3. Wiring Instructions

To wire the P-805 expansion board:

1. Connect the RS-485 communication terminal block to the OSDP/RSDP-bus (serial bus) on the AC-825IP panel.

For more information, see the

AC-825IP Hardware Installation and User Manual

.

2. Connect the 16 inputs and 8 outputs to your various applications.

For RS-485 communication, use a maximum of 1,200 m (4,000 ft) cable length and minimum 22 AWG.

4. Operating the P-805

When a P-805 expansion board is used with a AC-825IP access control panel, it is necessary to define input and

output types from the

Groups

element in the tree view in the AxTraxNG/AxTraxPro Access Control Management

Software. Input and output functions are defined using the

Links

element within each panel tree menu item.

For more information, see the

AxTraxNG User Guide

or the

AxTraxPro Desktop Client User Guide

.

When a P-805 expansion board is used with a AC-825IP access control panel, the unit must be set to installation

mode in the AxTraxNG/AxTraxPro Access Control Management Software as given below .

1. Turn off power.

2. Set all four DIP switches to

ON

.

3. Turn on power.

4. Wait three seconds. In 30 seconds or less set all four DIP switches to

OFF

.

The Transmit Data (TX) LED light blinks red.

RSDP-805 Series Installation Guide

www.rosslaresecurity.com

10

Summary of Contents for D-805 Series

Page 1: ...board is used with Rosslare s AxTraxPro Access Control Management Software the expansion board supports SIA Open Supervised Device Protocol OSDP V2 including OSDP SC secure channel The available RSDP 805 models are R 805 Series 16 Output Expansion Board S 805 Series 16 Input Expansion Board D 805 Series 4 Door Expansion Board P 805 Series 16 Input 8 Output Expansion Board www rosslaresecurity com ...

Page 2: ...orts OSDP RSDP bus S bus Tamper Input from enclosure 4 pin tamper connector Environmental Characteristics Operating Environment Indoor Operating Temp Range 0 C to 50 C 32 F to 122 F Operating Humidity Range 0 to 85 non condensing Physical Characteristics Dimensions H x W x D 178 x 87 x 38 mm 7 0 x 3 4 x 1 5 in Weight 315 g 11 2 oz Relays Characteristics Operation Voltage 12 VDC Operation Current 4...

Page 3: ...from the Groups element in the tree view in the AxTraxNG AxTraxPro Access Control Management Software Output functions are defined using the Links element within each panel tree menu item For more information see the AxTraxNG User Guide or the AxTraxPro Desktop Client User Guide When a R 805 expansion board is used with a AC 825IP access control panel the unit must be set to installation mode in t...

Page 4: ...Inputs 16 Supervised Inputs Voltage 5 VDC maximum voltage RS 485 Communication Ports OSDP RSDP bus S bus Tamper Input from enclosure 4 pin tamper connector Environmental Characteristics Operating Environment Indoor Operating Temp Range 0 C to 50 C 32 F to 122 F Operating Humidity Range 0 to 85 non condensing Physical Characteristics Dimensions H x W x D 178 x 87 x 38 mm 7 0 x 3 4 x 1 5 in Weight 2...

Page 5: ...rom the Groups element in the tree view in the AxTraxNG AxTraxPro Access Control Management Software Input functions are defined using the Links element within each panel tree menu item For more information see the AxTraxNG User Guide or the AxTraxPro Desktop Client User Guide When a S 805 expansion board is used with a AC 825IP access control panel the unit must be set to installation mode in the...

Page 6: ...age RS 485 Communication Port OSDP RSDP bus S bus Tamper Input from enclosure 4 pin tamper connector Environmental Characteristics Operating Environment Indoor Operating Temp Range 0 C to 50 C 32 F to 122 F Operating Humidity Range 0 to 85 non condensing Physical Characteristics Dimensions H x W x D 178 x 87 x 38 mm 7 0 x 3 4 x 1 5 in Weight 268 g 9 5 oz Reader Characteristics Reader Output Voltag...

Page 7: ...nel For more information see the AC 825IP Hardware Installation and User Manual For RS 485 communication use a maximum of 1 200 m 4 000 ft cable length and minimum 22 AWG 4 Operating the D 805 When a D 805 expansion board is used with a AC 825IP access control panel it is necessary to define input and output types from the Groups element in the tree view in the AxTraxNG AxTraxPro Access Control Ma...

Page 8: ...3 Turn on power 4 Wait three seconds In 30 seconds or less set all four DIP switches to OFF The Transmit Data TX LED light blinks red RSDP 805 Series Installation Guide www rosslaresecurity com 8 ...

Page 9: ... COM contacts Form C Relays RS 485 Communication Port OSDP RSDP bus S bus Tamper Input from enclosure 4 pin tamper connector Environmental Characteristics Operating Environment Indoor Operating Temp Range 0 C to 50 C 32 F to 122 F Operating Humidity Range 0 to 85 non condensing Physical Characteristics Dimensions H x W x D 178 x 87 x 38 mm 7 0 x 3 4 x 1 5 in Weight 284 g 10 oz Reader Characteristi...

Page 10: ...types from the Groups element in the tree view in the AxTraxNG AxTraxPro Access Control Management Software Input and output functions are defined using the Links element within each panel tree menu item For more information see the AxTraxNG User Guide or the AxTraxPro Desktop Client User Guide When a P 805 expansion board is used with a AC 825IP access control panel the unit must be set to instal...

Page 11: ...ontained within Rosslare s materials or documentation is intended to provide only general information about products available for purchase from Rosslare Enterprises Ltd and its associated companies Rosslare Reasonable efforts have been made to ensure the accuracy of this information However it might contain typographic errors inaccuracies or omissions that may relate to product descriptions visua...

Reviews: