background image

 

Real Time Automation, Inc. 

21 

1-800-249-1612 

 

 

 

 

 

 

Auto-Configure Group by Device vs. Auto-Configure Group by Data 
Type 

There are two different methods for Auto-Configure: Group by Device or Group by Data Type.   

There are a couple of rules to keep in mind when using Auto-Configure Mode: 

1)

 

If the other protocol inside the gateway is a server, slave, or adapter protocol, then there are no 
differences between the Auto-Configure modes. 

Group by Device (Default Method) 

Group by Device goes through the other protocol on the gateway and auto-configures the data groups 
on the Allen-Bradley PLC for all the data p

oints on the other protocol’s first device. After it finishes with 

the first device, it will auto-configure all the points for the second device (if one is configured), and so 
on.   

The data in this method is not optimized- there could potentially be a lot of wasted/unused data space, 

but it will be organized more logically from the master/client’s point of view.

 

Group by Data Type 

Group by Data Type goes through the other protocol on the gateway and auto-configures the data 
groups on the Allen-Bradley PLC for all the data points within the other protocol.   

Another way to view this option is to say that the data points allocated are packed together so there is 
very little wasted data space. The data is packed or optimized. 

Example

:

 

Protocol A is a master/client protocol that has 2 devices with the same setup:

 

Device_1 has 1 integer scan line, 1 float scan line, 1 integer scan line- each for 1 point of data 
Device_2 has 1 integer scan line, 1 float scan line, 1 integer scan line- each for 1 point of data 

Protocol B is a server/slave/adapter protocol that can be mapped as follows: 

Group by Device - 

Protocol B will have 4 scan lines that will look like the following: Scan Line 1 and 2 will 

represent Device_1 and Scan Line 3 and 4 will represent Device_2. 

Scan Line 1 => Type Integer, length of 2 
Scan Line 2 => Type Float, length of 1 
Scan Line 3 => Type Integer, length of 2 
Scan Line 4 => Type Float, length of 1 
 

Group by Data Type - 

Protocol B will have 2 scan lines that will look like the following: Like data types 

from Device_1 and Device_2 will be combined.  

Scan Line 1 => Type Integer, length of 4 
Scan Line 2 => Type Float, length of 2 

 

 

Summary of Contents for 460ETCBMS-NNA4

Page 1: ...Real Time Automation Inc 1 1 800 249 1612 Firmware Version 8 7 22 460ETCBMS NNA4 Protocol Gateway Product User Guide...

Page 2: ...ion or limitation of incidental or consequential damages therefore the limitations set forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect...

Page 3: ...ure Group by Data Type 21 Group by Device Default Method 21 Group by Data Type 21 External PLC Configuration Manual Configure Mode 22 Configuring Read and Write Scan Lines 24 Access Program Scope Tags...

Page 4: ...apping 56 String Mapping 56 Base Triggering Data Validiation Triggering 57 Security Configuration 59 Security Configuration Security Levels 60 Security Log In 61 Security Log Out 61 Email Configuratio...

Page 5: ...Real Time Automation Inc 5 1 800 249 1612 Replacing Configuration Using SD Card 79 Intelligent Reset Button 80 Utilities 81...

Page 6: ...7 4 9 1 20 Features Added 1 BMS BM DFM DS DM TCP USB PBS have been ported to the latest base software 2 TCP BMS BM now Available on N2E and N2EW hardware Platform 3 New ASCII Mode Available on TCP A U...

Page 7: ...nfigure the 460ETCBMS NNA4 gateway For further customization and advanced use please reference the appendices located on the CD or online at http www rtautomation com product 460 gateway support If at...

Page 8: ...h as LEDs For these sections be sure to identify the hardware platform you are using To find which hardware platform you are using 1 Look on the front or back label of the unit for the part number 2 O...

Page 9: ...Real Time Automation Inc 9 1 800 249 1612 Hardware NNA4 Powering the Gateway 1 Connect a 12 24 VDC power source to the gateway Red Wire Black Wire a The unit draws 175mA 12 V...

Page 10: ...Configuration The Port Configuration page is where you set port specific parameters These settings must match the settings of the device s that you are connecting to When you have completed your port...

Page 11: ...under the DIN Rail 3 While pressing the 460ETCBMS NNA4 against the rail press up to engage the spring loaded lower clip and rotate the unit parallel to the DIN Rail 4 Release upward pressure Removing...

Page 12: ...ogram from the CD ROM 3 Find unit under Select a Unit a Change Gateway s IP address to match that of your PC if DHCP has failed i You will know DHCP has failed if the gateway s IP address is AutoIP at...

Page 13: ...fault Gateway 2 The gateway must be on the same Network Subnet as the PC whether it s setup for DHCP or Static Once you have both devices on the same network you should be able to ping the gateway usi...

Page 14: ...ed after every change Multiple changes can be made before a restart but they will not be committed until the gateway is restarted When all desired changes have been made press the Restart Now button T...

Page 15: ...led Configuration cannot be changed during Running Mode If changes are needed click the Configuration Mode button shown in the green box below Configuring Mode Protocol communication is stopped and no...

Page 16: ...ice Configuration The device configuration area is where you assign the device description parameter Changes can only be made when the gateway is in Configuration Mode Once you are done configuring th...

Page 17: ...Once you are done configuring the Network Settings click the Save Parameters button If you are changing the IP Address of the gateway the change will not take effect until the unit has been rebooted...

Page 18: ...ernet port only 1 Delay Between Messages Enter the length of time to delay between read and write scan line requests ms 2 Response Timeout Enter the amount of time the gateway should wait before a tim...

Page 19: ...l Mode will be discarded 1 To add additional PLCs click the Select dropdown under Allen Bradley PLC Device List and select Add Generic PLC option a To remove a device navigate to the server to delete...

Page 20: ...y 32 bit 7 Any String Data Types will be mapped as String If the PLC is a MicroLogix SLC or PLC5E the data will be configured according to the following rules 1 Any 8 Bit Signed Unsigned and 16 Bit Si...

Page 21: ...he other protocol on the gateway and auto configures the data groups on the Allen Bradley PLC for all the data points within the other protocol Another way to view this option is to say that the data...

Page 22: ...r you want to modify the scan line s that already exist 4 To delete the scan lines that are already there and start over press Cancel 5 To add additional PLCs click the Select dropdown under Allen Bra...

Page 23: ...ly maintain a connection when there is data needed to be transferred then Unconnected UCMM will work best if you are only writing to the PLC Connected Class 3 Explicit messaging relies on reserved res...

Page 24: ...e and close the connection until a Change of State Leaving it at Connected messaging once we receive data the RTA gateway will constantly be writing to the PLC to maintain that connection a If you wis...

Page 25: ...to the gateway See the Scan Line Data Limit section at the bottom of the page for the given max values a If using a CompactLogix or ControlLogix below are the scan line data limits b If using a Contr...

Page 26: ...Real Time Automation Inc 26 1 800 249 1612 d If using a SLC 5 05 or PLC5E below are the scan line limits 5 Click the Save Parameters button 6 Repeat for the other direction if needed...

Page 27: ...additional syntax If you are using a tag that is defined within Program Scope then the tag name inside of the RTA gateway needs additional syntax for it to successfully communicate Example AnotherTag...

Page 28: ...ore setting the Handshake value equal to Trigger value How does this work 1 Read ETC Optimized Trigger tag until Change of State a Value 0 Enabled but Not valid value b Value 65535 Disabled 2 Map the...

Page 29: ...date the RTA_Opt_Trigger PLC tag to 1 7 Now your ASCII device will be updated with the data 8 Increment the RTA_Opt_Trigger PLC tag 9 Your ASCII device will get update again regardless if data is new...

Page 30: ...te Scan line that updates the PLC with the Handshake from the RTAgateway Handshake tag can be unique to your PLC program 3 Within the ETC configuration setup a PLC tag that you can identify as your Op...

Page 31: ...date your Read Scan Line tag with new data 12 Increment the RTA_Opt_Trigger PLC tag again 13 Now your ASCII device will be updated with the new data 14 In a working application the Handshake tag in yo...

Page 32: ...ter than the largest MAC ID on the MS TP network 5 Enter a unique Instance identifier for the gateway This value must be unique across the BACnet network 6 Inactivity Timeout Enter the amount of time...

Page 33: ...Data Type Default 2 Manual Configure Mode NOTE You may go back and forth between modes but when reverting from Manual Configure Mode to Auto Configure Mode all changes made in Manual Configure Mode wi...

Page 34: ...Float data will be mapped as Analog Objects 2 Any Coils or 1 8 16 32 Bit Binary Packs will be mapped as Binary Objects 3 Any String Data Types will be mapped as CharacterString Value Objects 4 The in...

Page 35: ...object properties includes any default object names units and COV that are already configured press OK You would want this option if you are adding additional data groups or you want to modify the da...

Page 36: ...r slave devices the RTA gateway is monitoring and sending over to the Build Automation System BAS to monitor you can configure the group to represent each device The image above displays 1 device if t...

Page 37: ...onfigure Mode these fields are not configurable You MUST be in Manual Configure Mode Follow these steps to configure binary inputs or outputs in Manual Configure Mode 1 Select Binary Input or Binary O...

Page 38: ...these fields are not configurable You MUST be in Manual Configure Mode Follow these steps to configure CharacterString value reads or writes in Manual Configure Mode 1 Select CharacterString Value Re...

Page 39: ...le The Group Name is designed to be used when there are multiple BACnet objects that have the same name This is useful when you have multiple identical devices connected on the other protocol Follow t...

Page 40: ...eway will automatically take the string data type from one protocol and map it into the other See String Auto Configure section for more details Option 3 Manual Configure Mappings If you don t want to...

Page 41: ...isplay Data button to view how the data is mapped and what the values of each mapping are Here you will see how each data point excluding strings is mapped To view select the device from the dropdown...

Page 42: ...3 on BACnet NOTE If a data point is mapped twice only the first instance of it will show here EX If Modbus 400001 400040 from Slave 1 are both mapped to AI1 only 400001 will show as being mapped to AI...

Page 43: ...iew the actual data mappings click the Edit Mapping button For more details see the Data Mapping Explanation section To view the data mappings purely as text click the View as Text button For more det...

Page 44: ...ps from a string click the dropdown menu to generate the information regarding that device The string data will be displayed in both Hex and ASCII only the ASCII data is sent The example below shows d...

Page 45: ...Info drop down and navigating to ASCII Diagnostics page You will also have to select the port you want to view in the dropdown below ASCII To view the string mappings click the Edit Mapping button Fo...

Page 46: ...on would look like my example below There are more detailed examples of what all the fields represent in the ASCII Parsing section The message is broken up into 3 Groups or Parsing fields To view the...

Page 47: ...ata type If the Auto Configure function does not map the data as you want or you want to add modify the mappings you may do so by going into Manual Configure mode The following are examples of the Aut...

Page 48: ...then only 1 operation is allowed c Select the Operation s to perform i Math Operations are performed in the order they are selected ii If more than one point is selected on the source the Math Operat...

Page 49: ...ase In this example Ram0 is scaled into Ram1 Ram1 is then increased by 5 and stored into Ram2 Ram0 and Ram2 could be considered a source or destination group 2 Temporary Ram Double a This is like the...

Page 50: ...ys to map the NetBmpStat Option 1 Map the whole 32bit value to a destination Example below shows the NetBmpStat is going to an Analog BACnet object Using a connection of 5 Modbus Slave devices AI1 wil...

Page 51: ...ult 0x80 7 128 nonrecoverable fault For this example the ETC Status is mapped to a PLC tag called PLC_Status Example ETC Status is 0x00000013 19 decimal here is the break down Hex Bit Decimal Explanat...

Page 52: ...e fault config err 0x10 28 268 435 456 Configuration Mode 0x20 29 536 870 912 No Ethernet Cable Plugged In For this example the MC Status is mapped to a PLC tag called MC_Status Example MC Status is 0...

Page 53: ...string 1 Enable red box above Check to enable mapping If not checked this mapping is skipped 2 Source Field yellow box above a Group Select the string data group you set up in the protocol config to...

Page 54: ...ual Configure Mode or click Cancel to remain in Auto Configure Mappings Mode Once OK is clicked there are 2 options on how to proceed from here 1 To keep the mappings that are already configured press...

Page 55: ...op of the Mapping Configuration page and select Auto Configure Mappings Click OK to proceed to delete all current mappings and go back to Auto Configure Mappings Mode Click Cancel to keep all mappings...

Page 56: ...at register 1 and want to see if 400011 is mapped If it is not in this text box then it is not mapped and no data will be transferred This is the text display for the example shown under the Data Mapp...

Page 57: ...ake value is set equal to Trigger value 5 Map Handshake to reference data point Note is an internal reference to the Server Slave number you are settings up ex RTA Server Slave products can only be Tr...

Page 58: ...ppings 4 The first mapping is going to be the Data Validation Triggering AO21 will write to the RTA MC Trigger 1 will mark data invalid 5 The second mapping the MC Handshake will increment that all da...

Page 59: ...ax of 32 characters case sensitive a Re enter the Password 4 E mail In case the password was forgotten a user can have their password e mailed to them if e mail was configured 5 Hint A helpful reminde...

Page 60: ...can have a separate security level associated with it for each user Security Levels 1 Full Access Capability to view and configure a web page 2 View Access Capability to view a web page but cannot co...

Page 61: ...word This is used to reset security settings Confirm reset password must be selected to confirm this action Once confirmed there is a 15 minute window to do a hard reset of the gateway by physically r...

Page 62: ...use 2 SMTP Mail Password If authentication is required enter the SMTP Server s password Optional 3 SMTP Server Enter the Name of the SMTP Server or the IP Address of the Server 4 From E mail Enter th...

Page 63: ...ction a Top dropdown select the Data Group This dropdown menu will contain all groups that go from the gateway to the network b Lower dropdown select the Data Point s Specific Point This is used to se...

Page 64: ...he Clear Error Value Ex Ticks Since Powerup 5000 This will clear the alarm after 5000 ticks have elapsed since the unit powered up 6 Enter an Alarm Name This will make the alarm unique and will be ava...

Page 65: ...m 7 Status The current status of the alarm either OK or ALARM 8 of Times Active This count represents the number of times this alarm has become active If an alarm is triggered this count will incremen...

Page 66: ...hen an alarm is cleared the following will occur 1 A one time notification will be sent to the email associated with the alarm a For duplicate emails to occur the alarm must become active and then be...

Page 67: ...his is to be used to prevent jitter Default value is 0ms This timer takes priority over the Stale Data Timer There is a separate timer per data mapping This timer is active only after the first write...

Page 68: ...larm that was active Common Errors 1 Destination or Source Point does not exist a Solution Re map the mapping 2 Source or Destination Pointer too small a There is not enough space on either the Source...

Page 69: ...lear All Values This will only affect displayed values 1 This will reset all displayed values back to zero and clear the Status Strings Example If viewing Allen Bradley PLC ETC01 10 1 100 18 this will...

Page 70: ...ng connection can be determined from the Network Bitmap Status value 4 Communication not attempted yet Flashing Red Specific Server Only No reads are configured and data needed for writes isn t valid...

Page 71: ...C to the gateway Common Error Strings These are the values for All PLCs or the specific PLC selected 1 IP xxx xxx xxx xxx tagname 04 Path Segment Error The tag name is wrong or the tag is not defined...

Page 72: ...d The gateway is connected to a BACnet MS TP master 2 Not Connected The gateway is not connected to a BACnet MS TP master 3 Error Timeout If the Inactivity Timeout is set to non zero the gateway has n...

Page 73: ...ter 7 Read Property Response Sent Number of Read Property responses sent to the BACnet MS TP master 8 Read Multiple Property Response Sent Number of Read Property Multiple responses sent to the BACnet...

Page 74: ...format the message how the gateway is expecting d Parameter Out of Range The BACnet MS TP master is asking for information outside of the gateway s defined range 4 BMS Message Error XXXXX The gateway...

Page 75: ...not had previous communication with on the network l Timeout BACnet MS TP message timed out m Resources busy BACnet MS TP message cannot be processed right now n Segmentation not supported BACnet MS...

Page 76: ...col is a master client you may set the LED to represent either all slaves servers configured in the gateway or a slave server device To select a slave server device 1 Select the protocol in the left d...

Page 77: ...her device into the 460 gateway whenever it is in Configuration Mode Upon clicking the Choose File button you will be prompted to select a location from which to load the saved file Once the location...

Page 78: ...tered an error while trying to load the saved configuration the gateway will indicate the first error it found and a brief description about it under the Load Configuration button Contact RTA Support...

Page 79: ...y you wish to copy the configuration from 2 Power up the gateway you wish to copy the configuration to DO NOT INSERT SD CARD YET 3 Navigate to the webpage inside the unit 4 Navigate to the dropdown Ot...

Page 80: ...on the hardware 1 On the side of the gateway with the SD card slot there is a small pinhole Using a paperclip press the button through this pinhole and hold the button for at least 5 seconds 2 After...

Page 81: ...tored in the Flash File System within the gateway Identify your device by clicking the Start Flashing LEDs button By clicking this button the two diagnostic LEDs will flash red and green Once you have...

Reviews: