3
Closet 300 PS Unit
Installation, Usage and Maintenance Instructions
The Closet 300 PS is supplied with a 3 core mains cable with a length of 2 metres. A 220/240V 50Hz single phase supply
with neutral and earth is required. All wiring must comply with l.E.E. and all local, national and EU requirements. THIS
APPLIANCE MUST BE EARTHED.
Pump Model
Motor Power
Rated Current
Minimum Fuse Size
Diver 6-700 M-A
0.65kW
3.8A
6A
The method of connection to the electricity supply must facilitate complete isolation and should preferably be made via
a fused isolator having a contact separation of at least 3mm in all poles and supplying the pump circuit only. The fused
isolator should also protect the cable supplying the unit.
A fuse/MCB suitable for the protection of motor loads should
protect the circuit to which the pump is connected. The instal-
lation of a ground fault interrupter / RCCD-protector is strongly
recommended.
Cable extensions should only be made with a safe and water-
proof system. The system should be interconnected as shown
in the diagram (L: Brown N: Blue E: Green/Yellow ) using suitable
cable with a cross section of at least 1.5mm2.
Note - the pump connection (indicated in shaded area) comes
pre-connected on Closet 300 PS.
03. INSTALLATION AND CONDITIONS OF USE
This product must be installed subject to the following limitations:
▪
Temperature of pumped liquid between 0ºC and +35ºC
▪
Voltage variation a/-5%
▪
Maximum number of starts per hour : 40
▪
Maximum water column between controller and highest water outlet: 6m
▪
Minimum positive head level: 100mm
▪
The pump is not suitable for pumping inflammable liquids or for use in locations where
there is a danger of explosion
▪
The pump is not suitable for use in swimming pools or garden ponds
▪
Do not cover or place anything on top of the controller
Install the Closet 300 PS unit in a dry location, indoors. Vibration isolating material
should be installed underneath the unit. The unit must be installed in a vertical
orientation, otherwise the pump will not operate correctly or leaks may occur.
Make sure that the water is free from sand, grit and other dirt. Do not run the
pump without water. The controller will stop pump operation when there is no
water and will need to be reset when this occurs.
The installer must pressure test the water system fully to ensure there are no leaks before connecting and starting the
pump for the first time. The maximum pump pressure is 3.5 bar. The pressure test should be carried out at a pressure of
at least 5 bar. Failure to ensure the integrity of all pipework, joints and fittings may result in flooding and property damage.
RVR Energy Technology accepts no liability for damage due to leaks either inside or outside the product.
We recommend the installation of a small (5 litre) expansion vessel on the cold water outlet, which will result in reduced
pump operating cycles and also eliminate frequent starting due to drips and leaks. This will prevent premature failure due
to frequent cycling. If an expansion vessel is installed, the expansion vessel charge pressure should be set to 1.5 bar with
no water pressure in the system. The system will operate satisfactorily without an expansion vessel provided the number
of start/stop cycles does not exceed 40 per hour.
We recommend the installation of an isolation valve on the pressurised outlet. A suitable flexible hose or connector should
be used to connect the Closet 300 PS to the pipework.
COLD WATER
INLET
OVERFLOW
PRESSURISED
OUTLET
04. ELECTRICAL INSTALLATION