Real Time Automation, Inc.
19
1-800-249-1612
BACnet/IP Server Configuration
Click the
BACnet/IP Server
button to access the primary configuration page for this device.
1)
Select which
Network Interface
to use for this BACnet/IP connection. If using single port
hardware, the Network Interface will default to Ethernet Port only.
2)
Enter a
Device Label
. This is an internal device alias used during data mapping.
3)
Enter the decimal value of the
UDP Port
that the gateway will communicate on. Default is 47808
(0xBAC0).
4)
Enter a unique
Instance
identifier for the gateway. This value must be unique on the BACnet/IP
network.
5)
Inactivity Timeout
: Enter the amount of time, in milliseconds, the gateway should wait before a
timeout state is declared. If the BACnet/IP client does not initiate communication within this
time frame the BACnet/IP LED will flash red and the timeout counter will increment. Enter zero
to disable this feature.
6)
Enter a
Name
,
Description
and
Location
for the gateway. These are used to identify the gateway
on the BACnet/IP network.
7)
Bit Pack
: Select the formatting of the binary input/output. Automap will use this packing size to
map binary objects to/from the other protocol.