Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
G-2
PARAMETERS AND
DESCRIPTIONS
Table G-1 lists all of the configurable parameters of the transducer block,
indicating the descriptions and index numbers for each parameters.
Table G-1. Transducer Block
Parameters
Parameter
Index Number
Definition
ALERT_KEY
4
ID number of the transmitter–may be used on the host for sorting alarms
BLOCK_ALM
8
Block alarm
COIL_DRIVE_FREQ
35
Frequency at which the coils are being driven (5 or 37.5 Hz)
DAMPING
30
Damping filter value (in seconds)
DENSITY_UNIT
31
Unit code associated with DENSITY_VALUE. Valid values are lb/cubic feet, or
kg/cubic meter
DENSITY_VALUE
75
User entered density value to be used by the transducer block when calculating flow
rate in mass flow units
DIAGNOSTIC_HANDLING
60
On/Off handling for diagnostics
ELECTRODE_MATERIAL
51
Enumerated string indicating flange material of installed flowtube
ELECTRODE_TYPE
52
Enumerated string indicating electrode type of installed flowtube
EP_TRIG_COUNTS
40
Number of EP measurements that must be above the trigger level to set empty pipe
EP_TRIG_LEVELS
41
Empty Pipe Trigger Levels
FLANGE_MATERIAL
54
Enumerated string indicating liner material of installed flowtube
FLANGE_TYPE
53
Enumerated string indicating liner material of installed flowtube
FLOW_TUBE_SERIAL_NUMBER
49
Flow tube serial number from physical tag on flowtube
FLOW_TUBE_TAG
48
Text String Identifier of flowtube
LICENSE_KEY
78
Key/password to enable diagnostic features. Any changes to the licensing will be
shown in the LICENSE_STATUS parameter
LINER_MATERIAL
50
Enumerated string indicating liner material of installed flowtube
LOI_LANG
39
Selects the language to be used in the local display for status and diagnostics
messages
LOW_FLOW_CUTOFF
37
When flow rate is less than this entered value, flow rate output will be set to 0 ft/s
MODE_BLK
5
Mode of the record of the block–contains the actual, target, permitted,
and normal modes
SENSOR_CAL_DATE
25
Date of the last sensor calibration–intended to reflect the calibration of the sensor
SENSOR_CAL_LOC
24
Location of the last sensor calibration–describes the physical location at which the
calibration was performed
SENSOR_CAL_METHOD
23
Method of the last sensor calibration–ISO defines several standard methods of
calibration (This parameter is intended to record that method or if some other method
was used.)
SENSOR_CAL_WHO
26
Name of the person responsible for the last sensor calibration
STATUS_MESSAGE_MFG
61
Used by manufacturing to test groups to simulate status codes
STRATEGY
3
Can be used to help group the blocks (Not checked or processed by the block)
TAG_DESC
2
Static tag–ASCII character string
TUBE_CAL_NO
33
Sensor gain and zero offset number used in flow calculation
(Number entered is locate on physical tag of the sensor.)
TUBE_SIZE
34
Tube Size. See Tube Size for actual line sizes
UPDATE_EVT
7
Update event
Summary of Contents for 8732 Series
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 TOC 6 ...
Page 26: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 2 14 ...
Page 38: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 3 12 ...
Page 92: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 A 8 ...
Page 186: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 H 8 ...
Page 189: ......