background image

ECFanGrid

TM

 

FG - 1601

Installation, Operation and Maintenance Instructions

©2017 Rosenberg Fans Canada Ltd.

INSTALLATION of CONSTANT VOLUME CONTROL 
SYSTEM 

A  FANGRID  System  requires  the  measurement  of 
negative  Air  Pressure  within  the  Space  in  front  of  the 
Inlet Fans Area. The measurement device consists of ¼” 
nylon  tubing  and  1/8”  nylon  tees  forming  a  circular 
‘Loop’  in  the  interior  of  the  Space.  The  distance  of  the 
circular ‘Loop’ from the Inlet Fan Face Area is calculated 
by the following 
Formula,  where  (a)  and  (b)  represent  the  width  and 
height of the space:      

INTERFACE of the CONTROL SYSTEM 

The  Flow  Control of  the  FANGRID  is  established  by  the 
connection of the circular ‘Loop’ and the ‘Pitot Ring’ on 
each  of  the  Inlet  Cones  to  a  DIFFERENTIAL  PRESSURE 
TRANSDUCER,  which  converts  the  Differential  Pressure 
with 

Calibration Factor (k-factor)

 of the Fan System.  

ELECTRICAL CONNECTIONS 

When  installed,  the  FANGRID  and  optional  Controls 
shall  be  wired  and  electrically  grounded  in  accordance 
with  local  codes  as  well  as  with  the  National  Fire 
Protection  Association  (National  Electrical  Code), 
ANSA/NFPA70 and/or the Canadian Electrical Code CSA 
C22.1.  The  FANGRID  installation  must  have  an 
uninterrupted,  ground  to  minimize  possible  personal 
injury, should any electrical fault occur. Failure to follow 
this  procedure  could  result  in  that  the  Installer  being 
liable for personal injury to others. 

Electrical characteristics of each individual Fan in the 
FANGRID, specifies maximum voltage and amperage 
requirements, for optimum performance. 

Required Line Voltage(s) and/or Control Voltage(s) are 
detailed and specified in the attached APENDIX A, B, C & 
D.   

Pre START-UP Check 

A – Lock-Out Main Power disconnect to the FANGRID, 
prior Module or UnoBox check. 

B – On outlet/discharge side check for visible damage 
resulting from installation. 

C – Check backdraft damper(s) for smooth operation, if 
supplied and move dampers to ensure full range of 
motion. 

D – On inlet side check for damage to inlet cone plate 
and inlet cone. 

E – Rotate the fan wheel(s) by hand and ensure that 
they are properly aligned with inlet cone. 

F – Check VFD sizing and ratings for voltage and 
horsepower. 

G – Check in coming voltage at main disconnect against 

phase to phase on three phase electrical system. – if is 
not within 5% of Fan Nameplate Rating or 2% of phase 

to phase, the condition must be corrected prior to start-

up. 

Summary of Contents for ECFanGrid FG-1601

Page 1: ...ECFanGridTM FG 1601 Installation Operation and Maintenance Instructions 2017 Rosenberg Fans Canada Ltd ECFANGRID MODULE ECFANGRID RETROFIT KIT ECFANGRID UNOBOX ARRAY...

Page 2: ...n 1 ECFanGrid Block Diagram Configuration 2 Safety Considerations 3 Inspection on Arrival 4 Inspection Prior to Installation 5 Installation of Modules and Unoboxes 6 Installation of Constant Volume Co...

Page 3: ...NFIGURATION TYPICAL SYSTEM 1 1 AV 05 12 17 1 0 ROSENBERG CANADA L F ORELLANA May 12 2017 FANGRID TYPICAL CONFIGURATION BLOCK DIAGRAM Power Supplied 460V 33K 60Hz Disconnect Customer Supplied SYSTEM CO...

Page 4: ...r if there is a discrepancy with regard to missing items the Carrier s Bill of Lading should be signed indicating damage and items missing INSPECTION prior to INSTALLATION After all forms of Packaging...

Page 5: ...ANSA NFPA70 and or the Canadian Electrical Code CSA C22 1 The FANGRID installation must have an uninterrupted ground to minimize possible personal injury should any electrical fault occur Failure to f...

Page 6: ...r to the FANGRID 2 Bump start the Fan s in the FANGRID to ensure Fan Rotation is correct if not check motor leads for correct connection 3 Perform start up on AC Motor s which are VFD controlled as sp...

Page 7: ...input signal 11V input resistance 130k PWM frequency 500 Hz PWM amplitude 10V 6 10 V power supply 5 max 6mA short circuit protection 7 Analog 2 GND GND UGND PE 15V 8 0 10V PWM actual value 0 10VDC Per...

Page 8: ...Rosenberg Fans Canada Ltd ECFanGrid Constant Volume or Constant Pressure Schematic EC FANGRID can be setup as a Constant Pressure or Constant Volume System with the combination of a Differential Pres...

Page 9: ...ECFanGridTM FG 1601 Installation Operation and Maintenance Instructions 0 1 2 3 2 4 5 6 7...

Page 10: ...ROTECTIVE FEATURE HAS TRIPPED Under voltage Incoming Voltage is below the tolerance limit of the specified line voltage Check main supply and fusing Failure is automatically reset after the voltage ri...

Page 11: ...or NOT ENOUGH Air Flow RPM of Fan too low Refer to Fan does not run at max speed above Air Flow restricted Check System duct elements filtration dampers duct fittings and size Actual System pressure...

Page 12: ...ngs Isolate Fan immediately Contact Rosenberg Support Fan operating in stall or forbidden flow region Move Operating Point by reducing pressure losses RCD Switch or Fuse tripping Ground Fault or Short...

Page 13: ...d POWER CONTROL WIRING ARCHITECTURE MAIN POWER 460V 3 60Hz DISCONNECT WITH FUSES SYSTEM CONTROL PANEL Operating ON Alarm Main Switch 1 Main Switch 2 Enable ON OFF Cable Entry from bottom of Cabinet 46...