Quality product for HVAC sector, accuracy  ± 1.5 % or ± 3 %

The calibrateable PREMASGARD

®

 1210 series compact pressure sensors with Modbus connection are optionally equipped with display and are used for 

measuring above-atmospheric, below-atmospheric, or differential pressures of air. The piezo-resistive measuring element is temperature-compensated 
and guarantees high reliability and accuracy. The pressure transmitters are provided with a pushbutton for manual zero point calibration and an adjust-
able offset. Applications of these pressure sensors are in cleanroom, medical and filter technology, at ventilation and air conditioning ducts, at spray 
booths, in large-scale catering facilities, for filter monitoring and level measurement, or for triggering frequency converters. Media measured with 
these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media. These differential pressure sensors 
are supplied including connection set 

ASD -06

 (2 m connection hose, two pressure connection nipples, screws).

TECHNICAL DATA:

Power supply: .......................... 24 V  AC  (± 20 %)  and  15 … 36 V  DC  (± 10 %) 
Power consumption:  ................. < 1 VA ⁄ 24 V DC,  < 2,2 VA ⁄ 24 V AC
Measuring ranges:  ...................

– 1000...+ 1000  Pa, 

or

 

– 5000...+ 5000  Pa,

 

depending on the type of device, see table

Bus interface:  ......................... RS 485, 

galvanically isolated,

 

Bus termination activatable via DIP switches.
Up to 32 devices possible in one segment.  
In case of a greater number of devices, RS485 transceivers must be used.

Bus protocol: ......................... Modbus  (RTU mode)  

address range 0...

247

 selectable

Baud rate:  .............................. 9600, 19200, 38400 Baud
Status indicator:  ..................... LED green = Telegram valid 

LED red = Telegram error 

Media temperature:  ................. 0 ... + 50 °C
Pressure connection:  ............... 4 ⁄ 6 x 11 mm  (hoses Ø = 4 ⁄ 6  mm), 

metal pressure connection nozzles

Type of pressure: ...................... differential pressure
Medium:  ................................. clean air and other non-aggressive, non-combustible gases
Accuracy:  ...............................

± 1.5 % 

or 

± 3 % EW

  (at 20°C) 

depending on the type of device

Zero point offset:  .................... ± 10  % of pressure range end value
Above- ⁄ below-
atmospheric pressure: ............. max. 5 x pressure range end value
Long-term stability:................. ± 1 %  per  year
Hysteresis: ............................ 0.3 %    of  final  value
Media contacting parts: ........... brass, Ni, Nylon, PU, Si
Temperature drift values: ......... ± 0.1 % of final value ⁄ °C
Current consumption: .............. <  20  mA
Linearity: .............................. < ± 1 %  of final value
Enclosure: ............................. plastic, material polyamide, 30 % glass-globe-reinforced,  

with quick-locking screws (slotted ⁄ Phillips head combination),  
colour pure white  (similar RAL 9010), enclosure cover for display is transparent!

Enclosure dimensions: ............. 72  x  64  x  37.8 mm    (Thor  III  without  display) 

72  x  64  x  43.3 mm    (Thor  III  with  display)

Cable gland: ........................... M 16 x 1.5 ,  including  strain  relief,  exchangeable,   

max. inner diameter 10.4 mm

Electrical connection: .............. 0.14 - 1.5 mm², via terminal screws
Humidity: .............................. < 95 %  r. H., non-precipitating air
Protection class: .................... III  (according to EN 60 730)
Protection type: ..................... IP 65  (according to EN 60 529)
Standards: ............................ CE conformity, electromagnetic compatibility according to  

EN 61 326 + A1 + A2, EMC directive 2004 ⁄ 108 ⁄ EC

Features: ..............................

illuminated single line display,

  cutout  ca. 36 x15 mm  (W x H), 

to display ACTUAL pressure 

ACCESSORIES: ....................... including connection set 

ASD-06

 (nipple straight)  

(included in the scope of delivery)
connection nipple 

ASD-07

 (at 90 degree angle) 

pressure outlet 

DAL-1

 for ceiling or in-wall installation (e.g. in clean rooms) 

Summary of Contents for 1301-1214-0010-200

Page 1: ...g Instructions Mounting Installation Pressure and differential pressure measuring transducers 1 5 3 incl connection set compact form with Modbus connection F Notice d instruction Convertisseur de pres...

Page 2: ...Plan cot Ma zeichnung Dimensional drawing Plan cot PREMASGARD 1210 PREMASGARD 1210 mit Display with display avec cran 107 72 15 64 18 20 6 4 14 8 43 3 M16x1 5 110 Pa 107 72 15 64 18 20 6 4 110 Pa 107...

Page 3: ...ngesetzt werden Busprotokoll Modbus RTU Mode Adressbereich 0 247 einstellbar Baudrate 9600 19200 38400 Baud Statusanzeige LED gr n Telegramm g ltig LED rot Telegrammfehler Medientemperatur 0 50 C Druc...

Page 4: ...BS 7100 0060 7000 000 BERWACHUNGSARTEN A Unterdruck P1 wird nicht angeschlossen ist luftseitig offen gegen Atmosph re P2 Anschluss im Kanal B Filter P1 Anschluss vor dem Filter P2 Anschluss nach dem F...

Page 5: ...wird mithilfe eines Werkzeuges Schraubendreher 2 5 Klingenbreite durchgef hrt Automatisches Einstellen des Offsets 1 Zum Setzen des Nullpunktes muss das Ger t mindestens 60 Minuten in Betrieb sein 2 D...

Page 6: ...einstellbar DIP 6 EVEN gerade O N aktiv 1 Stoppbit O N aktiv O N ODD ungerade OFF inaktiv 2 Stoppbits OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B...

Page 7: ...ktivierung Listen Only Mode Keine Antwort 10 L sche Z hler Echo Telegramm 11 Z hler Bustelegramme Unsigned 16 Bit alle g ltigen Bustelegramme 12 Z hler Kommunikationsfehler Parity CRC Framefehler etc...

Page 8: ...egmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabschirmgeflecht verwende...

Page 9: ...ihrer berwachungsorgane des T V und der rtlichen EVU zu beachten Der K ufer hat die Einhaltung der Bau und Sicherungsbestimmung zu gew hrleisten und Gef hrdungen aller Art zu vermeiden F r M ngel und...

Page 10: ...7 selectable Baud rate 9600 19200 38400 Baud Status indicator LED green Telegram valid LED red Telegram error Media temperature 0 50 C Pressure connection 4 6 x 11 mm hoses 4 6 mm metal pressure conne...

Page 11: ...kPa 0 101971 mH2O 1 bar 1 bar 1000 mbar 100000 Pa 100 kPa 10 1971 mH2O 1 mbar 0 001 bar 1 mbar 100 Pa 0 1 kPa 0 0101971 mH2O 1 mH2O 0 0980665 bar 98 0665 mbar 9806 65 Pa 9 80665 kPa 1 mH2O G PREMASGAR...

Page 12: ...e made before must be done in this configuration Offset adjustment is carried out using a tool called screwdriver 2 5 blade with in mm Automatic offset setting 1 Before setting the zero point the devi...

Page 13: ...r without selectable DIP 4 Bus termination with or without selectable DIP 6 EVEN numbered O N Active 1 stop bit O N Active O N ODD numbered OFF Inactive 2 stop bit OFF Inactive OFF The baud rate speed...

Page 14: ...isten only mode Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 Bit All valid bus telegrams 12 Counter communication errors...

Page 15: ...greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply line and c...

Page 16: ...ns issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The purchaser has to adhere to the building and safety regulations and has to pre...

Page 17: ...a utiliser un transceiver RS 485 Protocole de bus Modbus mode RTU Plage d adresses r glable 0 247 Taux de transfert 9600 19200 38400 Baud Affichage de l tat DEL verte t l gramme valide DEL rouge erreu...

Page 18: ...1 kPa 0 101971 mWs 1 bar 1 bar 1000 mbar 100000 Pa 100 kPa 10 1971 mWs 1 mbar 0 001 bar 1 mbar 100 Pa 0 1 kPa 0 0101971 mWs 1 mWs 0 0980665 bar 98 0665 mbar 9806 65 Pa 9 80665 kPa 1 mWs F PREMASGARD 1...

Page 19: ...demment doivent tre r alis s dans cette configuration On r alise le r glage du point z ro l aide d un outil tournevis 2 5 largeur de lame R glage automatique du point z ro 1 Pour ajuster le point z ro...

Page 20: ...EVEN pair O N aktiv 1 bit stop O N actif O N ODD impair OFF inaktiv 2 bit stop OFF inactif OFF Le taux de Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler...

Page 21: ...d cho 04 Activation Listen Only Mode mode coute seule Pas de r ponse 10 Efface compteur T l gramme d cho 11 Compteur T l grammes de Bus Unsigned 16 bits Tous les t l grammes de Bus valides 12 Compteu...

Page 22: ...parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn es alimentation ten...

Page 23: ...organes de surveillance du T V et des entreprises d approvisionnement en nergie locales L acheteur doit respecter les dispositions relatives la construction et la s curit et doit viter toutes sortes d...

Page 24: ...RS 485 DIP 32 RS485 Modbus RTU 0 247 9600 19200 38400 0 50 C 4 6 x 11 4 6 1 5 3 20 C 10 5 x 1 0 3 MS Ni Nylon PU Si 0 1 C 20 1 30 RAL 9010 72 x 64 x 37 8 Thor III 72 x 64 x 43 3 Thor III M 16 x 1 5 1...

Page 25: ...001 1 100 0 1 0 0101971 1 0 0980665 98 0665 9806 65 9 80665 1 r PREMASGARD 1210 1 1000 1000 1000 1000 PREMASGARD 1210 Modbus 1301 1214 0010 200 1000 1000 PREMASGARD 1210 Modbus 1301 1214 2010 200 5000...

Page 26: ...5678 ON DIPA 123456 ON DIPB Plug for display offset auto zero min max UB GND Shielding RS485 Modbus A RS485 Modbus B UB 24V AC DC mode Plug for display contact is on the right side Offset correction p...

Page 27: ...P 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON Modbus 128 64 1 193 DIP 1 DIP 2 PREMASGARD 1210 DIP B DIP 5 1 2 3...

Page 28: ...00 5000 5000 1000 1000 5000 5000 05 Write Single Coil 0x0001 0 0 1 ON OFF 08 Diagnostic 00 Loopback 01 Modbus Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16 13 16 14 16 15 16 0 17 Repor...

Page 29: ...29 DIP 6 Modbus Modbus 32 1 247 100 Profibus r Modbus Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D 5 B GND B D0 D MODBUS RTU Master Slave 1 Slave 2...

Page 30: ...30 P P 10 90 ZVEI VDE r...

Page 31: ...g Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccordement DAL 1 Druckauslass Pressure outlet Sortie pression Ma zeichnung ASD 07 Dimensional drawing Plan cot Copyright by S S Regelte...

Page 32: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...