Rotex 51424 Mounting, Operating, Testing & Maintenance Instructions Download Page 2

 

IM No. : IM/V/0021, Rev. 2 

Date: 06.11.2017 

Page 2 of 6 

 

 
 
 
IDENTIFICATION ON THE SOLENOID VALVE

 

 
a) 

VALVE MARKING 

 

 

Label on the 

ROTEX 

Solenoid Valve shows the following details: 

 

 

(1) 

Logo + Name & address of the Manufacturer 

(2) 

Valve Type / Code 

 

51424 

=  Valve Model 

 

Suffix 

=  Nil 

 

=  Orifice 

 

 

2R  

=  Port Connection 

 

B5 

=  Body Material  

 

M8 

=  Manual Override 

 

S2

 

=  Seal Material 

(3) 

Work Order reference / Sr. No. of the Valve 

(4) 

Operating Pressure 

(5) 

Month & Year of manufacture 

(6) 

Valve Symbol 

(7) 

Media 

 

         (1) 

            

 

 

 

 

ROTEX AUTOMATION LIMITED 
   VADODARA-390010, INDIA 
   FLUID CONTROL SYSTEM 

 

CODE : 51424-6-2R-B5-M8-S2 

 

 

ATM 

2-10 

MEDIA 

AIR 

DATE 

9/2016 

Wo. No. 

16100650/10 

 
  (6)           (2)      (4)      (3)            (5)      (7)     

 

 

 

 

 

 

                      

 

b) 

SOLENOID MARKING 

                               
                             (1) 

            

 

 

ROTEX 

VADODARA 

– 390010, 

INDIA 

 

(1) 
(2) 

Logo + Name of the Manufacturer 
Solenoid Type 
III       
110V  


Solenoid Size III 
Solenoid Voltage 

 

III-110V-DC-25-H 

 

 

DC   

=  Solenoid Current 

16100650-09/16 

 

 

25             

=  Solenoid Construction  

  

 

 

H            =  Solenoid Class H Insulation 

 

 

(3)  Work order No. Manufacturing Month / Year 

 
 

    (2) 

 

     (3) 

 
 
 (B)  

MOUNTING/INSTALLATION PROCEDURE

 

1. 

ENSURE THAT: 
a) 

While storing, keep the valve in cool, dry, dust free area.  

b) 

On  receipt  of  the  valve,  in  case  if  the  same  is  to  be  removed  from  the  sealed  plastic  bag  for 
inspection/testing,  put them back with dust plugs on its ports and sealing the plastic bag as soon as the 
inspection/testing is over. 

c) 

The valve should be removed from its card board and/or plastic bag just before the installation. 

  

d) 

Flush lines before installing the valve. 

         e) 

To  avoid  pressure  drop  and  to  achieve  optimum  parameters,  Pipe  /  Tube  /  Fitting  from  the  source  of 
pressure  to  the  valve  and  to  the  connected  equipment  should  have  ID  which  is 

  NW  (Orifice)  of  the 

valve. 

f) 

To  avoid  pressure  drop,  if  more  than  one  valve  is  being  operated  simultaneously  from  a  common 
header, then minimum ID of the header can be calculated as under. 

        

ID Header =  

 (NW

2

n) 

        

n = Number of Valves operating at a time and which are connected to a common header,  
NW = Orifice of the Valve. 

  

g) 

Incorporate filter in the line to avoid hard particles entering into the valve. 

h)   

Do not try to drill any additional holes or machine, modify any of the valve components.  

i)  

Inlet pressure does not exceed rated pressure. 

j) 

Hemp-

Filaments,  ’Jute’  or  even  Teflon-Ribbons  are  normally  not  required,  as  the  port  connections  of 

ROTEX Valve is accurately machined.  

k) 

Do not cover first two thread pitches with Teflon tape or sealant. To avoid over lap of the Teflon ribbon or 
cuts generated while tightening, getting carried away into the valve.  