background image

DPT-IQ

options

Default

options

options

options

options

options

options

options

options options options options options

Response

Time

1 Sec

V output

Max

0-Max CFM

corresponds

to 0-10VDC

P output

Max

line 1

Unit

line 2

Unit

Duct

Height

Duct 

Width

In

In

SqFt

1.0

Inwc

CFM

Model

AMS

Mode

Voltage

0-10V

Gain

area

AMS050

CDRAMS

AML3
AML6

CCUV*

AMP001
AMP002
AMP003
AMP015
AMP025

1-20 Sec

Voltage

0-5V

Current

4-20mA

l/s

m/s

FPM

m/min

m3/s

l/s

m/s

FPM

m/min

Pa

inwc

m3/s

Pa

FPM

m/min

Pa

m3/s
CFM

l/s

m/s

0.2 to

5.0

9

8

7

6

5

4

3

2

1

10

11

Diameter for CDRAMS

Diameter for AMP025

Notes

0-1 inwc

corresponds

to 0-10VDC

  1 

Model 

Choose the Ruskin Model that is piped to the DPT-IQ. (Or CCUV if not listed)

  2 

Response  The Ruskin DPT-IQ enables you to set the Response Time from 1 – 20 seconds with 1 second increments. 

  

Time 

Increasing the Response Time can reduce the influence of air turbulence.

  3 

Mode 

Use jumpers to complete, as described in Step 3 above.

  4 

V output  The Ruskin DPT-IQ enables you to set the Velocity or Volume Output Maximum, to improve resolution of the flow reading,

  

Max  

by limiting the range. NOTE: Output Units can be different from Display Units.

   

CFM 

50 Min to 100,000 Max - 1 CFM increments

   

l/s 

25 Min to 50,000 Max - 1 l/s increments

   

m/s 

1 Min to 100 Max - 1 m/s increments

   

FPM 

2,000 Min to 20,000 Max - 10 FPM increments

   

m/min 

60 Min to 6000 Max - 1 m/min increments

   

m3/s 

0.025 Min to 50 Max - 0.001 increments

   

 

EXAMPLE: The DPT-IQ has an effective range of 50 – 100,000 CFM. If Flow Volume readings are expected below 12,000  

   

 

CFM, adjust the V Output Maximum to 12,000 CFM, to improve resolution. The DPT-IQ can have the V Output Maximum  

   

 

set between 50 – 100,000 CFM, to improve resolution.

  5 

P output 

Set the Pressure Output Maximum, to improve resolution of the Pressure reading,

  

Max  

by limiting the range. NOTE: Output Units can be different from Display Units.

   

inwc 

0.10 inwc Min to 4.0 inwc Max - 0.01 inwc increments

   

Pa 

100Pa Min to 1000Pa Max - 50Pa increments

   

 

EXAMPLE: The DPT-IQ has a capable range of 0 – 4.0 inwc. If pressure readings are expected below 1.00 inwc, adjust   

   

 

the Pressure Output Maximum to 1.00 inwc, to improve resolution. The DPT-IQ can have the Pressure Output Maximum  

   

 

set between 0.1 – 4.0 inwc, to improve resolution.

  6  line 1 Unit  Choose which SI unit (inwc, FPM, CFM) or UI unit (m3/s, Pa, m/min. m/s, l/s) you will use.
  7  line 2 Unit  Choose which SI unit (inwc, FPM, CFM) or UI unit (m3/s, Pa, m/min. m/s, l/s) you will use.
 8 

Gain  The GAIN feature is designed to allow modification to the reported output. The number shown is a multiplier. Increase    

   

 

the reported output by increasing the GAIN number above 1.000. (To increase reported output by 5%, adjust number to   

   

 

1.050. Decrease the reported output by decreasing the GAIN number to less than 1.000. (To decrease reported output by  

   

 

5%, adjust number to 0.950. The range is from 0.200 to 5.000 with 0.001 increments.

 9 

area  Area is computed when you enter duct height and width for rectangular units, and diameter for round units. The computed  

   

 

value can be over-ridden if you enter an area (in square feet) in this selection.

  10  Duct Height  Enter in inches
  11  Duct Width  Enter in inches

note

sTeP 3  ConFIGURaTIon (continued)

size

RUsKIn DPT-IQ FloW MeTeR WITH BaCKlIT DIsPlaY InsTallaTIon InsTRUCTIons

5

* CCUV (Custom Configurable Universal Values) allows for Ka values and exponent values to match any device not listed in the Model column.  
Default value is Ka = 4005 and exponent 1/m = 0.5

Summary of Contents for DPT-IQ

Page 1: ...ns Installation Maintenance Manual Model DPT IQ Flow Meter with Backlit Display II DPT IQ 818 Replaces II DPT IQ 315 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE OR OBLIGATION...

Page 2: ...he Flow Meter DPT IQ measures airflow velocity and differential pressure It is designed to be used in combination with any Ruskin velocity pressure air measuring probe AMP series air measuring louver...

Page 3: ...ion WARNING Apply power after the device is properly wired STEP 1 MOUNTING THE DEVICE 1 Select mounting location duct wall panel within 120 feet of the air measurement station 2 Use the device as a te...

Page 4: ...MENU Selection convention used to input information into DPT IQ Entering information into the DPT IQ is accomplished with three 3 Menu buttons see Figure 3B The Menu buttons are labeled as follows Bu...

Page 5: ...n have the V Output Maximum set between 50 100 000 CFM to improve resolution 5 P output Set the Pressure Output Maximum to improve resolution of the Pressure reading Max by limiting the range NOTE Out...

Page 6: ...ice will proceed automatically Zeroing is complete when the LED turns off and the display reads 0 Press zero button again if zero is not displayed d Reinstall the pressure tubes ensuring the High pres...

Page 7: ...menu DISPLAY 31 2 Digit LCD 1 81 x 0 57 46 x 14 5mm Enclosure ABS UL94 V 1 NEMA 3 3 54 x 3 74 x 1 4 90 0 x 95 0 x 36 0 mm Measuring Element Piezoresistive Operating Range Air temperature Range of 14...

Page 8: ...3900 Dr Greaves Rd Kansas City MO 64030 816 761 7476 FAX 816 765 8955 www ruskin com 3900 Dr Greaves Rd Kansas City MO 64030 816 761 7476 FAX 816 765 8955 www ruskin com...

Reviews: