![rotork YT-2500 Series Product Manual Download Page 46](http://html1.mh-extra.com/html/rotork/yt-2500-series/yt-2500-series_product-manual_1491816046.webp)
Smart Positioner
YT-2500 / 2550 / 2501 Series
Product Manual
Ver. 1.34
46
9.6.3
D1 Value (Kd1)
D value indicates the derivative value of the compensation signal based on the percentage of error
allowance. As the value increase, it is more likely to have hunting. As the value decreases, it can
have poor linearity or dynamic characteristic. but these values are applicable for only when input signal
is increasing.
<ENTER>
→
<ENTER>
→
<UP>/<DOWN>
<ENTER>
→
Press <UP> or
<DOWN> button
if the above is not
displayed.
<ESC>
3 times
→
9.6.4
P2 (KP2) and D2 (Kd2) values
P2 and D2 values
’
principles are same as P1 and D1, but these values are applicable for only when
input signal is decreasing.
9.6.5
P_ (KP_) and D_ (Kd_) Values
P_ and D_ values’ principles are same as P and D values, but these values will be activated when the
error percentage of the actual stroke per input signal reaches within 1%.
9.6.6
PT1 (PT1) and PT2 (PT2) Values
PT value indicates the minimum time duration(unit: 0.1mSec) of internal signal controlling pilot valve.
PT1 is for increased input signal, and PT2 is for decreased input signal’s PT values.
<ENTER>
→
<ENTER>
→
<UP>/<DOWN>
<ENTER>
→
Press <UP> or
<DOWN> button
if the above is not
displayed.
68 means 6.8mSec
<ESC>
3 times
→