![Runway GK-C03NC1AD Owner'S Manual Download Page 18](http://html1.mh-extra.com/html/runway/gk-c03nc1ad/gk-c03nc1ad_owners-manual_1500199018.webp)
Rooftop Packaged
14
5.Electrical Installation
5.1 Electrical Date and Wire Sizing
Unit Model
Designation
Power Supply
(V, Ph, Hz)
Capability of Air
Switch(A)
Min. Sectional
Area of Earth
Wire(mm
2
)
Min. Sectional
Area of Power
Cord(mm
2
)
GK-C03NC1AD
220V,1Ph,60Hz
32
6
6
GK-C03TC1AD
220V,1Ph,60Hz
40
10
10
GK-C03TC1AK
220V,1Ph,50Hz
32
6
6
GK-C04NC1AD
220V,1Ph,60Hz
50
16
16
GK-C04TC1AF
220V,3Ph,60Hz
32
6
6
GK-C04TC1AM
380-415V,3Ph,50Hz
16
2.5
2.5
GK-C05NC1AD
220V,1Ph,60Hz
50
16
16
GK-C05NC1AF
220V,3Ph,60Hz
25
6
6
GK-C05TC1AF
220V,3Ph,60Hz
32
6
6
GK-C05TC1AM
380-415V,3Ph,50Hz
20
4
4
GK-H05TC1AM
380-415V,3Ph,50Hz
20
4
4
GK-C08TC1AF
220V,3Ph,60Hz
63
16
25
GK-C08TC1AM
380-415V,3Ph,50Hz
40
10
10
GK-H08TC1AM
380-415V,3Ph,50Hz
40
10
10
GK-C10TC1AF
220V,3Ph,60Hz
63
16
25
GK-C10TC1AM
380-415V,3Ph,50Hz
40
10
10
GK-C10TC1AM*
380-415V,3Ph,50Hz
100
25
50
GK-H10TC1AM
380-415V,3Ph,50Hz
40
10
10
GK-C13TC1AF
220V,3Ph,60Hz
100
25
50
GK-C15TC1AF
220V,3Ph,60Hz
100
25
50
GK-C15TC1AM
380-415V,3Ph,50Hz
63
16
25
GK-C15TC1AM*
380-415V,3Ph,50Hz
110
25
50
GK-H15TC1AM
380-415V,3Ph,50Hz
63
16
25
GK-C20TC1AF
220V,3Ph,60Hz
125
25
50
GK-C20TC1AM
380-415V,3Ph,50Hz
80
16
35
GK-C20TC1AM*
380-415V,3Ph,50Hz
120
25
50
GK-H20TC1AM
380-415V,3Ph,50Hz
80
16
35
GK-C25TC1AF
220V,3Ph,60Hz
160
50
95
GK-C25TC1AM
380-415V,3Ph,50Hz
100
25
50
GK-C25TC1AM*
380-415V,3Ph,50Hz
130
25
50
GK-H25TH1AM
380-415V,3Ph,50Hz
100
25
50
GK-H30TH1AM
380-415V,3Ph,50Hz
125
35
70
GK-C30TC1AM
380V,3Ph,50Hz
125
35
70
Note: *The unit with electric heat.