Rosenberg SupraBox COMFORT 1100H Operating Instructions Manual Download Page 23

Operation and Maintenance Manual for Rosenberg 

 Compact Ventilation Appliance series SupraBox 

Comfort  

 

 

BA 112 BB 11/12/A/SupraBox 1 

 

22

 

 

Check of the gap and gap coverage between wheel and inlet cone 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  The gap S should be constant on the entire perimeter of the wheel.

 

 

  The gap cover R should be about 1 to 2 % of the wheel diameter.

 

7.4.2 Operation 

 

Monitor the fans for correct function during the operation.  Vibrations, pressure 
fluctuations or other deviations from the provided operating parameters should6 be 
checked according to the following chapter. 
 

 

7.4.3 Maintenance and Cleaning 
 

 Monitor the unit operation during the first four to twelve weeks regarding the 
following points: 
 

-

 

Balance, unusual sounds, vibrations 

-

 

Fastening of the fan, the motor and the vibration absorbers 

-

 

For belt driven fans : Belt drive and belt tension

 

 

The fan as a fast rotating device needs regular monitoring as well as a three-month maintenance 
interval. In case of deviations of the standard operation conditions (air temperature, increased dust or 
permanent high humidity) or in case of continuous 24-hours-operation a shorter interval must be 
determined. 

 

Maintenance 

Fan unit 

Every         

3 Months 

If 

necessary 

Hygiene 

inspection 

Check the fan for dirt, mechanical defects, corrosion and 
proper fastening 

 

Check the fan gap  

 

 

Cleaning of the fan incl. impeller 

 

 

Check the impeller for imbalance 

 

 

Check the quiet running and bearing for sounds 

 

 

Picture:  gap of the fan 

Summary of Contents for SupraBox COMFORT 1100H

Page 1: ...ntilatoren GmbH Maybachstra e 1 74653 K nzelsau Gaisbach Tel 49 0 7940 142 0 Fax 49 0 7940 142 125 Email info rosenberg gmbh com www rosenberg gmbh com EN Betriebsanleitung Operating instruction Supra...

Page 2: ...Unit Installation 15 5 2 Assembly 15 5 3 Connection of the ventilation ducts to the unit 16 5 4 Electric Installation 16 5 5 Connection of the condensate exhaust air and overflow pipes 16 6 Startup an...

Page 3: ...12 A SupraBox 1 2 1 General Safety Information 1 1 Warnings regarding industrial safety measures The following icons inform about certain hazards or safe use Attention Danger Safety Advice Hazard by...

Page 4: ...ta specification or can be found on the name plate One single instance of the prescribed power limit being exceeded will inevitably cause damage to the built in components which results in the safe us...

Page 5: ...unit is mounted on a base frame with four adjustable feet for balancing uneven bottoms as well as for the outside installation Adjustment range 45 70 mm The compact housing consists of corrosion resi...

Page 6: ...operating point 2 x 200 W 2 x 310 W 2 x 470 W 2 x 800 W SFP Value In the operating point 900 Ws m 1015 Ws m 1128 Ws m 1440 Ws m SFP class in the operating point SFP2 SFP2 SFP3 SFP3 Heat recovery Effi...

Page 7: ...2 x 1600 W SFP Value In the operating point 1645 Ws m SFP class in the operating point SFP4 Heat recovery Efficiency Reverse flow plate heat exchanger up to 92 corresponding to WRG classes H1 Maximum...

Page 8: ...air M5 7 Condensate pan 2 Panel filter incoming air F7 8 Exhaust fan with EC motor 3 Adjustable rounded base 9 Incoming air fan with EC motor 4 Bypass flap 10 Control box incl control system 5 Mainte...

Page 9: ...erg Compact Ventilation Appliance series SupraBox Comfort BA 112 BB 11 12 A SupraBox 1 8 2 3 Device drawings Suprabox 800 H Condensate drain through the hose sleeve 19 4 x 3 7 Suprabox 1100 H Condensa...

Page 10: ...act Ventilation Appliance series SupraBox Comfort BA 112 BB 11 12 A SupraBox 1 9 Suprabox 1500 H A hose with appropriate hose sleeve is recommended for the condensate drain 19 4 x 3 7 Suprabox 2000 H...

Page 11: ...made for treating air or gaseous media according to the criteria stated below The compact ventilation appliancet is suitable for the conveyance of Clean air low dust or low greasy air Slightly aggres...

Page 12: ...y scope must be checked in accordance with the freight documents Missing parts or damages must be noted immediately on the freight documents and signed by the driver of the transport vehicle 4 2 Trans...

Page 13: ...ing capacity of the material handling equipment must always be checked before loading The fork length of the material handling equipment must be greater than the length of the transport pallet to be p...

Page 14: ...attachment The slings should not have an inclination angle of more than 60 Please note that when lifting the functional part the distribution is usually out of balance This is not visible from outsid...

Page 15: ...y be removed in order to avoid condensation water Open pallets must be covered by tarps Protect the functional parts against pollution e g chips stones wires etc Also the weatherproof functional parts...

Page 16: ...a may not exceed a maximum of 2 Choose an installation space with an unobstructed condensate drain and water trap as well as sufficient gradient of the condensate line The height level between install...

Page 17: ...y a professional electrician may install the electrical connection according to the VDE regulations The connection must properly be made according to the wiring diagram and the configuration scheme Al...

Page 18: ...SupraBox Comfort BA 112 BB 11 12 A SupraBox 1 17 areas against frost Do not connect the spout to the sewage system Alternatively a vacuum trap with non return ball can be used but make sure that ther...

Page 19: ...possible protective film Optical inspection of the unit gaskets for damage Re adjust the hinges of the maintenance doors Close all doors Operational check of the fans Pressure control of the reverse...

Page 20: ...hat it will not be switched on unintentionally This step disconnects the compact unit from the mains with all poles Be aware that the control box will still be hot For maintenance at the control box t...

Page 21: ...deline Please find instructions for the cleaning and hygiene inspection of each functional part of the device below 7 3 Maintenance and Cleaning of the housing and control Please keep to the following...

Page 22: ...he startup of the fans check the heat recovery the heater and the corresponding frost protection if the outside temperature is less than 5 C and operate them if necessary in order to prevent the unit...

Page 23: ...first four to twelve weeks regarding the following points Balance unusual sounds vibrations Fastening of the fan the motor and the vibration absorbers For belt driven fans Belt drive and belt tension...

Page 24: ...chassis rails Make sure that the wiring has been disconnected first For easy cleaning the exhaust fan can also be unlocked and detached at the four points of the vibration absorber The water or the c...

Page 25: ...the maintenance pan X Check the condensate and maintenance pan for dirt X Cleaning of the condensate and maintenance pan X Check the function of the trap and water level Fill in water if necessary X...

Page 26: ...ed final resistance for this filter version is 200 Pa Always replace panel filters completely The filters can be fully incinerated and must be disposed of accordingly Clean the housing bottom before i...

Reviews: