MEMS Digital In-Place Inclinometer System 

Quick Start Up Guide 

 
 

ICM0095B 

RST Instruments Ltd. 

14 

 

5.3 

CR310

 

W

IRING

 

To connect an IPI system to a CR310 Campbell logger, an RS485 to RS232 
i

nterface, such as RST’s ELGL4000 series, will need to be used. The interface/IPI 

assembly can be wired as follows (Figure 5-8): 

 

F

IGURE 

5-8

  

W

IRING SCHEMATIC FOR AN 

IPI

 SYSTEM TO THE 

CR310

 USING 

RS232

 

DB9

 CONNECTOR

 

In the event that the C1 and C2 ports are vacant, the C1 and C2 ports can be used 
in place of the DB9 port. See the wiring diagram outlined in Figure 5-9. 

 

 

F

IGURE 

5-9

  

W

IRING SCHEMATIC FOR AN 

IPI

 SYSTEM TO THE 

CR310

 LOGGER USING 

C1

 AND 

C2 

5.3.1 

Updating the Modbus Addresses With a CR310 

 

 

Before updating the Modbus addresses on the IPI string, ensure that all settings 
have been saved on the logger unit.  

Modbus addresses for sensors connected to a Campbell CR310 logger can be 
updated via a CRBasic code. Once the user has defined the number of sensors 
and their respective serial numbers, the code will automatically assign a Modbus 
address to each sensor in the string once the code is run.  

1.  Open LoggerNet. 

2. 

Navigate to the “CRBasic Editor” option under the 

Program

 menu (Figure 5-2). 

NOTE:

 

 

A

RS485

 TO 

RS232

 INTERFACE MUST BE USED WHEN UPDATING THE 

M

ODBUS ADDRESSES WITH A 

CR310

 LOGGER

.

 

Summary of Contents for MEMS IPI 4

Page 1: ...his document RST Instruments Ltd reserves the right to change the information at any time and assumes no liability for its accuracy Copyright 2020 RST Instruments Ltd All rights reserved Document Numb...

Page 2: ...ICM0095B RST Instruments Ltd Page i REVISION HISTORY Rev Revision History Date Prepared By Approved By A Initial release 2020 Nov 13 MP BN B Added instructions for Campbell CR6 and CR310 loggers DT L...

Page 3: ...R QUICK START UP INSTRUCTIONS 9 5 1 Hardware Requirements 9 5 2 CR6 Wiring 10 5 2 1 Updating the Modbus Addresses With a CR6 10 5 2 2 Code for CR6 12 5 3 CR310 Wiring 14 5 3 1 Updating the Modbus Addr...

Page 4: ...ger using C1 and C2 14 Figure 5 10 Select CRBasic editor under the Program menu 15 Figure 5 11 CR300 Series Program icon 15 Figure 5 12 Compiling and saving the code in the CRBasic editor 16 Figure 5...

Page 5: ...To ensure that all components are working together correctly and able to communicate RST recommends that initial set up and configuration take place in the office or warehouse prior to final installa...

Page 6: ...of each sensor and its order in the string from the top to the bottom of the string Connect the IPI string to the desired data logger following the wiring scheme outlined in Table 2 1 CAUTION IT IS C...

Page 7: ...ehouse installation in the field will be straightforward See ICM0062 for detailed instructions 2 2 1 Cleaning Connectors Keep caps on connectors Figure 2 3 until mated to the next sensor to prevent co...

Page 8: ...RE DT2485 logger or Campbell Logger o PC with LoggerNet and o RST ELGL4000 Interface if using CR310 3 2 PC HARDWARE Desktop or laptop with Intel or AMD processor USB port 3 3 WINDOWS HOST OPERATING SY...

Page 9: ...sion The current version can be downloaded from https rstinstruments com resources software Navigate to the site and select the appropriate data logger 2 Follow the on screen instructions to install t...

Page 10: ...Once the software connects to the logger the port and status indicators will turn green and the Status screen should display logger information 3 Navigate to the DTBus tab to configure the IPI sensors...

Page 11: ...o the string Insert a sensor to the current position in the string Change communication between ASCII and Modbus Remove the currently displayed sensor from the string or remove all sensors Add specifi...

Page 12: ...the Upload to Logger button to apply the changes Click Yes when asked to update Modbus Addresses 6 Wait for update process to finish The logger is now logging data 7 If desired real time sensor readi...

Page 13: ...ile csv will automatically be created in the data directory The default data directory is My Documents Multichannel 3 Before downloading the program will ask whether you would like to erase the existi...

Page 14: ...ses on the IPI string ensure that all settings have been saved on the logger unit Modbus addresses for sensors connected to a Campbell CR6 logger can be updated via a CRBasic code Once the user has de...

Page 15: ...will depend on the type of logger that will be used 6 Update the number of IPIs and the serial number of each IPI in the code in order of installation or planned installation 7 Compile the code and th...

Page 16: ...l LoggerNet instructions for ensuring current settings have been saved 12 Select Send New on the right hand side of the screen and open the saved CRBasic code from Step 7 13 Click on Start Running 14...

Page 17: ...nsors per string EndTable Main Program BeginProg Open serial port SerialOpen ComC1 9600 0 0 128 4 SerialFlush ComC1 Guard against serial number error causing incorrect data SerialOut ComC1 65534 MBA 2...

Page 18: ...gure 5 9 FIGURE 5 9 WIRING SCHEMATIC FOR AN IPI SYSTEM TO THE CR310 LOGGER USING C1 AND C2 5 3 1 Updating the Modbus Addresses With a CR310 Before updating the Modbus addresses on the IPI string ensur...

Page 19: ...Ensure that any existing settings have been saved 5 Remove the template code and paste the code see Section 5 3 2 into the editor The appropriate code will depend on the type of logger that will be u...

Page 20: ...COMPILING AND SAVING THE CODE IN THE CRBASIC EDITOR 8 If the compilation was successful the following message will appear at the bottom of the window FIGURE 5 13 SUCCESSFUL COMPILATION MESSAGE 9 Close...

Page 21: ...ct Send New on the right hand side of the screen and open the saved CRBasic code from Step 7 13 Click on Start Running 14 The Modbus addresses for the sensors on the IPI string will now be updated 5 3...

Page 22: ...in interface banner set mode on program run continuous reading mode SerialOut Com1 MODE 0 CHR 13 1 0 SerialIn interface_banner Com1 200 CHR 13 100 Delay 0 1 Sec SerialFlush Com1 Guard against serial n...

Page 23: ...nts Ltd 19 6 INSTALLATION Refer to the MEMS Digital In Place Inclinometer System Instruction Manual ICM0062 for detailed installation instructions 7 SERVICE AND REPAIR This product contains no user se...

Reviews: