background image

 

 

Rotork Fairchild PAX1 Motor Set Pressure 

Regulator 

User’s Manual

 

 

Product Overview 

The PAX1 Motor Set Pressure Regulator is a flexible 
low voltage DC powered linear actuator coupled to 
one of five Fairchild precision pressure regulators 
capable of controlling pressure ranges of 0-0.5 psig to 
0-3000 psig and housed in a flameproof enclosure.  
The unit is inherently lock in last place as the actuator 
will maintains its position upon loss of electrical 
power.  

The PAX1 can be actuated open loop using two 
optically isolated switch closure inputs (Up and Down) 
to change the pressure regulators setpoint.   The PAX1 
will continue to change the pressure regulator 
setpoint in response to the input until either of the 
adjustable range limits are reached.    

The PAX1 has an isolated 4-20 mA control input to 
proportionally control the pressure regulator setpoint.  
There is a 1-5 vdc non isolated control input as well.  
In analog control mode, the unit is fail freeze upon 
loss of either control signals. 

The actuator features UP and DOWN push buttons 
under the cover to facilitate commissioning and to 
permit local control of the 

pressure regulator’s 

setpoint

.  There is an 8mm (5/16”) female hex motor 

drive interface under the cover to allow manual setpoint control in the case of loss of electrical power. 

The actuator includes two fully adjustable 1A, 250VAC SPDT alarm relays (one High and one Low) 
providing alarm function when the pressure regulator output pressure reaches critical values.  The relays 
are magnetically latched so the alarm switch states are maintained when the power is disconnected.  
This allows accurate alarm function on systems that remove power from the actuator between 
adjustments to conserve power as is typically done in solar powered installations.  

The PAX1 offers an optional optically isolated electronic 4-20mA feedback output.  This feedback feature 
is functional for both the pulse control and analog control configurations.  The unit must be powered to 
facilitate the feedback output function. 

 

Summary of Contents for PAX1

Page 1: ...well In analog control mode the unit is fail freeze upon loss of either control signals The actuator features UP and DOWN push buttons under the cover to facilitate commissioning and to permit local c...

Page 2: ...uipment damage serious injury or death Hazardous Area Ratings Flameproof Factory Mutual CSA Class I Division 1 Groups ABCD T6 T5 Class I Division 1 Groups B C D T6 T5 Class II III Division 1 Groups EF...

Page 3: ...tart with the third thread back and work away from the end of the fitting to avoid the possibility of contaminating the regulator Install the regulator in the air line The inlet and outlet connections...

Page 4: ...elays require ferrules supplied to provide proper insulation for the high voltage AC connections Power Supply Sizing For 12 vdc operation the recommended power supply should have 2 amp capacity For 24...

Page 5: ...p Rtn MTR ENAB DN V mA V mA 1 2 3 4 5 6 7 8 9 10 11 12 UP PWR LOOP SUPPLY Figure 1 SW2 Isolation Switch Set to Isolate FEEDBACK Switch set to PULSE Internal connection of NO ISOLATE switch Set to ISOL...

Page 6: ...A 1 2 3 4 5 6 7 8 9 10 11 12 PWR Figure 3 FEEDBACK 4 20 mA CONTROLLER Set switch to ANALOG SW1 Set switch to 4 20 mA Lp Pwr DN UP MTR ENAB V mA V mA 1 2 3 4 5 6 7 8 9 10 11 12 PWR Figure 4 FEEDBACK 1...

Page 7: ...3 4 5 6 7 8 9 10 11 12 PWR Figure 5 FEEDBACK POWER SUPPLY MILLIAMMETER LOOP SUPPLY CLOSED SWITCH DISABLES MOTOR Lp Pwr DN UP MTR ENAB V mA V mA 1 2 3 4 5 6 7 8 9 10 11 12 PWR Figure 6 FEEDBACK POWER...

Page 8: ...parate external power source SW2 NO The Pulse control input circuit is connected to the DC power supply providing power to the unit Push button switches UP Moves the pressure regulator setpoint to a h...

Page 9: ...through the hole in the top PCA cover near the SET button Turning the motor clockwise increases pressure counter clockwise decreases pressure Take care not to drive the actuator into its mechanical s...

Page 10: ...rol current 2 7 Move the SETUP SWITCH to the TRAVEL LIMIT HI setting 2 8 Using the UP and DN buttons under the cover adjust the output pressure to the highest desired pressure 2 9 Apply the desired co...

Page 11: ...o the ALARM SWITCH HI setting 4 5 Using the UP and DN buttons adjust the pressure regulator to its HI ALARM pressure 4 6 Press the SET button and wait for the ALARM HI LED to turn from Green then red...

Page 12: ...d 6 2 Turn the adjustment clockwise to increase the output pressure and counter clockwise to decrease the output pressure 6 3 Take care when manually adjusting the actuator as you can damage the unit...

Page 13: ...AUST 2X M8 MOUNTING HOLES 13 71 348 1 2 69 68 3 1 25 31 8 2 5 63 6 9 37 238 0 3 66 93 0 5 12 130 0 O 0 35 9 0 2X BRACKET MOUNTING HOLES 5 87 149 0 22595 1 MOUNTING BRACKET SOLD SEPARATELY 1 4 18 NPTF...

Page 14: ...87 0 1 25 31 8 2 5 63 6 9 14 232 2 O 5 25 133 4 2X M5 MOUNTING HOLES 14 18 NPTF GAGE PORT 1 2 14 NPTF 1 2 14 BSPT 1 2 14 BSPP 3 4 14 NPTF 3 4 14 BSPT 3 4 14 BSPP INLET OUTLET 1 2 14 NPTF OR 3 4 14 NPT...

Page 15: ...9 284 1 15 26 387 7 8 87 225 3 1 4 18 NPTF GAGE 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST 3 75 95 2 BRACKET 1 2 14 NPTF OR 3 4 14 NPTF CONDUIT PORT M5 GROUND SCREW HOLE 1 18 30 0 1 2 14 NPTF 1 2 14 BSPT 1 2...

Page 16: ...7 10 3 261 7 12 81 325 4 1 18 30 0 0 75 19 0 3 07 78 0 6 07 154 2 O 6 93 175 9 M5 SAFETY SCREW HOLE 1 25 31 8 2 5 63 6 2X M8 x 1 25 MOUNTING HOLES O 1 99 50 5 O 2 12 53 8 8 47 215 2 1 4 18 NPTF INLET...

Page 17: ...07 78 0 1 00 25 3 3 61 91 6 6 157 156 4 11 4 288 4 1 18 30 0 13 86 352 0 6 07 154 2 O 6 93 175 9 2X M8 X 1 25 MOUNTING HOLES 1 4 NPTF OR BSPT INLET OUTLET 1 2 14 NPTF OR 3 4 14 NPTF CONDUIT PORT M5 SA...

Page 18: ...3 6 2X M8 x 1 25 MOUNTING HOLES 3 07 78 0 0 53 13 5 1 4 OR 3 8 NPT OR BSPT INLET OUTLET 4 923 125 0 10 119 257 0 12 625 320 7 1 2 14 NPTF OR 3 4 14 NPTF CONDUIT PORT M5 SAFETY SCREW 1 18 30 0 6 07 154...

Page 19: ...e 11 30VDC Power Consumption 22 watts max 1 watt standby Actuation Electrical Analog Actuation Control 4 20 mA 1500V optically isolated from power supply Switch for common power supply 1 5VDC non isol...

Page 20: ...eed Multi turn pot 1 2 60 mm min Limit adjustments Push button switch to accept current thrust rod position for 2 End of Travel limit 2 Alarm Switch and Analog Feedback Calibration Setup Switch 8 posi...

Page 21: ...Remove the pressure regulator and Thrust Rod Cap exposing the Thrust Rod With the setup knob to the Operate Pulse mode and pressing the Jog Up button extend the thrust rod to its most extended opposi...

Page 22: ...tor Assembly Thrust Rod Thrust Rod Cap Pressure Regulator Mounting Bolts Pressure Regulator Mounting Plate Pressure Regulator Figure 16 OM 100PAX1R REV B 06 18 Actuator O Ring O Ring O Ring Contact Fa...

Reviews: