4
x
Set-up and installation
C
53
:
– Vertical opening for flue gas outlet
– Opening for supply air inlet into different pressure area possi-
ble.
– Openings must not be installed on opposite walls of the build-
ing
C
63
:
– Connection to a separately approved and marketed flue
gas/supply air system if allowed by national law.
– This allows all other described installation forms to the real-
ised for equipment type C if the conditions of the respective
installation form are met.
– If the dimensions of the system used differ from those
described in this manual (see chap. 4.5.1), a suitable arith-
metical dimensioning verification is required.
– For data on dimensioning calculation, see tab. 15-1.
– Properties and possible applications of the pipe system:
a) Minimum requirements according to chap. 4.5.1 fulfilled
b) Condensate flow into the equipment allowed with single
assignment, not allowed with multiple assignment.
c) Maximum combustion air temperature: 60 °C
d) Maximum allowed flue gas recirculation current under
wind conditions: 10%
C
83
:
– Connection to one or more pieces of equipment to an under-
pressure flue gas system that is part of the building.
– Vertical opening for flue gas outlet
– Air supply feed via associated second pipe
1)
– Opening for supply air inlet into different pressure area possi-
ble.
– Suitable arithmetical dimensioning verification required
because vacuum prevails in the case of the flue gas inlet into
the common air/flue gas system.
– For data on dimensioning calculation, see tab. 15-1.
– Properties and application options of the flue gas system:
a) Minimum requirements according to chap. 4.5.1 fulfilled
(except for pressure class)
b) Condensate flow into the equipment allowed with single
assignment, not allowed with multiple assignment.
C
93
:
– as for C
33
, but
– Connection of the supply air pipe to an existing vertical shaft
(e.g. chimney) that is part of the building.
1)
– The cross-section of this installation shaft must be dimen-
sioned so that the following
minimum distance
must be
maintained
between the external wall of the flue gas line
and the
internal face of the installation shaft
:
– with a rectangular shaft cross-section:
2 cm
– with a round shaft cross-section:
3 cm
.
B
23
:
– Flue gas pipe without flow safeguard - underpressure opera-
tion
– Properties and application options of the flue gas pipe:
a) Minimum requirements according to chap. 4.5.1 fulfilled
– Opening for flue gas outlet to the outside
– Supply air directly from installation room (see chap. 4.2.3)
– If the dimensions of the flue gas pipe differ from those
described in these instructions (see tab. 4-2), a suitable cal-
culated dimensioning verification is required.
– For data on dimensioning calculation, see tab. 15-1.
B
23P
:
– as for B
23
, but underpressure operation
B
33
:
– Connection of more than one piece of equipment to a com-
mon flue gas system (underpressure flue gas shaft)
– Vertical opening for flue gas outlet
– Supply air directly from the installation room (see chap. 4.2.3)
– Suitable arithmetical dimensioning verification required
because vacuum prevails in the case of the flue gas inlet into
the common air/flue gas system.
– For data on dimensioning calculation, see tab. 15-1.
– Parts under overpressure of the connection pipe must be con-
ducted as a concentric pipe system.
B
53
:
– as for B
33
, but connection to associated flue gas pipe
(ROTEX system) including flue gas opening
B
53P
:
– as for B
53
, but overpressure operation
1)
If the air supply pipe was used beforehand as a flue gas pipe or chimney of an
oil or solid fuel furnace, it should be cleaned prior to use as an air supply pipe.
Summary of Contents for GCU compact 315
Page 81: ...13 x Notes 13 Notes...
Page 82: ...13 x Notes...