Real Time Automation, Inc.
72
1-800-249-1612
a)
“Buffer Overflow” –
The BACnet/IP client is asking for too much information in a single message.
b)
“Invalid ADPU” –
The gateway is not able to process the message, try again later.
c)
“Preempted by Higher Priority” –
The BACnet/IP client message has aborted due to a higher
priority task, try again later.
d)
“Segmentation Not Supported” –
The gateway does not support segmentation. Break up the
client request into multiple requests.
3)
BS: Message Reject - The gateway rejected a message due to one of the common reasons below:
a)
“Buffer Overflow” –
The BACnet/IP client is asking for too much information in a single message.
b)
“Invalid Parameter Data Type” –
This BACnet/IP data type is not supported.
c)
“Invalid Tag” –
BACnet/IP message is not how the gateway expects the message.
d)
“Parameter Out of Range” –
The BACnet/IP client is asking for information outside of the
gateway's defined range.
4)
BS: Message Error “XXXXX” –
The gateway is sending an error a message due to the listed
explanation:
a)
“Inconsistent parameters” –
i)
BACnet/IP client tried to write a priority that was out of range or reserved (Priority 6) and
was rejected.
ii)
BACnet/IP client tried to write to ALL, REQUIRED, or OPTIONAL object property.
b)
“Invalid Data Type” –
BACnet/IP client tried to use a data type with an object that is not
supported.
c)
“Service request denied” –
BACnet/IP request cannot be processed because the BACnet/IP
connection is not established.
d)
“Read access denied” –
BACnet/IP read request cannot be processed.
e)
“Unknown object” –
BACnet/IP client tried to access an object our gateway does not support.
f)
“Unknown property” –
BACnet/IP client tried to access a property our gateway does not support
for that object type.
g)
“Unsupported object type” –
BACnet/IP client tried to access an object type our gateway does
not support.
h)
“Value out of range” –
BACnet/IP message could not be completed because the passed value
was not in the valid range.
i)
“Write access denied” –
BACnet/IP client tried to write a non-writeable property in our gateway.
j)
“Invalid array index” –
i)
BACnet/IP client tried to write a priority that was out of range or reserved (Priority 6) and
was rejected.
ii)
BACnet/IP client tried to write an arr
ay for an object or property that doesn’t have an array
index.
k)
“Unknown device” –
Gateway is trying to send a message to a device we have not had previous
communication with on the network.
l)
“Timeout” –
BACnet/IP message timed out.
m)
“Resources busy” –
BACnet/IP message cannot be processed right now.
n)
“Segmentation not supported” –
BACnet/IP message is too large to send in one message.
o)
“Service not supported” –
BACnet/IP client tried to perform a service that the gateway does not
support.
p)
“Abort Other” –
BACnet/IP message is aborted for an unknown reason.
q)
“Invalid Tag” –
BACnet/IP message is not how we expect.
r)
“Unknown” –
BACnet/IP message error for an unknown reason.