PRINTED CIRCUIT BOARD COMPRESSOR SECTION

COMPRESSOR #1 COOLING OPERATION

1.

Begins with a call from the thermostat, 12 volt positive (+) to terminal #5 (Y1) in the 9-pin connector.  (Yellow wire at the

thermostat).  This call is subject to thermostat time delays.  The Ground (12 VDC-) is Blue in terminal #4.

2.

12 VDC passes through the circuit board to terminals T3B and T2, Comp 1 Coil.  (Subject to 115 VAC power through the

Circuit 1 Exclusion Relay and the Freeze Switch).

3.

12 VDC exits terminals T3B and T2, Comp 1 Coil and goes to the Compressor #1 relay coil.

4.

The Compressor Relay #1 closes.

5.

Compressor #1 starts and runs until the compressor signal is satisfied at the thermostat.  (What else might shut the compressor

off?)

COMPRESSOR #2 COOLING OPERATION

1.

Begins with a call from the thermostat, 12 volt positive (+) to terminal #6 (Y2) in the 9-pin connector.  (Orange wire at the

Thermostat).  Subject to a 2-degree temperature differential and a thermostat time delay.  The Ground (12 VDC-) is Blue in

terminal #4.

2.

12 VDC passes through the circuit board to terminals T3A and T10, Comp 2 Coil.

3.

12 VDC exits terminals T3A (12 VDC-) and T10,  (12 VDC+) Comp 2 Coil.

4.

The compressor relay #2 closes.  (Subject to available 115 VAC power).

5.

Compressor #2 starts and runs until the compressor #2 signal is satisfied at the thermostat.

Summary of Contents for 6535*335 Series

Page 1: ...1 series heat pumps if the 6535 3209 Replacement P C Board Kit has been installed in the unit RV Products A Division of Airxcel Inc P O Box 4020 Wichita KS 67204 1 877 430 8084 Service Center Locator...

Page 2: ...8 Printed Circuit Board 9 Pin Thermostat Plug Connector 9 Printed Circuit Board Indoor Blower Section 10 Printed Circuit Board Compressor Section 11 Printed Circuit Board Freeze Sensor Section 12 Pri...

Page 3: ...display indicates room temperature and the word ROOM is shown on the LCD until the temperature selector is pressed at which time the display temporarily indicates the setpoint temperature and the word...

Page 4: ...mp is locked out for 2 hours backup heat counter is reset if Heat Pump is running for more than 20 minutes and does not call for backup heat 71 Gas Furnace turns off Thermostat satisfied 69 Gas Furnac...

Page 5: ...Above Set ID fan high compressor 1 and OD blower low cycle as needed 9 Cool Auto Hi Stage 2 2 Degrees Above Set ID fan high compressors 1 and 2 and OD blower high cycle as needed 10 Cool On Hi No ID...

Page 6: ...6 II HEAT PUMP OPERATION SEQUENCE COOLING MODE...

Page 7: ...7 III HEAT PUMP OPERATION SEQUENCE HEATING MODE...

Page 8: ...8 IV 6535 320 PRINTED CIRCUIT BOARD FUNCTION CHART...

Page 9: ...you were looking straight at it NOTE 1 Pin connections in this p c board socket are identical to those in the thermostat 2 Low voltage connections to the p c board socket are subject to thermostat tim...

Page 10: ...s HOT leg power continues from terminal T6 to the High Speed motor tap 4 The motor starts and runs on High Speed until the signal is lost from the thermostat LOW SPEED INDOOR BLOWER OPERATION 1 Begins...

Page 11: ...l 4 The Compressor Relay 1 closes 5 Compressor 1 starts and runs until the compressor signal is satisfied at the thermostat What else might shut the compressor off COMPRESSOR 2 COOLING OPERATION 1 Beg...

Page 12: ...Outdoor Coil Sensor T16 and T17 terminals are connected to a thermister located in the condenser Outdoor coil 2 This sensor is an active part of the circuit only in the heating mode 3 This sensor is i...

Page 13: ...e same 2 second time delay 3 The Outdoor Blower starts and runs on Low speed until compressor 1 goes off or the second stage cooling is energized HIGH SPEED OUTDOOR BLOWER OPERATION 1 Begins with a 11...

Page 14: ...eg to the motor is not routed through the printed circuit board 6 The 115 volts HOT leg power continues from terminal T6 to the High Speed motor tap and the motor begins to run on High Speed 7 12 VDC...

Page 15: ...15 V WIRING DIAGRAM 6536 SERIES TWO TON PACKAGED HEAT PUMP...

Page 16: ...6536 A Model Secondary Wiring Diagram 6536 B SERIES TWO TON PACKAGED HEAT PUMP...

Reviews: