44
CompTrol Interface V4.0.x | Issue 21-05-2021 | 1000932
Program 3 – temperature setpoint definition for equipment rooms with temperature limit alarm
9.2.2 Setting program 3 via DIP switch S1
S1-1 S1-2 S1-3 S1-4
Designation
ON
ON
OFF OFF
Program 3: Temperature setpoint definition for equipment rooms with
temperature limit alarm
Table 23: DIP switch setting for program 3
9.2.3 Setting functions for program 3 via DIP switch S2
The following table lists the functions for program 3 in brief. See
Interface expansion module” on page 23
for a detailed description of the functions.
DIP switch
Status
Function
S2-1
ON
OFF
CompTrol Interface is configured as master in the X/Y remote control bus
CompTrol Interface is configured as slave in the X/Y remote control bus
S2-2
ON
OFF
X4b-II
, operating signal;
X4c-III
, temperature limit alarm
X4b-II,
compressor signal;
X4c-III
, temperature limit alarm
S2-3
ON
OFF
For setting the temperature limit value (see
limit value via DIP switch S2” on page
S2-4
ON
OFF
For setting the temperature limit value (see
limit value via DIP switch S2” on page
S2-5
ON
OFF
Forced mode
Inoperative
S2-6
ON
OFF
All digital outputs are closed without a signal (NC)
All digital outputs are open without a signal (NO)
S2-7
ON
OFF
Setting determines the value shown on the 7-segment display (see
7-segment display” on page 21).
S2-8
ON
OFF
Setting determines the value shown on the 7-segment display (see
7-segment display” on page 21).
Table 24: Functions in program 3
9.2.4 Setting the analog signal type on S4 and S7
The position of the jumpers on pin headers
S4
and
S7
determines the current analog signal type
(see “4.4.1 Analog input X3” on page 19).
9.3 Analog input
Note
●
If a signal exceeds or falls below a boundary value at analog input
X3-S
, the temperature set-
point 23 °C is transferred. (see “5.3.4 Signal boundary value monitoring” on page 27)
●
Analog input
X3-S
is only evaluated if a signal is applied to digital input
X2b-D4
(see