![Rosemount 8714D Quick Installation Manual Download Page 3](http://html1.mh-extra.com/html/rosemount/8714d/8714d_quick-installation-manual_1487409003.webp)
Quick Installation Guide
00825-0100-4764, Rev BA
June 2004
Rosemount 8714D
3
S
TEP
1: C
HANGE
T
RANSMITTER
P
ARAMETERS
1. Use the HART Communicator or Local Operator Interface (LOI) to change the
parameters of the transmitter to the following:
Tube Calibration Number:
1000015010000000
Units:
ft/s
Analog Output Range:
20mA = 30.00 ft/s
Analog Output Zero:
4mA = 0 ft/s
Coil Pulse Mode:
6 Hz
2. Set the loop to manual (if necessary).
3. Power down the transmitter.
S
TEP
2: C
ONNECT
W
IRING
AND
P
OWER
U
P
1. Insert one end of the wiring assembly into the 8714D Calibration Standard; wire the
contact end of the wiring assembly to the transmitter. See Figures 1 and 2 on the
following page for detailed instructions regarding 8712D, 8732C, and 8742C.
Rosemount 8712D (Figure 1):
Use the six contact Pin terminal plug-style wiring assembly. Follow the numeric convention
for the 8712D so the plugs match the terminal block.
Rosemount 8732C/8742C (Figure 2):
Use the two black connector-style wiring assembly. (One connector has four contacts, the other
has three.) Remove the electronics side cover (furthest away from the conduit plugs). If you do not
have a LOI, the connectors will be clearly visible on the bottom side of the board.
If you have a LOI, remove the two mounting screws from the LOI assembly and pull the
display assembly away from the connector assembly until the connector assembly on the
back of the board is fully released. Then, plug the calibrator connectors into the appropriate
receptacles.
Figure 1. Rosemount 8712D Terminal Block