48
Installation & Maintenance
Instructions
11.0 Advanced Menu
UPS
11.2.12 UPS - Reserve Power Pack Configuration
The Reserve Power pack consists of an super capacitor pack that
can be configured to carry out an action on the loss of power.
LOP AC - Loss of Power Action
Action to be taken on Power Loss:
OPN
- Run to the configured OPEN limit
SPT
- Stayput, remain at current position
CLS
- Run to the configured CLOSE limit
POS
- Run to configured position (See LOP PO)
DIS
- Action disabled
LOP PO - Loss of Power Position
When LOC AC is set to POS the actuator will run to its
configured loss of power position. Can be set between 0 to
100% of travel.
LOP TO - Loss of Power Timeout
On loss of power the LOC AC action can be delayed.
Timeout can be set between 0 to 5 seconds.
LOP SP - Loss of Power Speed
The speed at which the actuator will travel when executing
the LOC AC operation. Can be set between 50 to 100% of its
Rated speed.
OR REM - Override Remote Control Mode
OFF
- Actuator will respond to the command inputs
when selected for remote operation and the RPP is
active.
ON
- The LOP AC action will override the Remote
command inputs.
OR LOC - Override Local Control Mode
OFF
- Local open and close operation enabled
whilst RPP is active.
ON
- The LOP AC action will override Local operation.
OR LST - Override Local Stop mode
OFF
- Local Stop mode has priority over all control
modes.
ON
- The LOP AC action will override Local stop mode.
RESERVE POWER PACK CONFIGURATION
LOP AC - Loss of Power Action
LOP PO - Loss of Power Position
LOP TO - Loss of Power Timeout
LOP SP - Loss of Power Speed
OR REM - Override Remote Control Mode
OR LOC - Override Local Control Mode
OR LST - Override Local Stop Mode
SPEED
CPT 20
CPT 4
INTTIM
ADVANC
INFO
ST ACT
AMP ST
TEMP
SW VER
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust Display or
Ouput Torque
LOCREM
Local / Remote Operation
MANJOG
Manual Jog
TORQ/THRSTC
Close Torque/Thrust
TORQ/THRSTO
Open Torque/Thrust
CL ACT
Close Action
OP ACT
Open Action
BASIC
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
CTRCFG
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LO
LOS HI
ACTCFG
RELAYS
R1 CFG
R1 FRM
R2 CFG
R2 POS
ACTTYP
ACTSIZ
ENCINI
SPLTRG
MINCMD
MAXCMD
BSRACT
ASRACT
ASPOS
BSRPOS
UPS
LOP AC
LOP PO
LOP TO
OR REM
OR LOC
OR LST
LOP SP
DEFLTS
LD CUST
ST CUST
LD FACT
R2 FRM
R1 POS
R5 CFG
R5 FRM
R6 CFG
R6 POS
R6 FRM
R5 POS
R7 CFG
R7 FRM
R8 CFG
R8 POS
R8 FRM
R7 POS
COMMS
MODBUS
PROFIBUS
PAKSCAN
HART
FFBUS
COM TO
LOS ACT
LOS PO
MIN SP
MAX SP
D1 CFG
D2 CFG
D2 FRM
D3 CFG
D3 FRM
D4 CFG
D4 FRM
D1 FRM
DIG IN
PRM OC
Primary Option
RI CTL
Remote Control Inputs
2W PRI
2 Wire Priority
LOS AC
RIRO Only
LOS PO
RIRO Only
ESDACT
ESD Action
ESDOLS
ESD Override Local Stop
KNBMNT
Local Maint
CMDSRC
CMD SRCE
INFO
RELAYS
DIG IN
SPLTRG
ACT CFG
UPS
COMMS
CTRCFG
Control Setup
CMDSRC
STL TO
TURNS***
OP DIR***
INTTIM
CL TIE
ST CLS
SP OPN
CL OFF
ST OPN
SP CLS
OP ON
OP OFF
CL ON
OP TIE
ACTCFG
11.2.11 ACTCFG - Actuator Configuration
ACTTYP
-
Actuator Type
AT QT
-
Quarter-turn Unit
AT ROT
-
Rotary Unit
AT LIN
-
Linear Unit
This setting must match the configuration of the unit to
ensure correct operation.
ACTSIZ
-
Actuator Size
This parameter matches the Thrust
characteristic of the actuator model.
For example CML-1500 lbf.
This setting must match the configuration of the unit to
ensure correct operation.
CAUTION
ENCINI - Encoder Initiation
This procedure is only necessary after replacement of
electronics assemblies or disassembly of the actuator drive
system. The Encoder
MUST
be re-initialised before electrical
operation.
This procedure will invalidate the current travel limit
settings. The travel limits MUST be reset before putting
the actuator back in to service.
Select the ENCINI menu and enter the Edit mode.
Use the UP or DOWN pushbuttons to move the actuator to
the centre position of travel.
Press ENTER to Re-Initialise the Encoder.
The travel Limits must now be Reset and any characterisation
parameters re-installed.
ACTCFG - ACTUATOR CONFIGURATION
ACTTYP - ACTUATOR TYPE
ACTSIZ - ACTUATOR SIZE
ENCINI - ENCODER INITIALIZATION
SPEED
CPT 20
CPT 4
INTTIM
ADVANC
INFO
ST ACT
AMP ST
TEMP
SW VER
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust Display or
Ouput Torque
LOCREM
Local / Remote Operation
MANJOG
Manual Jog
TORQ/THRSTC
Close Torque/Thrust
TORQ/THRSTO
Open Torque/Thrust
CL ACT
Close Action
OP ACT
Open Action
BASIC
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
CTRCFG
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LO
LOS HI
ACTCFG
RELAYS
R1 CFG
R1 FRM
R2 CFG
R2 POS
ACTTYP
ACTSIZ
ENCINI
SPLTRG
MINCMD
MAXCMD
BSRACT
ASRACT
ASPOS
BSRPOS
UPS
LOP AC
LOP PO
LOP TO
OR REM
OR LOC
OR LST
LOP SP
DEFLTS
LD CUST
ST CUST
LD FACT
R2 FRM
R1 POS
R5 CFG
R5 FRM
R6 CFG
R6 POS
R6 FRM
R5 POS
R7 CFG
R7 FRM
R8 CFG
R8 POS
R8 FRM
R7 POS
COMMS
MODBUS
PROFIBUS
PAKSCAN
HART
FFBUS
COM TO
LOS ACT
LOS PO
MIN SP
MAX SP
D1 CFG
D2 CFG
D2 FRM
D3 CFG
D3 FRM
D4 CFG
D4 FRM
D1 FRM
DIG IN
PRM OC
Primary Option
RI CTL
Remote Control Inputs
2W PRI
2 Wire Priority
LOS AC
RIRO Only
LOS PO
RIRO Only
ESDACT
ESD Action
ESDOLS
ESD Override Local Stop
KNBMNT
Local Maint
CMDSRC
CMD SRCE
INFO
RELAYS
DIG IN
SPLTRG
ACT CFG
UPS
COMMS
CTRCFG
Control Setup
CMDSRC
STL TO
TURNS***
OP DIR***
INTTIM
CL TIE
ST CLS
SP OPN
CL OFF
ST OPN
SP CLS
OP ON
OP OFF
CL ON
OP TIE