Section I :: User
19
I SECTION I :: USER
I.1
MACHINE DESCRIPTION
I.1.1 DECLARED CONDITIONS OF USE
MCAEBY are air cooled condensing. Range is equipped with axial fans.
Use is expected to civil air-conditioning systems, and the correct
operation of the unit is subject to the strict observance of the operating
instructions in respect of the technical spaces in the installation and
operating limits specified in this manual. The machine is designed for
outdoor installation.
DANGER!
The machine is designed for outdoor installation.
Segregate the unit if installed in areas accessible to
persons under 14 years of age.
DANGER!
Do not introduce pointed objects through the air
flow and intake grilles.
IMPORTANT!
The unit will function correctly only if the
instructions for use are scrupulously followed, if
the specified clearances are complied with during
installation, as well as the use restrictions indicated
in this manual.
IMPORTANT!
If clearance distances are not maintained at
installation, it could cause malfunctioning with an
increase in absorbed power and a considerable
reduction in cooling capacity.
DANGER!
Be careful of hot surfaces inside the machine
I.1.2 MACHINE IDENTIFICATION
The units feature a serial number plate located on the side which
includes machine identification data.1).
MATRICOLA
MODELLO
Alimentazione
V / ph / Hz
Potenza ass.
kW
Corrente max.
A
Corrente di spunto
A
Grado di protez.
IP
Tipo fluido frig.
Carica fluido frig.
kg
Carica olio
kg
Press. Diff. Olio
kPa
Press. Max. gas
kPa
Press. Min. gas
kPa
Press. Max. H
2
O
kPa
Fig. 1
I.1.3 STRUCTURAL FEATURES
Load-bearing structure and panels in galvanised and RAL 9018 painted
sheet metal; galvanised steel sheet metal base, soundproofed
compressor compartment.
N° 1 Hermetic Scroll-type compressor with thermal protection.
Air side exchanger composed of coil with copper pipes and aluminium
fins, complete with protection grille.
Electric fans axial fans with external rotor, equipped with internal
thermal protection and complete with protection and electronic speed
control.
Refrigerant circuit in annealed copper pipe (EN 12735-1-2) complete
with: drier filter, Load connections, safety pressure switch with manual
reset on the high pressure side, conveyable safety valves, pressure
switch with automatic reset to control the pressure on the low side.
Crankcase heater, Liquid humidity indicator, thermostatic expansion
valve, reverse cycle valve, receiver of liquid and gas separator and
check valves, taps with flare.
Unit complete with:
canalizable condensate discharge
Ecological R410A refrigerant fluid load.
I.1.4 ELECTRICAL CONTROL BOARD
Electrical panel accessible by removing the front panel, conforming to
IEC standards, equipped with opening and closing using the
appropriate tool.
Complete with:
electrical wiring arranged for power supply
400V-3ph+N-50Hz;
auxiliary circuit power supply 230V-1ph-50Hz derived from main
power supply;
isolator, complete with door lock safety device;
three-pole circuit breaker to protection of the compressor;
fuse for the fan and the auxiliary circuit;
controller phase sequence / phase loss;
power contactor;
user interface terminal board;
removable machine control.
The electronic control card is managed by the keyboard inserted in the
machine. This electronic board performs the following functions:
management of safety delays; functions that control the working
interventions of the unit devices;
complete protection of the unit, possible shutdown and display of all
the triggered alarms;
display of operating devices by LED; of the heat pump;
self-diagnosis with continuous monitoring of the unit functioning
status.
Advanced functions:
arranged for serial connection, with RS485 outlet for logical dialogue
with building automation, centralized systems and supervision
networks;
check-up and monitoring of scheduled maintenance status;
computer-assisted unit testing.
I.1.5 FUNCTIONING LIMITS R410A
Cooling cycle:
B.S. Temperature inlet air to the heat exchanger:
20°C ÷ 43°C for
REV
;
I.1.6
SAFETY INFORMATION
DANGER!
Always install a general automatic switch in a
protected area near the machine, which has a
characteristic delayed curve, sufficient capacity and
breaking power. There must be a minimum distance
of 3 mm between the contacts.
Earth connection is compulsory by law to ensure
user safety while the machine is in use.
DANGER!
Connections must be made in compliance with
current standards and with the diagrams provided
with the machine.
The safety door interlock automatically prevents electric power being
fed to the unit if the cover panel over the electrical panel is opened.
I.1.7 INFORMATION REGARDING UNINTENDED
USE
DANGER!
The machine was designed and built solely to
function as reversible condensing with
condensation / evaporation air; any other use other
than this is Expressly Forbidden. Installing the
machine in an explosive environment is prohibited.