
Segment Pattern
Unsigned 16 Bit
See Binary Pattern
4x0006
Dot Matrix Character A
Unsigned 8 Bit
0…255
ASCII character
4x0007
Dot Matrix Character B
Unsigned 8 Bit
0…255
ASCII character
4x0008
Dot Matrix Character C
Unsigned 8 Bit
0…255
ASCII character
4x0009
Dot Matrix Character D
Unsigned 8 Bit
0…255
ASCII character
4x0010
Dot Matrix Character E
Unsigned 8 Bit
0…255
ASCII character
4x0011
Dot Matrix Character F
Unsigned 8 Bit
0…255
ASCII character
4x0012
Dot Matrix Character G
Unsigned 8 Bit
0…255
ASCII character
4x0020
Brightness LCD-backlighting
Unsigned 8 Bit 0...63
0...100%
4x0021
*
Offset CO2
Signed 16 Bit
–512...511
Offset
4x0022
*
not assigned
Signed 16 Bit
–512...511
Offset
4x0023
*
Offset temperature
Signed 16 Bit
–512...511
Offset
4x0024
*
Offset relative humidity
Signed 16 Bit
–512...511
Offset
*
only for device version with setpoint potentiometer