9.2 Quarterly inspections 

 

Visual inspection of the general conditions of the 
equipment systems as well as the absence of 
leaks; 

 

Inspection of the ventilation filter (see paragraph 
0). 

9.3 Annual inspections 

 

Inspection of the tightness of bolts, nuts, flanges 
and water supply connections that may have been 
loosened by vibration; 

 

Check the state of integrity of the magnesium 
anodes (see paragraph 0). 

9.4 Cleaning of the ventilation filter  

There’s a ventilation filter located in the upper part of 

the equipment. It must be cleaned frequently in 
order to maintain the efficiency of the system.  

Every 1000 hours of operation, the “FiL” alarm appears 

on the display of the equipment. This means that 
you need to check the cleanliness of the filter.  

To remove the filter, grab it with the fingers from the 

appropriate side opening and pull it out (Fig. 20). 

The filter can be cleaned by rinsing, water gush or 

slamming. Since the filter is made of stainless 
steel, it should not be substituted regularly. 

 

 

 

Fig. 20 

– Details of the ventilation filter 

 

 

N.B. 

The filter obstruction reduces the heat pump 

system performance causing insufficient 
or even total lack of ventilation. 

 

9.5 Magnesium anodes 

The magnesium anode (Mg), also "sacrificial" anode, 

avoids any parasitic currents, generated inside the 
boiler, that can trigger corrosion processes on the 
device surface. 

In fact, magnesium is a metal with a lower 

electrochemical potential in comparison to the 
material that coates the inside of the boiler. It 
therefore attracts the negative charges that are 
formed during the heating of the water and would 
cause the boiler t

o corrode. The anode “sacrifices” 

itself by corroding instead of the tank. The boiler 
has two anodes, one in the lower part and one in 
the upper part of the tank (which is also the area 
that is most susceptible to corrosion).  

The integrity of the magnesium anodes should be 

checked at least every two years (but preferably 
annually), by qualified personnel. 

Before performing the inspection, it is necessary to: 

 

Close the cold water input supply; 

 

Remove the water from the boiler (see paragraph 
9.6); 

 

Unscrew the upper anode and check its state of 
corrosion. The anode should be replaced if more 
than 30% of its surface is corroded; 

 

Perform the same operation for the lower anode. 

 

The anodes have appropriate sealing gaskets in 
order to avoid causing water leaks. It is 
recommended to use anaerobic sealant for 
threads compatible for use on sanitary and 
heating systems. In case of inspection, the anodes 
and the gasket sealings must be replaced by new 
ones. 

9.6 Emptying the boiler 

It is advisable to drain the water from the boiler if the 

boiler is idle for a certain period of time, especially 
in low temperatures. 

As for the equipment, it is sufficient to disconnect the 

water supply input connection (see paragraph 0). 

Alternatively, during the system installation stage, it is 

advisable to install a drain tap with a hose-holding 
connection. 

 

 

N.B. 

It is important to empty the system in case of 

low temperatures to avoid that the water 
freezes.  

 

 

 

Ventilation 

filter 

 

Side  

slot

 

 

Summary of Contents for RKHH2E200AAV33

Page 1: ...Installation Manual Installation manual Domestic Hot Water Heat Pump Monobloc type RKHH2E200AAV33 RKHH2E260AAV33 RKHH2E260PAAV33 Domestic Hot Water Heat Pump Monobloc type English...

Page 2: ......

Page 3: ...RKHH2E P AAV33 ROTEX Domestic Hot Water Heat Pump 2018 8 Installation manual 3...

Page 4: ...ing limits 16 5 5 Fundamental safety rules 16 5 6 Information on coolant used 16 6 Installation and connections 17 6 1 Preparation of the installation site 17 6 2 Ventilation connection 17 6 2 1 Parti...

Page 5: ...ead the service manual For more information see the installer and user reference guide 1 2 For the user If you are not sure how to operate the unit contact yourinstaller This appliance can be used by...

Page 6: ...o NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are preferably carried out under dry weather conditions to avoid...

Page 7: ...ssor breakdown do NOT charge more than the specified amount of refrigerant When the refrigerant system needs to be opened refrigerant must be treated according to the applicable legislation WARNING Ma...

Page 8: ...a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure t...

Page 9: ...to the unit Installation manual Instruction manual designed for a certain unit or application explaining how to install configure and maintain it Operation manual Instruction manual designed for a ce...

Page 10: ...able to instructions figures drawings or descriptions without prejudice to errors of any kind The Supplier shall not be held responsible for damages attributable to misuse improper use or as a consequ...

Page 11: ...power etc Version Configuration description RKHH2E200AAV33 RKHH2E260AAV33 Air source heat pump for the production of domestic hot water RKHH2E260PAAV33 Air source heat pump for the production of domes...

Page 12: ...t of a structural nature WARNING The equipment can be transported horizontally only during the last km following the instructions in the section Positions permitted for transporting and handling above...

Page 13: ...160 mm 13 Hermetically sealed rotary compressor 14 Replaceable magnesium anode 15 1 5 kW 230 W Electric heating element 16 Condenser pump discharge line 17 Condenser return 18 Replaceable magnesium a...

Page 14: ...element power kW 1 5 1 5 1 5 Maximum current in HP A 2 4 2 4 2 4 Required overload protections A 16A T fuse 16A automatic switch characteristic C to be expected during installation on power supply sys...

Page 15: ...Mg anode 26x250 mm 1 x Mg anode 26x250 mm 1 x Mg anode 26x400 mm Insulation 50 mm high density polyurethane foam Defrosting Active with Hot Gas valve Dimensions mm H1714xD600xDmax650 H2000xD600xDmax6...

Page 16: ...ate functional monitoring system with alarm functions in order to avoid such damage being caused Moreover it is necessary to arrange for a back up service in case of failure 5 4 Operating limits The a...

Page 17: ...r connection to the condense drain Be available and ready with adequate discharge pipes in case of damage caused to the boiler or actuation of the safety valve or breakage of pipes connections Have co...

Page 18: ...ickness Sound mufflers can be mounted when deemed necessary Fit the pipes the holes in the wall and the connections to the heat pump with vibration damping systems WARNING The simultaneous operation o...

Page 19: ...ersions A B C D E F G mm mm mm mm mm mm mm 650 1714 600 160 1101 795 H I J K L M N mm mm mm mm mm mm mm 70 150 380 195 O P mm mm 337 5 10 6 4 Water supply connections Connect the cold water inlet and...

Page 20: ...rol device of the check valve a safety valve and a device to interrupt the water load Fig 8a N B The drain pipe connected to the equipment for protection against overpressure must be installed sloping...

Page 21: ...n via siphon with water shut off valve 6 5 Solar power system integration Fig 10 is an example of solar power system integration Cold water intake pipe Solar power system pump and accessories Solar co...

Page 22: ...e brown yellow and the water temperature measured by lower thermistor is higher than SP8 the heat pump stops and water is heated by the solar panels The heat pump restarts when the contact stops and t...

Page 23: ...fication plate The commissioning procedure should be completed by following these steps Fill the boiler by connecting the water inlet tap and check for any leaks from gaskets and connections Tighten t...

Page 24: ...Stand by mode In the stand by mode the instrument can automatically switch on at certain time slots and independently enables the anti Legionella and defrosting functions When the equipment is switch...

Page 25: ...een finished the function is automatically disabled and the equipment is automatically restored to the Automatic or Economy mode depending on which one was previously set by the user ANTI LEGIONELLA o...

Page 26: ...keyboard follow this procedure Make sure that no other advanced procedures are in progress Press and hold the and the keys until Loc will appear on the display for 1 second If the keyboard is locked i...

Page 27: ...slot operation in order to avoid malfunctions caused by users 8 1 3 7 Display of the operating status Make sure that the keyboard is not locked paragraph 0 and that no other advanced procedures are in...

Page 28: ...ivation See parameters i0 i1 18 and i9 Switch off the equipment and restart it or disconnect the equipment from the mains power supply Main consequences Compressor will be switched off Defrosting will...

Page 29: ...ngs Make sure that the keyboard is not locked paragraph 0 and that no other advanced procedures are in progress Press and release the key the first available code will appear on the display Press and...

Page 30: ...ures are in progress Press and hold the and keys for 4 seconds PA password will appear on the screen Press and release the key Press and release either the or the key within the next 15 seconds to set...

Page 31: ...the compressor and consequently lead to breakdown of the equipment At every Start up the fan is activated for an amount of time set by parameter C12 1 minute After this amount of time the system meas...

Page 32: ...Lower thermistor calibration CA2 C F 25 0 25 0 0 0 Evaporator thermistor calibration CA3 C F 25 0 25 0 0 0 Thermistor type P0 0 1 1 0 PTC 1 NTC 2 PT1000 Decimal point P1 0 1 1 1 Display decimal point...

Page 33: ...r stopped Evaporator temperature to conclude defrosting procedure only if P4 1 d2 C F 50 0 50 0 3 0 Maximum duration of defrosting procedure d3 min 0 99 8 Automatic defrosting start threshold evaporat...

Page 34: ...for digital input alarm counter reset i9 min 1 999 240 Buzzer enabling u9 0 1 1 0 Buzzer disabled 1 Buzzer enabled Switching on time for Monday Hd1 1 2 1 1 HOn1 HOF1 2 HOn2 HOF2 Switching on time for...

Page 35: ...RKHH2E P AAV33 ROTEX Domestic Hot Water Heat Pump 2018 8 Installation manual 35 Parameter description Code U M Min Max Default Notes 1 ODD 2 EVEN RESERVED E9 0 2 0...

Page 36: ...necessary to Disconnect the device from the mains power supply Remove any air ducts see paragraph 0 Remove the upper cover by undoing the appropriate locking screws Fig 18 Manually reset the tripped...

Page 37: ...ctrochemical potential in comparison to the material that coates the inside of the boiler It therefore attracts the negative charges that are formed during the heating of the water and would cause the...

Page 38: ...regulations WARNING This equipment contains greenhouse fluorinated gas included in the Kyoto protocol The maintenance and disposal operations must only be carried out by qualified personnel INFORMATIO...

Page 39: ...mperature settings of the water heater C 55 Sound power level Lwa indoors in dB dB 53 The water heater is able to work only during off peak hours NO Any specific precautions that shall be taken when t...

Page 40: ......

Page 41: ......

Page 42: ...r im Ausland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani...

Reviews: