RS PRO IRT 1900 Instruction Manual Download Page 9

 

EN-7 

b).  Before  pressing  the  test  button,  always  check  the 

mains status LED’s for the following sequence : 

P-E Green LED must be NO 

P-N Green LED must be NO 

       Red LED must be OFF 

If the above sequence is not displayed or the Red LED 
is ON for any reason, do not proceed as there may be 
incorrect  wiring.  The cause must be rectified before 
proceeding. 

c). If other loads are connected to the test circuit, these 

may  cause  erroneous  readings.    To  make  the  most 
accurate  readings,  loads  on  the  circuit  should  be 
disconnected. 

d). Use only the leads supplied with instrument. 

 

5-2 Preparation : 

a). Connect the instrument to the circuit to be tested (see 

following  sections  for  procedure).    Make  sure  the 
LED’s are lit as per the initial checks. 

b). If the sequence is not correct, disconnect the 

instrument and check the installation wiring for a 
possible fault. 

 

Summary of Contents for IRT 1900

Page 1: ...Instruction Manual IRT 1900 Digital RCD Tester FR EN IT DE ES TEST 0 180 X1 2 X1 X5...

Page 2: ...f Parts and Positions 4 4 2 LCD Display 5 4 3 Connections For RCD Testing 6 V OPERATING INSTRUCTIONS 6 5 1 Warning initial checks to be carried out before any testing 6 5 2 Preparation 7 5 3 Testing 8...

Page 3: ...tions rated at 230V AC 10 Under No circumstances must it be connected to higher voltage or phase to phase Never open the instrument case There are no user serviceable parts inside If the unit does not...

Page 4: ...Resilient case protects against everyday knocks 0 and 180 degree phase angle switch permits quick tests and consistent readings III SPECIFICATION Test current range 10 20 30 100 300 500 mA Test curren...

Page 5: ...IEC Test Lead External Earth Probe Environmental Conditions The product is designed for indoor use and up to a maximum altitude of 2000m Installation Category 300V CAT III single phase 230V Pollution...

Page 6: ...roceed test button 3 Phase angle select button 4 x 1 2 x 1 x 5 test current factor select button 5 x 1 2 x 1 x 5 test current factor select button 6 Trip current settings 7 Wiring indication 8 Storage...

Page 7: ...ion 3 x 1 2 test current factor indication 4 x 1 test current factor indication 5 x 5 test current factor indication 6 0 180 phase angle indication 7 180 360 angle indication 8 Analog indication 9 Dis...

Page 8: ...0 100 P N V OPERATING INSTRUCTIONS To ensure safe and proper use of this instrument the following instruction must be followed 5 1 Warning initial checks to be carried out before any testing a Always...

Page 9: ...rectified before proceeding c If other loads are connected to the test circuit these may cause erroneous readings To make the most accurate readings loads on the circuit should be disconnected d Use o...

Page 10: ...nctioning correctly and OL will be displayed d While the test is being conducted the units displayed will be ms for milliseconds e If the Press to Test button is released the result will be displayed...

Page 11: ...tch again Press the Press to Test button the breaker should trip e The readings obtained in 5 4 d and 5 4 c should both be within the trip time specified for the breaker at its rated tripping current...

Page 12: ...tch to the 180 position and press the Test button g The trip times of the last two measurements should both be less than 40 ms If the tripping times are greater than 40 ms the RCD may be faulty and mu...

Reviews: