5.6 Type Test Specifications
Electrical Safety
Levels
Comments
Dielectric Withstand
2 kV RMS for 1 minute
ANSI/IEEE C37.90 (1989)
IEC 60255-5 (Section 6)
High Voltage Impulse
5 kV peak
IEC 60255-5 (Section 8)
Insulation Resistance
500 VDC for 1 minute
IEC 60255-5 (Section 6
Electrical Environment
Levels
Comments
High Frequency Disturbance
(Oscillatory)
2.5 kV @ 1MHz for 2s
ANSI/IEEE C37.90.1
IEC 60255-22-1
IEC Surge
4 kV / 2 kV
IEC 61000-4-5
(Level 4)
IEC Fast Transient
2 kV / 1 kV
IEC 61000-4-4
(Level 4)
ANSI/IEEE Fast Transient
4 kV
ANSI/IEEE C37.90.1
IEC Radiated RFI Immunity
10 V/m
IEC 61000-4-3
ANSI/IEEE Radiated RFI
Immunity
35 V/m
ANSI/IEEE C37.90.2
ESD
(Electrostatic Discharge)
15 kV (air discharge)
8 kV (contact)
IEC 61000-4-2
(Level 4)
Atmospheric Environment
Levels
Comments
Temperature (Dry Cold)
-40
°
C
IEC 60068-2-1
Test Ad: 16 hrs @ -40
°
C
Temperature (Dry Heat)
85
°
C
IEC 60068-2-2
Test Bd: 16 hrs @ 85
°
C
Humidity
95%
non-condensing
IEC 60068-2-30
Test Db: 6 cycles, 55
°
C, 95% Humidity
5.7 Operating Environment
Parameter
Range
Comments
Ambient Operating
Temperature
-40 to 85
°
C
Ambient Temperature as
measured from a 30cm
radius surrounding the
center of the enclosure.
Ambient Relative Humidity
5% to 95%
Non-condensing
Ambient Storage
Temperature
-40 to 85
°
C