background image

8

AUTO CLOSE DELAY TIMER

This timer delays the closing of the door when it is
opened by an Auto input activator (terminal 14) or
floor loop (terminal 30).

After the connection is removed and the door has
reached the open limit switch, the timer will time out
and close the door. For no closing delay, set the timer
to 0. Setting and messages for this timer will be
displayed as "dEL =" plus time.

SETTING THE TIMERS

The timers are set using the UP and DOWN arrow
buttons as described in PUSHBUTTONS on page 3
and the individual buttons for each timer. The Digital
Gateway should be in a normal state (display showing
the cycle count and no activators activated) before
setting the timers. The timers will count in one-second
intervals.

To set the timers:

1.

Push the button for the timer you want to set. The
display will show the present setting of that timer.

2.

Use the UP and/or DOWN arrow keys to raise or
lower the setting. Releasing the arrow key will
enter the new setting in the memory. The display
will show that setting for four seconds, or until
another button is pushed. Figure 7 shows the
setting of the Close Delay backup timer.

CL = 3

Push to
Set the
Timer

Push to Choose the
CLOSE Backup Timer

A0500027

Figure 7

START-UP PROCEDURES

1.

Install the door following the procedures outlined
in the door installation manual.

2.

Make all necessary electrical connections. Follow
the electrical schematic shipped in the door
control box. The schematics shown in this manual
are for informational purposes only. (See INPUTS
TO THE DIGITAL GATEWAY on page 4 for a
description of the various inputs to the Digital
Gateway.)

3.

Turn on the power. If any of the N.C. connections
are missing, the COnnECt message will be
displayed and the missing input LED will blink.
Once the connection is made, the LEDs will go off
and the system will be ready for operation. (See
ALARM CONDITIONS—COnnECt, MISSING
CONNECTIONS on page 9 for more information
on missing connections.)

4.

Set the timers as required. The backup timers
should be set for 1–2 seconds longer than it will
take the door to open or close. The A/A Close
Delay timer and Auto Close Delay timer should be
set as required for proper closing of the door.
(See SETTING THE TIMERS.)

NOTE: Use the OPEN and/or CLOSE jog buttons

to check door operation. If a problem is
noticed, the buttons can be released to
stop the door.

5.

Run the door. Check the door for proper opera-
tion. Check the motor rotation, limit switch opera-
tion, reversing edge, breakaway kill switch, timer
settings, etc. Check all activators for proper
activation.

START-UP PROCEDURES

Summary of Contents for DG1200

Page 1: ...Revision April 15 1998 0 215 006 Rytec Corporation Digital Gateway Installation Owners Manual Model DG1200...

Page 2: ......

Page 3: ...NPUTS TOTHE DIGITAL GATEWAY AC INPUTS 4 Limit Switches Terminals 8 and 9 4 OPEN LSO 4 CLOSE LSC 4 PB1 Pushbutton Terminal 11 4 Alternate Action Inputs A A Momentary Contact Activators Terminal 12 4 Au...

Page 4: ...UP PROCEDURES 8 ALARM CONDITIONS COnnECt MISSING CONNECTIONS 9 OP 0 OPEN TIME EXCEEDED 9 CL 0 CLOSE TIME EXCEEDED 10 AJAr BREAKAWAY KILL SWITCH 10 OLr OVERLOAD RELAY 10 EdGE REVERSING EDGE 10 NON ALA...

Page 5: ...assage Limit Switch LSP 14 PROGRAM 4 PROGRAMMABLE OPTIONS 15 Close Jog 15 Open Jog 15 Reverse Delay 15 Loop Call Delay 15 PROGRAM 5 REVERSE INPUT LOGIC 15 PROGRAM 6 15 SETTING THE PROGRAM OPTIONS 15 D...

Page 6: ...This page intentionally left blank...

Page 7: ...oten tial for personal injury if the procedure is not performed as described CAUTION is used to indicate the potential for damage to the product or property dam age if the procedure is not followed as...

Page 8: ...r an overview of the Digital Gateway controls A0500028 DOWN Arrow Auto Close Delay Timer A A Close Delay Timer UP Arrow Display Message Explanation CLOSE Backup Timer OPEN Backup Timer Digital Display...

Page 9: ...button will operate while the Digital Gateway is in the AJAr or EdGE alarm condition See Figure 1 CLOSE JOG This pushbutton jogs the door closed It is not operational when the door is being controlled...

Page 10: ...rnate Action Inputs A A Momentary Contact Activators Terminal 12 N O Contact A momentary connection while the door is closed closing or stopped between limits will open the door A momentary connection...

Page 11: ...Conditions It will reset the system the same as the Open Jog Reset button Program 2 Terminal 24 N O Contact This input has various functions that are explained in the Programming section of this manu...

Page 12: ...closed closing or stopped between limits The door will remain open as long as the connection is present When the connection is removed the Auto Close delay timer will count down and close the door Th...

Page 13: ...be displayed as OP plus time CLOSE BACKUPTIMER This is the backup timer for the closing of the door It functions the same as the open backup timer When the time has been exceeded the CL 0 message will...

Page 14: ...kup Timer A0500027 Figure 7 START UP PROCEDURES 1 Install the door following the procedures outlined in the door installation manual 2 Make all necessary electrical connections Follow the electrical s...

Page 15: ...s must be present If neither of the limit connections are present both the LSO and LSC LEDs will blink If the limits are wired correctly and the Digital Gateway still shows a missing limit connection...

Page 16: ...box has tripped The display message OLr will blink and the OLR LED will be on Find and correct the problem that caused the overload relay to trip reset the overload relay and reset the Digital Gatewa...

Page 17: ...ateway is reset with the Open Jog Reset button or Stop input See Figure 14 HELLO A0500027 Figure 14 EdGE REVERSING EDGETRIPPED The message EdGE will be displayed if the door comes down on something ac...

Page 18: ...puts of the Digital Gateway share a common power source which is terminal 4 Terminal 4 is internally connected to the 24 vac power source Terminal 5 is the open output supplying power to the open cont...

Page 19: ...ilable program follows See SETTING THE PROGRAM OPTIONS on page 15 for programming instructions PROGRAM 1 OUTPUT 7 This output can tell you if the door is not closed fully open or about to close When o...

Page 20: ...r is fully closed the door will open and the Passage timer PEt will begin counting down When the Passage timer reaches zero the door will stop Activating this input again will close the door If the A...

Page 21: ...on the loop long enough to open the door but traffic approaching the door will activate the door When the Loop input is activated while the door is fully closed the Loop timer will count down and then...

Page 22: ...e digits of the security code then press the Set button to enter the Program Mode 3 Once you have entered the program mode the display will show the various program menus See Figure 21 Press the Selec...

Page 23: ...with a normally open N O or a normally closed N C contact connected to them See PROGRAM 5 REVERSE INPUT LOGIC on page 15 The various models of Rytec doors require slightly different combinations of N...

Page 24: ...93 A1D1 193 A1D1 193 A1C1 MOTOR DATA 230 208 VOLTAGE 460 575 2 9 FLA 1 8 0 97 0 7 150 ma MAX 20 21 23 26 4 28 29 27 30 5 OPEN CLOSE 4 M1C M1O OLR X2 2 3 1 4 CONNECTED INTERNALLY DIGITAL GATEWAY LSO 5...

Page 25: ...al infor mation only Due to varying require ments for individual customers a schematic is prepared for each door installation This schematic is shipped inside of the control box and must be used for t...

Page 26: ...8 CONNECTED INTERNALLY 1 4 5 5 2 3 X2 BY OTHERS SEE MOTOR TABLE FOR FUSE SIZE 1 FUSED DISCONNECT L2 L3 L1 BY RYTEC 5 18 CLOSE 4 19 M1O M1C OLRL M1C M1O OLRH OPEN MOTOR LO MOTOR HI BRAKE MOTOR X2 4 5...

Reviews: