REQUIREMENTS 

1.  The pump should be located in a well-

ventilated but frost-free area. 

2.  The distance between pump-motor and 

other objects should be at least 6 inches to 
avoid overheating. 

3.  To minimize inlet wear, use the shortest 

inlet pipe possible. 

4.  Ensure check valve is installed on discharge 

pipe. If pump is used for boiler water supply, 
a check valve must be installed in the piping 
between the pump and boiler. 

5.  Pump should be installed on cement base, 

or other similar base with suitable height. It 
can also be bolted securely to a wall. 

6.  When installing the drainage pipe, support 

pipe weight to avoid strain on the pump and 
twisting of the pipe. 

 

! WARNING ! 

Pump should never be mounted with the 
motor hanging upside down. 

 
7.  Arrows on the inlet and outlet indicate the 

direction of liquid flow through the pump. 
Verify that liquid can flow easily before 
starting the pump. 

8.  Before installation, the inlet pipeline should 

be cleaned. If the pumped liquid contains 

impurities, a strainer should be installed 1.5’ 
to 3’ in front of the inlet (particularly 
recommended for pumps with flows less 
than 35 gpm). 

9.  Avoid airlocks when installing the inlet pipe. 

Refer to 

Figure 3

.  

 

 

Figure 3 

 

10. Install bypass on outlet pipe to ensure 

adequate lubrication and cooling.  

11. Motor should be correctly grounded. Pump 

can be damaged by phase loss, unstable 
power or power surge.  

12. Install a pressure meter on pump outlet to 

monitor pump operation. 

 

 

ELECTRICAL CONNECTION– SECTION C 

 

! WARNING ! 

Electrical installation should be carried out 
in accordance with the local electrical code. 
Make sure that the electricity supply has 
been switched off before electrical 
connection. 
 
Use care when accessing pump electrical 
components.  

 

SPECIFICATIONS 

Electrical specifications (voltage, hertz) are 
shown on the pump nameplate. Verify that the 
power supply voltage and hertz match pump 
requirements. An external ON/OFF switch must 
be installed. 
 
 
 

CONNECTION 

Electrical connection should be in accordance 
with diagram shown on the connecting box, and 
motor current should be within rated amps as 
shown on nameplate. Three phase pump 
requires extra magnetic starter with protection. 
 

ROTATION DIRECTION 

On this three phase motor, rotating direction is 
critical. The rotating direction is indicated on the 
fan cover (counterclockwise viewing from fan 
cover end). Interchanging any two leads with 
power off can reverse the pump rotation. 
 

POSITIONING CONNECTION BOX 

The position of the motor connecting box is 
adjustable. Referring to 

Figure 4

, the position 

can be changed by removing the motor fan 
cover, unscrewing the frame bolts, and turning 

Summary of Contents for RAE PUMPS MSVF 1

Page 1: ...tenance Manual MSVF Series Multistage Vertical External Mount Pumps RAE Pumps 1212 Streng Street Cincinnati OH 45223 513 779 3034 www RAEPumps com 60 Hz MODELS MSVF 1 MSVF 2 MSVF 3 MSVF 4 MSVF 8 MSVF16 MSVF 32 MSVF 42 MSVF 65 MSVF 85 ...

Page 2: ...07 PERIODIC INSPECTION 07 TROUBLESHOOTING SECTION E 08 DIMENSIONS SECTION F 09 MSVF 1 DIMENSIONS WEIGHTS AND OUTLINE DRAWING 09 MSVF 2 DIMENSIONS WEIGHTS AND OUTLINE DRAWING 09 MSVF 3 DIMENSIONS WEIGHTS AND OUTLINE DRAWING 10 MSVF 4 DIMENSIONS WEIGHTS AND OUTLINE DRAWING 10 MSVF 8 DIMENSIONS WEIGHTS AND OUTLINE DRAWING 11 MSVF 16 DIMENSIONS WEIGHTS AND OUTLINE DRAWING 11 MSVF 32 DIMENSIONS WEIGHTS...

Page 3: ...ps 1212 Streng Street Cincinnati OH 45223 513 779 3034 Info RAEPumps com www RAEPumps com For information or technical assistance on the power source contact the power source manufacturer s local dealer or representative DANGER This pump is not intended to transfer explosive liquids such as gasoline diesel oil and other similar liquids It is only suitable for water and diluted low viscosity non co...

Page 4: ... 290 290 377 261 218 MOTOR DATA Nominal speed 3500 rpm at 60 Hz Standard voltage 3 phase 230V 460V Protection class IP54 Insulation class F INSTALLATION SECTION B WARNING When running the motor surface column and base temperature is extremely high especially when high temperature liquids are being pumped Mount pump in a safe place to avoid accidental touch HANDLING When lifting pumps with motor si...

Page 5: ...ass on outlet pipe to ensure adequate lubrication and cooling 11 Motor should be correctly grounded Pump can be damaged by phase loss unstable power or power surge 12 Install a pressure meter on pump outlet to monitor pump operation ELECTRICAL CONNECTION SECTION C WARNING Electrical installation should be carried out in accordance with the local electrical code Make sure that the electricity suppl...

Page 6: ...ection should be counterclockwise viewing from fan cover end 2 Piping and joints are fitted carefully to prevent leaks 3 The pump has been filled with liquid as described in the START UP instructions below Failure to do so will damage the bearing and mechanical seal 4 The suction filter is clear of obstruction START UP 1 Do not start the pump until it has been filled completely with liquid 2 To fi...

Page 7: ...mps with a motor power equal to or less than 5HP should not be restarted more than 100 times per hour Pumps with a motor power greater than 5HP should not be restarted more than 20 times per hour SEAL MAINTENANCE Mechanical seal will be adjusted automatically The rotating and stationary parts are lubricated and cooled by the transferring liquid When replacing the mechanical seal the user needn t d...

Page 8: ...circuit Pump runs but liquid flow is inconsistent 1 Suction pipe is too small 2 Insufficient liquid in the pump inlet 3 Liquid level is low 4 Pump inlet pressure is too low compared to water temperature pipeline loss and flow 5 Suction pipe is partially blocked 1 Enlarge inlet pipeline 2 Improve system and increase incoming liquid 3 Try to lift liquid level 4 Improve system and increase inlet pres...

Page 9: ...0 31 57 20 16 11 41 7 48 6 10 81 57 145 MSVF1 170 32 99 21 57 11 41 7 48 6 10 83 78 145 MSVF1 190 34 41 22 49 11 41 7 48 6 10 90 39 145 MSVF1 210 35 83 24 41 11 41 7 48 6 10 92 59 145 MSVF1 230 37 24 25 83 11 41 7 48 6 10 94 80 145 MSVF1 250 41 22 27 64 13 58 7 76 6 50 112 44 145 MSVF2 Model A B C D E Weight Max Inlet Pressure inches inches inches inches inches pounds psi MSVF2 20 19 02 10 16 8 86...

Page 10: ... 7 48 6 10 85 98 145 MSVF3 170 32 99 21 57 11 41 7 48 6 10 88 18 145 MSVF3 190 36 97 23 39 13 58 7 76 6 50 105 82 145 MSVF3 210 38 39 24 80 13 58 7 76 6 50 108 02 217 MSVF3 230 39 80 26 22 13 58 7 76 6 50 110 23 217 MSVF3 250 41 61 27 64 13 98 9 07 7 40 127 87 217 MSVF4 Model A B C D E Weight Max Inlet Pressure inches inches inches inches inches pounds psi MSVF4 20 20 91 11 26 9 65 6 69 5 59 52 91...

Page 11: ... 19 176 37 145 MSVF8 120 42 40 27 04 15 35 10 23 8 19 180 78 145 MSVF8 140 52 56 32 87 19 69 12 99 10 04 337 31 145 MSVF16 Model A B C D E Weight Max Inlet Pressure inches inches inches inches inches pounds psi MSVF16 20 1 27 04 15 63 11 41 7 48 6 10 92 59 87 MSVF16 20 30 00 16 02 13 98 9 06 7 40 123 46 87 MSVF16 30 33 94 18 58 15 35 10 23 8 19 149 91 145 MSVF16 40 35 71 20 35 15 35 10 23 8 19 165...

Page 12: ...F32 80 68 90 43 31 22 59 15 75 12 20 694 46 217 MSVF32 90 2 71 65 42 06 22 59 15 75 12 20 703 28 217 MSVF32 90 71 65 42 06 22 59 15 75 12 20 703 28 217 MSVF32 100 2 74 41 48 82 22 59 15 75 12 20 714 30 217 MSVF32 100 74 41 48 82 22 59 15 75 12 20 714 30 217 MSVF42 Model A B C D E Weight Max Inlet Pressure inches inches inches inches inches pounds psi MSVF42 10 1 37 48 22 09 15 37 10 23 8 19 222 67...

Page 13: ...8 11 13 39 877 44 217 MSVF65 50 2 66 38 39 41 26 97 18 11 13 39 886 26 217 MSVF85 Model A B C D E Weight Max Inlet Pressure inches inches inches inches inches pounds psi MSVF85 10 1 42 17 22 48 16 69 12 99 10 04 390 21 58 MSVF85 10 42 17 22 48 16 69 12 99 10 04 414 47 58 MSVF85 20 2 52 09 30 43 21 65 12 99 10 04 465 18 145 MSVF85 20 1 53 07 30 43 22 64 14 17 11 22 546 75 145 MSVF85 20 56 02 30 43 ...

Page 14: ... been properly installed and maintained and has not been subject to abuse Modifications including removal of pump tags or misapplication void this warranty Pump must return to RAE Pumps with complete history of service for inspection and warranty consideration RAE Pumps does not accept the responsibility for transportation to and from our plant Furthermore we do not assume any responsibility for c...

Reviews: