background image

2. Installation

RuggedCom® RuggedSwitch™

10

RS900G Installation Guide Rev 107

2. Installation

2.1. DIN Rail Mounting

An optional DIN rail mounting bracket is available for the RS900G.

Figure 2.1. DIN Rail Mounting

Summary of Contents for RUGGEDSWITCH RS900G

Page 1: ...RuggedSwitch RS900G Hardware Installation Guide Revision 107 April 10 2013 www RuggedCom com ...

Page 2: ...X RuggedBackbone RuggedRated and eRSTP are trademarks of RuggedCom Inc ROS RuggedRouter and RuggedSwitch are registered trademarks of RuggedCom Inc Other designations in this manual might be trademarks whose use by third parties for their own purposes would infringe the rights of the owner Linux is the registered trademark of Linus Torvalds in the U S and other countries The registered trademark L...

Page 3: ...ounding 12 2 3 HIPOT Dielectric Strength Testing 13 2 4 Failsafe Output Wiring and Specifications 13 2 5 RS232 Port Wiring 13 2 6 RJ45 Ports Signal Description 15 3 Specifications 16 3 1 Operating Environment 16 3 2 Power Supply Specifications 16 3 3 Failsafe Relay Specifications 16 3 4 Twisted Pair Data Port Specifications 16 3 5 Fiber Optic Port Specifications 17 3 6 Physical Dimensions 18 3 7 T...

Page 4: ...S900G Front Panel 9 1 2 RS900G Bottom Panel 9 2 1 DIN Rail Mounting 10 2 2 Power Supply Inputs 11 2 3 DC Power Supply Wiring and Grounding 12 2 4 HIPOT Dielectric Strength Testing 13 2 5 Failsafe Output Relay 13 2 6 RS232 Female Connector 14 2 7 RJ45 Port Connector 15 3 1 RS900G Physical Dimensions 18 ...

Page 5: ...ernet Pin Assignment 15 3 1 Operating Environment 16 3 2 RS900G Power Supply Specifications 16 3 3 Failsafe Relay Specifications 16 3 4 Twisted Pair Data Port Specifications 16 3 5 Fiber Optic Port Specifications 17 3 6 Physical Specifications 18 3 7 RS900G IEC 61850 3 Type Tests 19 3 8 RS900G IEEE 1613 Type Tests 20 3 9 IEC Environmental Type Tests 20 3 10 Agency Approvals 22 ...

Page 6: ...terference in which case the user will be required to correct the interference at his own expense Caution Service This product contains no user serviceable parts Attempted service by unauthorized personnel shall render all warranties null and void Changes or modifications not expressly approved by RuggedCom Inc could invalidate specifications test results and agency approvals and void the user s a...

Page 7: ...rray of intelligent functionality for high network availability and manageability Ethernet Ports 2 Fiber Optic Gigabit Ethernet Ports 1000BaseX 8 Fast Ethernet Ports 10 100BaseTX Full compliance with IEEE 802 3 802 3u and 802 3z Non blocking store and forward switching Full duplex operation and flow control IEEE 802 3x Industry standard fiber optical connectors LC SC SFP Bi Directional simplex fib...

Page 8: ...ators for link activity and speed ROS Advanced Network Management Enhanced Rapid Spanning Tree eRSTPTM Quality of Service 802 1p for real time traffic Port rate limiting 128kbps to 8Mbps VLAN 802 1q with double tagging IGMP Snooping for multicast filtering Port configuration status statistics mirroring security Loss of link management on fiber ports Web based Telnet CLI management interfaces SNMP ...

Page 9: ...ront Panel Figure 1 1 RS900G Front Panel LED Activity Description Solid Link Established LINK LED Yellow Blinking Tx Rx Activity Power LED Solid Power On Alarm LED Solid Alarm condition exists Table 1 1 RS900G Front Panel LED Definitions 1 2 RS900G Bottom Panel Figure 1 2 RS900G Bottom Panel ...

Page 10: ...Installation RuggedCom RuggedSwitch 10 RS900G Installation Guide Rev 107 2 Installation 2 1 DIN Rail Mounting An optional DIN rail mounting bracket is available for the RS900G Figure 2 1 DIN Rail Mounting ...

Page 11: ...und is used as the ground conductor for all surge and transient suppression circuitry internal to the RS900G unit 4 Chassis Ground should be connected to the AC Ground terminal 1 Equipment must be installed according to the applicable country wiring codes 2 Surge Ground MUST be disconnected from the Chassis Ground during HIPOT dielectric strength testing 3 All line to ground transient energy is sh...

Page 12: ... must be connected to the DC inputs according to the polarity markings on the unit 1 Equipment must be installed according to the applicable country wiring codes 2 Surge Ground should be connected to Chassis Ground via a braided cable or other appropriate ground wire 3 Chassis Ground must be connected to the protective earth 4 All line to ground transient energy is shunted to the Surge Ground term...

Page 13: ... test Figure 2 4 HIPOT Dielectric Strength Testing 2 4 Failsafe Output Wiring and Specifications The Failsafe output relay is provided to signal critical error conditions that may occur on the RS900G The contacts are energized upon power up of the unit and remain energized until an alarm condition or power loss occurs Figure 2 5 Failsafe Output Relay 2 5 RS232 Port Wiring The RS232 port is used fo...

Page 14: ... Connector Pin Signal 1 No Connection 2 Transmit Data 3 Receive Data 4 No Connection 5 Ground 6 No Connection 7 No Connection 8 No Connection 9 No Connection Table 2 1 RS232 Female DCE Pinout This port is not intended to be a permanent connection and the cable shall be less than 2m 6 5 ft in length ...

Page 15: ...0 100 1000Base Tx 1 RX A 2 RX A 3 TX B 4 NC C 5 NC C 6 TX B 7 NC D 8 NC D Table 2 2 RJ45 Ethernet Pin Assignment RuggedCom does not recommend the use of CAT 5 cabling of any length for critical real time substation automation applications However transient suppression circuitry is present on all copper ports to protect against damage from electrical transients and to ensure IEC 61850 3 and IEEE 16...

Page 16: ...ing Isolation Maximum Power Consumption 12 24 VDC 10 VDC 36 VDC 3 15A T a 1 5 kV DC 24 VDC 18 VDC 36 VDC 3 15A T a 1 5 kV DC 48 VDC 36 VDC 72VDC 3 15A T a 1 5 kV DC HI 125 250 VDC b HI 110 230 VAC b 88 VDC 85 VAC 300 VDC 265 VAC 3 15A T a 4 kV AC 5 5 kV DC 10W a T denotes time delay fuse b This is the same power supply for both AC and DC Table 3 2 RS900G Power Supply Specifications 3 3 Failsafe Re...

Page 17: ... 25 2SC10 SM SC 1310 9µ 125 10 3 22 3 10 2SC25 SM SC 1310 9µ 125 7 3 24 3 25 SFP MM LC 850 50µ 125 8 5 4 22 3 0 5 SFP SM LC 1310 9µ 125 9 3 24 0 10 SFP SM LC 1310 9µ 125 7 3 26 3 25 SFP d SM LC 1550 9µ 125 5 0 26 0 50 SFP d SM LC 1550 9µ 125 0 5 26 0 80 SFP SM SC Simplex 1310 9µ 125 9 3 22 3 10 SFP d SM SC Simplex 1490 9µ 125 9 3 22 3 10 a All cabling is duplex type unless otherwise specified b Al...

Page 18: ...n Guide Rev 107 3 6 Physical Dimensions Figure 3 1 RS900G Physical Dimensions Parameter Value Comments Dimensions 7 4 2 6 5 0 inches 187 96 66 04 127 0 mm Length Width Depth Weight 2 7 lbs 1 2 kg Enclosure 20 AWG Galvanized Steel Table 3 6 Physical Specifications ...

Page 19: ... 40 A m continuous 1000 A m for 1 s N A D C Power ports 30 for 0 1s 60 for 0 1s 100 for 0 05s N A IEC 61000 4 29 Voltage Dips Interrupts A C Power ports 30 for 1 period 60 for 50 periods N A IEC 61000 4 11 Voltage Dips Interrupts A C Power ports 100 for 5 periods 100 for 50 periods N A Signal ports 2 5kV common 1kV differential mode 1MHz 3 D C Power ports 2 5kV common 1kV differential mode 1MHz 3 ...

Page 20: ... C Power ports 5 kV Signal ports 2kV AC Failsafe Relay D C Power ports 1 5kV DC C37 90 6 Dielectric Strength A C Power ports 2kV AC Table 3 8 RS900G IEEE 1613 Type Tests If the unit contains copper ports the IEEE 1613 conformance is Class 1 During disturbance errors may occur but recovery is automatic If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 During disturbance no e...

Page 21: ...3 Specifications RuggedCom RuggedSwitch 21 RS900G Installation Guide Rev 107 ...

Page 22: ...950 EN 61000 6 2 CE Compliance is claimed via Declaration of Self Conformity Route FCC FCC Part 15 Class A Approved CISPR EN55022 Class A Approved FDA CDRH 21 CFR Chapter 1 Subchapter J Approved IEC EN EN60825 1 1994 A11 1996 A2 2001 Approved CSA Hazardous Locations Class 1 Division 2 Groups A B C D T6 rating at 40 C T4A rating at 85 C Approved Table 3 10 Agency Approvals ...

Page 23: ...is product contains no user serviceable parts Attempted service by unauthorized personnel shall render all warranties null and void For warranty details visit www RuggedCom com or contact your customer service representative Should this product require service contact the factory at RuggedCom Inc 300 Applewood Crescent Concord Ontario Canada L4K 5C7 Phone 1 905 856 5288 Fax 1 905 856 1995 ...