Drive Roller RDR  BL-2  Version 1.1 

User installation, connection & Warranty Manual

 

User-Man-RDR BL-2 v.1.1 - Rev 30-03-17.docx                                  pag. 2 

 

CABLE CONNECTIONS  

0V  GND

  (MAIN SUPPLY) 

BLUE 

wires section 

0.5 mm² 

+24 VDC

  (MAIN SUPPLY) 

BROWN 

DIRECTION 

BLACK 

wires section 

0.2 mm² 

ON-OFF

,    SPEED ADJUST 

GREY 

+10 VDC output 

RED 

TTL SIGNAL (5V) 

GREEN 

FAULT output (Max. 20mA) 

YELLOW 

A white wire is present in the cable with no customer use, to be kept 

isolated. The input-output signals are PNP type and possible to be 

directly connected to PLC. 

 

POWER SUPPLY:

  connect the BLUE (GND) and BROWN (24VDC) 

bigger section wires to a 24VDC power supply, sufficient for all the 

connected RDR running at a time, at the max transported  load 

absorbed current. If a PLC or outer signals are used, the 0V-GND of 

RDR power supply and the one of PLC must be jumped together. 

IMPORTANT

: Verify that no high spikes over 40V are present on the 

DC supply or on the signals, or in case put filters on disturb sources 

(contactors, AC motors etc.), or  use  different  power supplies, with 

se24VDC.  Avoid to connect RDR 0VDC to the AC ground, if 

this is required please ensure that no eddy currents are present. 

In case of very long 24VDC main supply line, verify on RDR a voltage 

around  to 24V  (or in any case in  between  the admitted voltage        

18-28V) on nearer and farer loaded RDRs from power supply.  

In case adjust power supply voltage, increase wires section and/or 

connect 24VDC supply as closed loop. 

WARNING

: in case a power supply is feeding many RDRs with 

frequent contemporary start/stops or inclined conveyor, please use 

a Motor Brake Controller system (Chopper). Example Cabur MBC2K 

or Maxon Motor Shunt Regulator  or Mi-Control mod. mcER-L40 o 

L41, not included in the delivery, 1 each power supply (please ask 

technical details to Rulmeca). 

 

START : 

after having connected the 24 VDC supply,

 

to start the RDR 

at max speed apply 10-24VDC to the GREY wire or jump the RED and 

GREY leads.

 

WARNING

: do not switch off the RDR by direct contacts on the main 

24VDC supply, because the load inertia can cause RDR over-voltages 

and electronics faults. 

Start-stop by contact near the RDR 

(max 3 m) 

 

Start-stop by remote contact 

 

Start-stop by PLC 

 

 

SPEED VARIATION : 

apply a variable voltage 0÷10V or 24V, to GREY 

wire:  2.3VDC 

 standing;  2.3 ÷ 10 VDC 

 min-max speed adjust; 

10 ÷ 24 VDC 

 all max speed.  Use a 10KΩ potentiometer. 

The RED wires, gives a 10VDC for the signal supply.  

Speed adjustment by potentiometer near the RDR 

 

Speed adjustment by remote potentiometer 

 

Speed adjustment by PLC 

 

 

DIRECTION REVERSAL

: the not connected BLACK wire voltage level is 

low (0V) and the RDR is running in the default clockwise direction. 

To invert the RDR rotation into anti-clockwise direction, give a +24V 

to the BLACK wire. The rotation direction is seen from the cable side. 

WARNING: The reverse signal must be given before the start signal, 

with the standing RDR. 

 

 

TTL Signal

: green wire. The internal TTL sensors give a 

square wave 0–5V (TTL signal) with a resolution of 12 

pulses per motor rotor revolution, at any speed.

 

 

FAULT

: in case the RDR is running at correct temperature and 

current, the Fault signal output voltage on the YELLOW cable is 

+24VDC. In case of over-temperature (>85°C)  or  over-current  the 

Fault signal output voltage is going down to GND-0V (alarm logic). 

The fault signal output can provide max 20 mA. 

Over-temperature fault

: RDR BL-2 gets an inner temperature sensor. 

When the motor temperature goes over 85°C, the RDR activates the 

Fault signal output (YELLOW wire), by pulling it from +24V down to 

0V.  After 60 seconds, if the RDR is not manually switched off, the 

inner drive provides to switch off the motor. The over-temperature 

Fault  signal automatically  resets  after the motor reaches a 

temperature <75°C and the RDR resumes to work. 

Over-current fault

:  the RDR BL-2 motor is protected against over-

current due to roller overloading or material block on the conveyor. 

If the current goes over 3A, the inner drive reduces the current down 

to 1.5A for 2 sec., then stops the motor. Then it is trying to restart 

the roller 3 times. If still blocked, the fault signal output is activated 

by pulling it from +24V down to 0V and the motor is switched off.   

To reset the over-current Fault, the material block must be removed 

and then the mains supply must be switched off and after few 

seconds back on. The RDR restarts normally.  

 

SAFETY PROTECTION:

 

the RDR Drive Roller is protected against 

polarity inversion of the supply voltage, for  a safe connection 

avoiding burning risks. 

WARRANTY 

Rulmeca

 gives a 12 months warranty, starting from the delivery date, on 

the RDR Drive Rollers and on the external Electronic boards (if any), 

against material or production defects.  According to this warranty, the 

products returned to our factory site: Via Toscanini 1, 24011 Almè (BG), 

Italy, or to our Rulmeca sister company sites and found defective, will be 

repaired or replaced under warranty. 

-As pure components, the present warranty doesn't cover the costs for 

RDR  disassembling-reassembling from the conveyor and for return 

transports. 

-This warranty is void in case of clear overloaded products, twisted cables, 

incorrect assembly, wrong connection (not according to the present 

diagrams  and instructions), tampering, alteration, wrong cleaning with 

aggressive procedures or products and intervention by people not 

qualified by Rulmeca. 

-The std. warranty is not covering the working wear of the shell, rubber or 

coatings or other damages due to shocks or accidents. 

-The warranty is not covering indirect damages or loss of production due 

to product brake down (for critical applications keep proper spare parts, 

suitable for fast replacement). 

- This warranty is applying to the Rulmeca client and it is not transferable 

to a third part. 