CF Auto-loading
Not used
Terminal resistance of MJ2 (modular jack 2)
RD terminal resistance of pin No.24 and 25 of CN1
Terminal resistance of MJ1 (modular jack 1)
SD terminal resistance of pin No.12 and 13 of CN1
*1
Setting of DIP Switches
Setting of dip switches is as follows. (The following
fi
gure shows the condition when the panel is unpacked.)
When setting DIP switch, turn the power off.
DIPSW 1 (CF Auto-loading)
Please refer to "Reference Manual (Function)."
DIPSW 2, 3 and 4 (not used)
Keep OFF.
DIPSW 5, 6, 7, 8 (Setting of Terminal Resistance)
Set DIPSW 7 ON in the case of connecting V7+ to PLC by RS-422/485 (Two-wire system).
Set DIPSW 5
*1
, 7 ON in the case of connecting V7+ to PLC by RS-422/485 (Four-wire system).
Set DIPSW 6 or DIPSW 8 when using MJ1 or MJ2 with the following connection.
- Master station of Multi-Link2
- Temperature control network/PLC2Way
- Card recorder: CREC
- Serial extension I/O: V-I/O
- V-Link: RS-485, the last V7+ station only.
*1 It will be supported from the hardware version "b." The hardware version is indicated on the right of
"Ser No" on the back of the unit.