Real Time Automation, Inc.
27
1-800-249-1612
BACnet/IP Server Object Configuration
– Analog Objects
Click the
Set Up BACnet Names, Units, and COV
button at the bottom of the BACnet/IP Server
Configuration page to access the Object Configuration page.
When in Auto-Configure Mode, these fields are not configurable.
Follow these steps to customize Analog Inputs or Outputs in Manual Configure Mode:
1)
Select
Analog Input
or
Analog Output
from the upper left dropdown menu.
2)
Select a
Group
to use.
-
T
hese group names are defined on this page under the “Group Name” dropdown menu.
3)
Enter a
Name
to identify this object on the network.
-
The combination of
Group
and
Name
should be unique for each point in the gateway.
4)
Select the
Unit Category
corresponding to the units you want this object to be identified with
(optional). Then select the
Unit
from the dropdown menu.
5)
Set the
COV
(Change of Value) for this object.
-
If the BACnet/IP Client issues a COV-Subscription, the gateway will issue a COV
Notification when the Present-Value changes by more than the given COV-Value. This
value shift can be in a positive or negative direction.