5
on, but the card is shown in red on the NetArrays IOC screen and cannot be enabled, this
indicates an error in the cards calibration data.
For long term accuracy, the calibration channels should be monitored to the desired accuracy
tolerance.
In order to measure current, the 3099/11 Termination Module contains eight (8) 0.01% precision
250
resistors that convert the input currents to voltages for measurement by the card. The
3099/11 termination module can also dist24 VDC fused power through a resettable fuse,
per channel, rated at 300 mA, 30 Volts max, to current mode sensors.
Another current measurement option, the S3099/11-001 Termination Module contains eight (8)
0.01% precision 100
resistors that convert the input currents to voltages for measurement by
the card. The S3099/11 Termination Module can also dist80 VDC fused power through a
replaceable fuse rated at 2.5 amps, 80 Volts max, to current mode sensors. Each channel on the
S3099/11-001 has a 125 mA replaceable fuse.
The 3108 and 3118 cards can be used with user supplied field termination. The card can be
connected to the field termination by using RTP supplied flying lead termination cable or user
supplied field wiring/cabling.
Specifications
Module Safety Integrity Level:
3108
: SIL-2 (SIL-3 in redundant configuration)
when used with RTP termination assembly and RTP
termination cable
3118
: Non-interfering
Card Address:
Determined by the slot of the controller backplane
Number of channels:
8
Isolation:
Channel to RTP System and Channel to Channel
600 VAC RMS or 400 VDC
Type of protection:
Transformer isolation
Input Signal Ranges:
±10 VDC
Maximum permanent allowed
overload (no damage):
±12.5 Volts for 3099/31
±30 mA for 3099/11
±100 mA for S3099/11
Reading out of guard band:
Reported in error status word.
Common Mode Voltage:
600 VAC RMS or 400 VDC continuous
Common Mode Rejection:
–140 dB at 60 Hz
Common Mode Crosstalk:
–150 dB at 60 Hz
Crosstalk between Channels:
-84 dB DC/AC at 50 Hz
Common Points between Channels: None
Normal Mode Rejection:
3108
: 0 dB at 60 Hz
3118
: -70 dB at 60 Hz
Conversion method:
Successive approximation