6.2 Requirements for the installation location
Prior to beginning the assembly work, make sure
the measures for establishing and securing a de-
energised state at the workplace have been car-
ried out.
The following activities have been completed:
n
The pole for assembling the TracFeed
®
SFA have been
installed.
n
Mast disconnectors and connecting rods have been installed.
6.3 Assembly preparation
To attach the TracFeed
®
SFA to poles or (tunnel) walls, you require
retaining brackets for offset mounting in order to connect the force-
displacement transmission device that needs to be connected to
the back.
Corresponding retaining brackets are available for
different pole types as accessories from Rail
Power Systems GmbH customer service.
NOTICE!
Property damage from excessively long bolts!
If the bolts chosen are too long, there is a risk of
property damage to the components of the Trac-
Feed
®
SFA.
–
Do not screw in bolts deeper than 17 mm.
–
Do not forcibly screw in bolts deeper than flush
with the base plate.
Assembly
Assembly preparation
14.09.2022
TracFeed
®
SFA Electromechanical remote motor drive
40