Smart Positioner
YT-2700
Product Manual
Ver. 1.18
26
5.2
Connection
Fig. 5-1: Terminal Overview
5.3
Ground
1. Ground must be done before operating the positioner.
2. There are two ground bolts on the positioner. An internal ground is
“F.G” of the terminal on the
PCB. An external ground bolt is located next to the conduit entry. Please make sure that the
resistance is less than 100 ohm.
AO:
Analog Output
AI:
Analog Input
Vs:
Voltage Source
R
L
:
Load Resistance
IN +:
Input Signal (+)
IN -:
Input Signal (-)
F.G :
Frame Ground
OUT+: Feedback Signal (+)
OUT-:
Feedback Signal (-)
Summary of Contents for YT-2700
Page 1: ...SMART POSITIONER PRODUCT MANUAL YT 2700 Rotork YTC Limited VERSION 1 18 ...
Page 11: ...Smart Positioner YT 2700 Product Manual Ver 1 18 11 2 8 Product Dimension Fig 2 2 YT 2700L ...
Page 12: ...Smart Positioner YT 2700 Product Manual Ver 1 18 12 Fig 2 3 YT 2700R Fork lever type ...
Page 13: ...Smart Positioner YT 2700 Product Manual Ver 1 18 13 Fig 2 4 YT 2700R Namur Type ...